Mitsubishi Electric HVAC-Proposed - MFZ - M-Series Heat Pumps - Indoor Units (Multi Zone)-0_MFZ-KA12NA

MFZ - M-Series Heat Pumps - Indoor Units (Multi Zone) Model Number: 0_MFZ-KA12NA Floor-mounted indoor unit mounts on the floor or up to 5" above the floor and has front panel access to the filter for ease of cleaning.  It is perfect for difficult areas that may be smaller or don't have usable...


MasterFormat: Central HVAC Equipment | Decentralized Unitary HVAC Equipment | Air-Source Unitary Heat Pumps...



Mitsubishi Electric HVAC-Proposed
3400 Lawrenceville Suwanee Rd.
Suwanee, GA 30024
Tel: (800) 687-1966
Fax: (800) 658-1458

http://www.mehvac.com

Request More Info

DOWNLOADS

Related Products

Overview



MFZ - M-Series Heat Pumps - Indoor Units (Multi Zone) - 0_MFZ-KA12NA

MFZ - M-Series Heat Pumps - Indoor Units (Multi Zone)


Model Number: 0_MFZ-KA12NA

Floor-mounted indoor unit mounts on the floor or up to 5" above the floor and has front panel access to the filter for ease of cleaning.  It is perfect for difficult areas that may be smaller or don't have usable space on the walls. Rated capacities range from 9,000-18,000 Btu/h.


Provides cooling and heating in a wide range of capacities
Standard Hybrid Catechin pre-filter and Anti-allergy Enzyme filters are included with indoor unit
Choice of fan speeds: Low, Medium, High, and Super High; Auto fan speed control also included
Quiet operation
Bottom supply outlet operates in heat mode
Wireless remote controller is included; PAR-21MAA wired remote controller can be installed as an option
Indoor unit powered from outdoor unit using A-Control
Auto restart following a power outage
Unit can be recessed mounted into wall
For use with the MXZ series only




Power Supply Phase, Cycle, Voltage 1 Phase, 60Hz, 208/230V *3
Cooling Rated Capacity 9000 Btu/h (2.64 kW) *1
Heating at 47° F Rated Capacity 10900 Btu/h (3.2 kW) *2
Minimum Circuit Ampacity MCA 1 Ampere
Recommended Fuse/Breaker Size 15 Ampere
Refrigerant Type R410A
Airflow Cooling : DRY 169-205-251-314 CFM (5-6-7-9 m³/min)
Airflow Cooling : WET 163-197-241-303 CFM (5-6-7-9 m³/min)
Sound Pressure Level Heating 40-35-30-25 dB(A)
Sound Pressure Level Cooling 40-35-30-25 dB(A)
Dimensions H x W x D Height 23-5/8 Inches (600 mm)
Dimensions H x W x D Width 27-9/16 Inches (700 mm)
Dimensions H x W x D Depth 7-7/8 Inches (200 mm)
Refrigerant Pipe Size O.D. Gas (Low Pressure) 3/8 Inch (9.52 mm)
Refrigerant Pipe Size O.D. Liquid (High Pressure) 1/4 Inch (6.35 mm)
Field Drainpipe Size O.D. 5/8 Inch (15.88 mm)
Refrigerant Piping Connection Method Indoor / Outdoor Flared / Flared
Operation Conditions - Indoor Intake Air Temperature Cooling - Maximum - DB , WB 90°F (32°C) DB , 73°F (23°C) WB
Operation Conditions - Indoor Intake Air Temperature Cooling - Minimum - DB , WB 67°F (19°C) DB , 57°F (14°C) WB
Operation Conditions - Indoor Intake Air Temperature Heating - Maximum - DB , WB 80°F (27°C) DB, 67°F (19°C) WB
Operation Conditions - Indoor Intake Air Temperature Heating - Minimum - DB , WB 70°F (21°C) DB, 60°F (16°C) WB
Operation Conditions - Indoor Intake Air Temperature Cooling - Minimum - WB 57°F (14°C) WB
Operation Conditions - Indoor Intake Air Temperature Heating - Maximum - DB 80°F (27°C) DB, 67°F (19°C) WB
Operation Conditions - Indoor Intake Air Temperature Heating - Maximum - WB 67°F (19°C) WB
Operation Conditions - Indoor Intake Air Temperature Cooling - Maximum - DB 90°F (32°C) DB
Operation Conditions - Indoor Intake Air Temperature Cooling - Maximum -WB 73°F (23°C) WB
Operation Conditions - Indoor Intake Air Temperature Cooling - Minimum - DB 67°F (19°C) DB
Operation Conditions - Indoor Intake Air Temperature Heating - Minimum - DB 70°F (21°C) DB
Operation Conditions - Indoor Intake Air Temperature Heating - Minimum - WB 60°F (16°C) WB
Operation Conditions - Outdoor Intake Air Temperature Cooling - Maximum - DB , WB 115°F (46°C) DB
Operation Conditions - Outdoor Intake Air Temperature Heating - Maximum - DB , WB 75°F (24°C) DB, 65°F (18°C) WB
Operation Conditions - Outdoor Intake Air Temperature Heating - Minimum - DB , WB 6°F (-14°C) DB, 5°F (-15°C) WB
Operation Conditions - Outdoor Intake Air Temperature Cooling - Maximum - DB 115°F (46°C) DB
Operation Conditions - Outdoor Intake Air Temperature Heating - Maximum - WB 65°F (18°C) WB
Operation Conditions - Outdoor Intake Air Temperature Heating - Minimum - DB 6°F (-14°C) DB
Operation Conditions - Outdoor Intake Air Temperature Heating - Minimum - WB 5°F (-15°C) WB
Operation Conditions - Outdoor Intake Air Temperature Cooling- Minimum - DB 14°F (-10°C) DB
Operation Conditions - Outdoor Intake Air Temperature Heating - Maximum - DB 75°F (24°C) DB
External Finish Munsell 1.0Y 9.2 / 0.2
Voltage Indoor - Outdoor S1-S2 AC 208 / 230V
Voltage Indoor - Outdoor S2-S3 DC 12-24V

