Owens Corning World Headquarters
One Owens Corning Parkway
Toledo, OH 43659
Toll-Free: (800) GET-PINK
Web site: www.owenscorning.com
Description & Uses
-
Owens Corning EnDuraGold™ fiber glass duct board is a rigid, resin-bonded
fibrous glass boards with a tough, damage-resistant, flame-retardant, reinforced
aluminum foil (FRK) facing. When fabricated into duct systems, it combines excellent
thermal and acoustical insulating properties with substantially airtight transmission
of air when all joints are sealed with UL 181A listed closures.
-
EnDuraGold™ fiber glass duct board features a durable airstream
surface that isolates the glass fiber substrate from the airstream and inhibits
penetration of the insulation by dirt, dust and other pollutants. This durable
airstream surface makes it easier to clean the duct system using methods and
equipment described in North American Insulation Manufacturers Association (NAIMA)
Publication AH122, Cleaning Fibrous Glass Insulated Duct Systems, Recommended
Practice.
-
EnDuraGold™ fiber glass duct board may be used to fabricate components
for indoor commercial and residential heating, ventilating and air conditioning
duct systems operating at static pressures to ±2 in. w.g. (500 Pa), internal
air temperatures 40°F (4°C) to 250°F (121°C) and air velocities
to 6,000 fpm (30.5 m/s).
-
Straight duct sections, elbows, tees, offsets and other system elements
can be quickly and easily fabricated and assembled into a complete air transmission
system using these lightweight, thermally efficient boards.
Features & Benefits
- An EPA registered biocide in the fiberglass
mat protects the air stream surface from microbial growth and meets requirements
of ASTM C 1338, ASTM G 21
(fungi test) and ASTM G 22 (bacteria test).
- Thermal/acoustical insulation board
plus jacket forms a single component duct system. This reduces inspection
time and the chance of uninsulated duct
system
components.
- R-values as published for EnDuraGold™ fiberglass duct board
are superior to those of compressible insulation of equal thickness. Factory
control of
thickness assures that installed R-values will be as published for the product.
- Duct
systems built with these boards absorb fan and air turbulence noise; reduce
popping noises caused by expansion, contraction and vibration. Fabrication
and
installation are quieter.
- These lightweight boards are easier to transport
and handle than insulated sheet metal ducts. They reduce the load imposed
on the structure by the duct
systems.
- Closures with UL 181A listed pressure-sensitive tape, heat-activated
tape, or glass fabric and mastic virtually eliminate air leakage. This
saves energy and
eliminates the need for system over design.
- Meets the following model codes
and most other applicable codes: NFPA 90A/90B, ICC International Mechanical
Code, SBCCI, ICBO, BOCA, CABO, Corps
of Engineers
Guide Spec., NYC MEA #186-69.
- Proper fabrication and installation guidelines
help ensure long-term performance of the system. These standards, developed
by NAIMA and SMACNA,
lead to clearer
understanding between specifier and contractor.
Availability
EnDuraGold™ fiberglass duct board is available in the following forms::
TYPE 475 |
1" (25mm) |
TYPE 800 |
1" (25mm) |
TYPE 800 |
1 1/2" (38mm) |
TYPE 1400 |
2" (51mm) |
Type designates board stiffness defined by flexural rigidity. Type selection
depends on duct size, pressure and reinforcement schedule. The 11/2" (38
mm) thickness provides superior thermal value.
Physical
Property Data |
Property |
Test Method |
Value |
Operating temperature limits |
UL 181 |
Internal: 250 °F (121 °C)
External: 150 °F (66 °C) |
Maximum air velocity |
UL 181 Erosion Test |
6,000 fpm (30.5 m/s) |
Static pressure limit |
UL 181 |
±2 in. w.g. (500 Pa) |
Water vapor sorption |
ASTM C 1104 |
<3% by weight at 120 °F (49
°C), 95% R.H. |
Mold growth
Fungi resistance
Bacteria resistance |
UL 181
ASTMG 21
ASTMG 22 |
Meets requirements
Meets requirements
Meets requirements |
Surface burning
characteristics |
UL 723* |
Flame spread 25*
Smoke developed 50 |
Fire retardancy |
UL 181 |
Flame penetration: 30 min. |
The surface burning characteristics of these products have been
determined in accordance with UL 723. This standard should be used to measure
and describe the properties of materials, products or assemblies in response
to heat and flame under controlled laboratory conditions and should not be
used to describe or appraise the fire hazard or fire risk of materials, products
or assemblies under actual fire conditions. However, results of this test may
be used as elements of a fire risk assessment which takes into account all
of the factors which are pertinent to an assessment of the fire hazard of a
particular end use. Values are reported to the nearest 5 rating. |