SAFTI FIRST -SuperLite I-XL - 20-45 Minute Fire Protective Glazing with Partial Radiant Heat Protection

DOWNLOADS

20-45 minute, CPSC Cat. II, directional clear specialty tempered glazing with partial radiant heat protection.


Category: 088100 | door glass | security glass...

MasterFormat: Door Louvers and Vision Lights | Fire-Rated Glass and Glazing Systems | Fire-Resistant Glazing...



SAFTI FIRST
100 N Hill Drive
Suite 12
Brisbane, CA 94005
Tel: (888) 653-3333
Fax: (415) 824-5900

info@safti.com

https://www.safti.com/

Find a rep/distributor

Request More Info

DOWNLOADS

Related Products

Overview


SuperLite I-XL - 20-45 Minute Fire Protective Glazing with Partial Radiant Heat Protection

20-45 minute, CPSC Cat. II, directional clear specialty tempered glazing with partial radiant heat protection.

Features

  • Patented directional specialty tempered glazing tested without hose stream that provides partial radiant heat protection not available with ceramics.
  • Accepted by the GSA and AHJ’s across the country as an economical and value added alternative to traditional unsafe wired glass and expensive ceramics.
  • Meets the highest human impact safety requirements.
  • Approved for 20 minute applications without limitations.
  • Received a General Approval from the City and County of Los Angeles (RR25655). For a list of AHJs across the US that have approved SuperLite I-XL.
  • Regularly specified for use in urban-wildfire exterior applications and perfect for property line requirements.
  • Available in specialty architectural make-ups.
  • Lifetime warranty.
  • USA manufactured for fast delivery and competitive pricing.

Specifications

  • Thickness: 1/4” (6 mm)
  • Weight: 3.0 lbs./sq.ft.
  • Sound Transmission Rating: STC 28
  • Fire Rating: 20-45 minutes without hose stream.
  • Impact Safety Rating: CPSC 16 CFR 1201 Cat. I and II
  • Solar Heat Gain Coefficient: 0.70 SHGC

Listings and warranty

SuperLite I-XL is listed and labeled by Intertek/Warnock-Hersey Inc. and Underwriters Laboratories, nationally recognized testing laboratories approved by OSHA.


Standards

UL 9, UL 10B, UL 10C, NFPA 80, NFPA 252, NFPA 257, ASTM E152, ASTM E163, ASTM E2074, ASTM E2010-01, CPSC 16 CFR 1201 Cat. II U.S. Pat. No. 5,910,620 This product requires AHJ approval because it does not pass the hose stream portion of the fire test.


See More


Specifications

Fire RatingApplicationMax CV AreaMax CV WMax CV HStops
20 MinutesSteel Doors3,341in²35-1/8”95-1/8”5/8"
20 MinutesSteel Sidelites, Windows and Transoms5,760 in²96"96"5/8"
45 MinutesSteel Doors3,341in²35-1/8”95-1/8”5/8"
45 MinutesSteel Sidelites, Windows and Transoms5,760 in²96"96"5/8"