Power Supply Phase, Cycle, Voltage 1 Phase, 60Hz, 208/230V *3
Cooling Rated Capacity 12000 Btu/h (3.52 kW) *1
Heating at 47° F Rated Capacity 14400 Btu/h (4.2 kW) *2
Minimum Circuit Ampacity MCA 1 Ampere
Recommended Fuse/Breaker Size 15 Ampere
Refrigerant Type R410A
Airflow Cooling : DRY 177-215-261-321 CFM (5-6-7 m³/min)
Airflow Cooling : WET 170-207-252-309 CFM (5-6-7-9 m³/min)
Sound Pressure Level Cooling 41-36-31-26 dB(A)
Sound Pressure Level Heating 41-36-31-28 dB(A)
Dimensions H x W x D Height 23-5/8 Inches (600 mm)
Dimensions H x W x D Width 27-9/16 Inches (700 mm)
Dimensions H x W x D Depth 7-7/8 Inches (200 mm)
Refrigerant Pipe Size O.D. Gas (Low Pressure) 3/8 Inch (9.52 mm)
Refrigerant Pipe Size O.D. Liquid (High Pressure) 1/4 Inch (6.35 mm)
Field Drainpipe Size O.D. 5/8 Inch (15.88 mm)
Refrigerant Piping Connection Method Indoor / Outdoor Flared / Flared
Operation Conditions - Indoor Intake Air Temperature Cooling - Maximum - DB , WB 90°F (32°C) DB , 73°F (23°C) WB
Operation Conditions - Indoor Intake Air Temperature Cooling - Minimum - DB , WB 67°F (19°C) DB , 57°F (14°C) WB
Operation Conditions - Indoor Intake Air Temperature Heating - Maximum - DB , WB 80°F (27°C) DB, 67°F (19°C) WB
Operation Conditions - Indoor Intake Air Temperature Heating - Minimum - DB , WB 70°F (21°C) DB, 60°F (16°C) WB
Operation Conditions - Indoor Intake Air Temperature Heating - Maximum - WB 67°F (19°C) WB
Operation Conditions - Indoor Intake Air Temperature Heating - Maximum - DB 80°F (27°C) DB, 67°F (19°C) WB
Operation Conditions - Indoor Intake Air Temperature Cooling - Minimum - WB 57°F (14°C) WB
Operation Conditions - Indoor Intake Air Temperature Heating - Minimum - WB 60°F (16°C) WB
Operation Conditions - Indoor Intake Air Temperature Heating - Minimum - DB 70°F (21°C) DB
Operation Conditions - Indoor Intake Air Temperature Cooling - Minimum - DB 67°F (19°C) DB
Operation Conditions - Indoor Intake Air Temperature Cooling - Maximum -WB 73°F (23°C) WB
Operation Conditions - Indoor Intake Air Temperature Cooling - Maximum - DB 90°F (32°C) DB
Operation Conditions - Outdoor Intake Air Temperature Cooling - Maximum - DB , WB 115°F (46°C) DB
Operation Conditions - Outdoor Intake Air Temperature Heating - Maximum - DB , WB 75°F (24°C) DB, 65°F (18°C) WB
Operation Conditions - Outdoor Intake Air Temperature Heating - Minimum - DB , WB 6°F (-14°C) DB, 5°F (-15°C) WB
Operation Conditions - Outdoor Intake Air Temperature Heating - Maximum - DB 75°F (24°C) DB
Operation Conditions - Outdoor Intake Air Temperature Cooling- Minimum - DB 14°F (-10°C) DB
Operation Conditions - Outdoor Intake Air Temperature Heating - Minimum - WB 5°F (-15°C) WB
Operation Conditions - Outdoor Intake Air Temperature Heating - Minimum - DB 6°F (-14°C) DB
Operation Conditions - Outdoor Intake Air Temperature Heating - Maximum - WB 65°F (18°C) WB
Operation Conditions - Outdoor Intake Air Temperature Cooling - Maximum - WB 115°F (46°C) DB
Operation Conditions - Outdoor Intake Air Temperature Cooling - Maximum - DB 115°F (46°C) DB
External Finish Munsell 1.0Y 9.2 / 0.2
Voltage Indoor - Outdoor S2-S3 DC 12-24V
Voltage Indoor - Outdoor S1-S2 AC 208 / 230V

