Knauf Friendly Feel® Duct Wrap with ECOSE Technology and KwikStretch® Markings is a thermal and acoustical insulation blanket made from highly resilient, inorganic glass fibers bonded by a thermosetting resin. It is available unfaced, with a foil-scrim-kraft (FSK) jacket and with a white or black metalized polypropylene-scrim-kraft (PSK) jacket. Vapor retarders provide a 2" (51 mm) staple flange on one edge, and the factory-applied facing assures uniform quality. KwikStretch Markings on the staple flange allow for easy and accurate job site measurements.
ECOSE Technology is a revolutionary new binder chemistry that makes Knauf Insulation products even more sustainable than ever. It is based on rapidly renewable bio-based materials rather than nonrenewable petroleum-based chemicals traditionally used in fiber glass insulation products. ECOSE Technology reduces binder embodied energy and does not contain phenol, formaldehyde, acrylics or artificial colors.
Knauf Friendly Feel® Duct Wrap with ECOSE Technology is used as external insulation on commercial or residential heating or air conditioning ducts. It is suitable for the exterior of rectangular or round sheet metal ducts and spaces or surfaces where temperature and condensation must be controlled.
- Low "k" factor significantly reduces heat gain or loss when applied with proper compression
- Flexible
- Lightweight
- KwikStretch marketings on the staple flanges
- Excellent acoustical properties
- Tough and resilient
- Certified for indoor air quality as a low emitting product by The GREENGUARD Environmental Institute to both the GREENGUARD Certification ProgramSM and the more stringent GREENGUARD Children and SchoolsSM standard
- Energy conservation, which lowers operating costs
- System efficiency increases; energy usage/costs decrease
- Conforms easily to flat or irregular surfaces
- Rolls allow for faster installation, lower labor costs
- Easier, faster measurement of stretch-out lengths
- Reduces sound transmission through the duct wall
- Assured condensation control when used with proper installations and sealed joints, seams and penetrations
- Resists damage in shipment, and during and after installation
- Carbon negative: meaning Knauf insulation products used for thermal insulating purposes recover the energy that it took to make them in just hours or a few days, depending on the application. Once installed, the product continues to save energy and reduce carbon generation as long as it is in place
- Contains three primary ingredients:
- Sand, one of the world's most abundant and renewable resources
- Post-consumer recycled bottle glass
- ECOSE Technology which reduces binder embodied energy by up to 70%
- ASTM C 1139 unfaced; Type I, Type II,
- Grade 1 0.75 lb/ft3
- Grade 2 1.0 lb/ft3
- Grade 3 1.5 lb/ft3
- ASTM C 553; Type I, II, III
- ASTM C 1136; Type II
- ASTM C 1290
- GREENGUARD Children and SchoolsSM
- Certification
- California Title 24 (installed at 25% compression)
- HH-I-558C; Form B, Type I, Class 7
- NFPA 90A and 90B
- CAN/ULC S102-M88
- CAN/CGSB-51.5M; Type II (FSK facing)
- CAN/CGSB-51.11-92
- UL/ULC Classified (FSK)
- Unfaced or composite (insulation, facing and adhesive) does not exceed 25 Flame Spread, 50 Smoke Developed when tested in accordance with ASTM E 84 (PSK only), CAN/ULC S102-M88, NFPA 255 and UL 723
- Faced—up to 250°F (1221°C); Unfaced—up to 350°F (177°C)
- Less than 5% by weight when tested for 96 hours at 120°F (49°C) and 95% relative humidity