Power Supply Phase, Cycle, Voltage 1 Phase, 60Hz, 208/230V *3
Cooling Rated Capacity 18000 Btu/h (5.28 kW) *1
Heating at 47° F Rated Capacity 21600 Btu/h (6.3 kW) *2
Minimum Circuit Ampacity MCA 1 Ampere
Recommended Fuse/Breaker Size 15 Ampere
Refrigerant Type R410A
Airflow Cooling : DRY 251-279-325-394 CFM (7-8-9 m³/min)
Airflow Cooling : WET 241-269-313-379 CFM (7-8-9-11 m³/min)
Sound Pressure Level Heating 47-42-38-35 dB(A)
Sound Pressure Level Cooling 46-42-38-35 dB(A)
Dimensions H x W x D Height 23-5/8 Inches (600 mm)
Dimensions H x W x D Width 27-9/16 Inches (700 mm)
Dimensions H x W x D Depth 7-7/8 Inches (200 mm)
Refrigerant Pipe Size O.D. Gas (Low Pressure) 1/2 Inch (12.7 mm)
Refrigerant Pipe Size O.D. Liquid (High Pressure) 1/4 Inch (6.35 mm)
Field Drainpipe Size O.D. 5/8 Inch (15.88 mm)
Refrigerant Piping Connection Method Indoor / Outdoor Flared / Flared
Operation Conditions - Indoor Intake Air Temperature Cooling - Maximum - DB , WB 90°F (32°C) DB , 73°F (23°C) WB
Operation Conditions - Indoor Intake Air Temperature Cooling - Minimum - DB , WB 67°F (19°C) DB , 57°F (14°C) WB
Operation Conditions - Indoor Intake Air Temperature Heating - Maximum - DB , WB 80°F (27°C) DB, 67°F (19°C) WB
Operation Conditions - Indoor Intake Air Temperature Heating - Minimum - DB , WB 70°F (21°C) DB, 60°F (16°C) WB
Operation Conditions - Indoor Intake Air Temperature Cooling - Maximum - DB 90°F (32°C) DB
Operation Conditions - Indoor Intake Air Temperature Cooling - Maximum -WB 73°F (23°C) WB
Operation Conditions - Indoor Intake Air Temperature Cooling - Minimum - DB 67°F (19°C) DB
Operation Conditions - Indoor Intake Air Temperature Heating - Minimum - DB 70°F (21°C) DB
Operation Conditions - Indoor Intake Air Temperature Heating - Minimum - WB 60°F (16°C) WB
Operation Conditions - Indoor Intake Air Temperature Cooling - Minimum - WB 57°F (14°C) WB
Operation Conditions - Indoor Intake Air Temperature Heating - Maximum - DB 80°F (27°C) DB, 67°F (19°C) WB
Operation Conditions - Indoor Intake Air Temperature Heating - Maximum - WB 67°F (19°C) WB
Operation Conditions - Outdoor Intake Air Temperature Cooling - Maximum - DB , WB 115°F (46°C) DB
Operation Conditions - Outdoor Intake Air Temperature Heating - Maximum - DB , WB 75°F (24°C) DB, 65°F (18°C) WB
Operation Conditions - Outdoor Intake Air Temperature Heating - Minimum - DB , WB 6°F (-14°C) DB, 5°F (-15°C) WB
Operation Conditions - Outdoor Intake Air Temperature Cooling - Maximum - DB 115°F (46°C) DB
Operation Conditions - Outdoor Intake Air Temperature Cooling - Maximum - WB 115°F (46°C) DB
Operation Conditions - Outdoor Intake Air Temperature Heating - Maximum - WB 65°F (18°C) WB
Operation Conditions - Outdoor Intake Air Temperature Heating - Minimum - DB 6°F (-14°C) DB
Operation Conditions - Outdoor Intake Air Temperature Heating - Minimum - WB 5°F (-15°C) WB
Operation Conditions - Outdoor Intake Air Temperature Cooling- Minimum - DB 14°F (-10°C) DB
Operation Conditions - Outdoor Intake Air Temperature Heating - Maximum - DB 75°F (24°C) DB
External Finish Munsell 1.0Y 9.2 / 0.2
Voltage Indoor - Outdoor S1-S2 AC 208 / 230V
Voltage Indoor - Outdoor S2-S3 DC 12-24V