- FSK and white PSK facings—maximum .02 perms
- Black PSK facing—maximum .09 perms
- Does not accelerate corrosion on steel, copper or aluminum
- The corrosion rate in mils/yr will not exceed that of 1 ppm chloride solution
|
.75 PCF Duct Wrap |
Insertion Loss, dB/LF of Duct |
Duct Dimensions |
Nominal Thickness |
63Hz |
125Hz |
250Hz |
500Hz |
1000Hz |
2000Hz |
4000Hz |
12" × 12" |
1 1/2" |
.6 |
.6 |
.6 |
.7 |
7.4 |
14.2 |
20.9 |
24" × 12" |
1 1/2" |
.6 |
.6 |
.6 |
.7 |
7.4 |
14.2 |
20.9 |
48" × 12" |
1 1/2" |
.5 |
.5 |
.5 |
.6 |
7.4 |
14.1 |
20.9 |
24" × 24" |
1 1/2" |
.5 |
.5 |
.5 |
.6 |
7.4 |
14.1 |
20.9 |
24" × 12" |
1 1/2" |
.8 |
.8 |
.8 |
.8 |
7.5 |
14.2 |
21.0 |
24" × 8" |
2" |
1.0 |
1.0 |
1.0 |
1.0 |
10.4 |
17.1 |
23.9 |
Sound and vibration design and analysis, National Environmental Balancing Bureau, 1994
Density |
Thickness |
Out-of-Package
R-Value |
Installed R-Value
(@ 25% Compression) |
.75 PCF |
1 1/2" |
5.1 |
4.2 |
.75 PCF |
2" |
6.8 |
5.6 |
.75 PCF |
2 3/16" |
7.4 |
6.0 |
.75 PCF |
2 1/2" |
8.5 |
7.0 |
.75 PCF |
3" |
10.2 |
8.4 |
1.0 PCF |
1 1/2" |
5.6 |
4.5 |
1.0 PCF |
2" |
7.4 |
6.0 |
1.5 PCF |
1 1/2" |
6.1 |
4.8 |
1.5 PCF |
2" |
8.2 |
6.4 |
Mean Temperature |
Mean Temperature (SI) |
.75 PCF
k |
.75 PCF
k (SI) |
1.0 PCF
k |
1.0 PCF
k (SI) |
1.5 PCF
k |
1.5 PCF
k (SI) |
50°F |
10°C |
.28 |
.040 |
.26 |
.037 |
.23 |
.033 |
75°F |
24°C |
.29 |
.042 |
.27 |
.039 |
.24 |
.035 |
100°F |
38°C |
.31 |
.045 |
.29 |
.042 |
.26 |
.037 |
125°F |
52°C |
.33 |
.048 |
.31 |
.045 |
.28 |
.040 |
150°F |
66°C |
.36 |
.052 |
.34 |
.049 |
.31 |
.045 |
175°F |
80°C |
.39 |
.056 |
.37 |
.053 |
.33 |
.048 |
200°F |
93°C |
.43 |
.063 |
.40 |
.058 |
.36 |
.052 |
Knauf Insulation products with ECOSE Technology are certified for indoor air quality as a low emitting product by The GREENGUARD Environmental Institute to both the GREENGUARD Certification ProgramSM and the more stringent GREENGUARD for Children and SchoolsSM standard. http://www.greenguard.org/
Use of this product may help building projects meet green building standards as set by the Leadership in Energy and Environmental Design (LEED) Green Building Rating System.
- MR Credit 4.1 – 4.2 Recycled Content
- MR Credit 5.1 – 5.2 Regional Materials
- ID Credit 1 GREENGUARD For Children & Schools
Density |
Thickness |
Width |
Length |
Facing |
.75 PCF
(12 kg/m3) |
11/2" (38 mm) |
48" (1219 mm) |
100' (30.48 m) |
FSK, Unfaced,
PSK |
2" (51 mm) |
75' (22.86 m) |
23/16" (56 mm) |
75' (22.86 m) |
21/2" (64 mm) |
75' (22.86 m) |
3" (76 mm) |
50' (15.24 m) |
1.0 PCF
(16 kg/m3) |
11/2" (38 mm) |
48" (1219 mm) |
100' (30.48 m) |
2" (51 mm) |
75' (22.86 m) |
1.5 PCF
(24 kg/m3) |
11/2" (38 mm) |
48" (1219 mm) |
75' (22.86 m) |
2" (51 mm) |
50' (15.24 m) |
Labeled
Thickness |
Installed
(25% Compression)
Thickness |
Round |
Square |
Rectangular |
1 1/2" (38 mm) |
1 1/8" (29 mm) |
P+9 1/2" (241 mm) |
P+8" (203 mm) |
P+7" (178 mm) |
2" (51 mm) |
1 1/2" (38 mm) |
P+12" (305 mm) |
P+10" (254 mm) |
P+8" (203 mm) |
2 3/16" (56 mm) |
1 5/8" (42 mm) |
P+13" (330 mm) |
P+11" (279 mm) |
P+8 1/2" (216 mm) |
2 1/2" (64 mm) |
1 7/8" (48 mm) |
P+141/2" (368 mm) |
P+12 1/2" (318 mm) |
P+9 1/2" (241 mm) |
3" (76 mm) |
2 1/4" (57 mm) |
P+17" (432 mm) |
P+14 1/2" (368 mm) |
P+11 1/2" (292 mm) |
P=Duct Perimeter
Knauf Insulation GmbH
One Knauf Drive
Shelbyville, IN 46176
Toll Free: (800) 825-4434
Tel: (317) 398-4434
Fax: (317) 398-3675
E-mail: info.us@knaufinsulation.com