Smoke Guard - Model 2100 Fire and Smoke Curtain

DOWNLOADS
This vertically deploying fire and smoke rated curtain is an economical choice for openings. This solution works well for atrium separation, openings in walls, and for specialty enclosures where fire-rated protection is required in areas which do not require egress in an emergency. System Rating...

Category: 2 hour smoke curtains | two hour smoke curtains

MasterFormat: Smoke Containment Barriers



Smoke Guard
287 N. Maple Grove
Boise, ID 83704
Tel: (800) 574-0330
Fax: (208) 639-7851

info@smokeguard.com

http://www.smokeguard.com

Find a rep/distributor

Request More Info

DOWNLOADS

Related Products

Overview



Model 2100 Fire and Smoke Curtain

Model 2100 Fire and Smoke Curtain

This vertically deploying fire and smoke rated curtain is an economical choice for openings. This solution works well for atrium separation, openings in walls, and for specialty enclosures where fire-rated protection is required in areas which do not require egress in an emergency.

System Rating

The M2100 system is 2 hour (120 minute) fire endurance rated complying with the UL 10D standard and listed by Intertek Laboratories. The M2100 | Fire + Smoke system is also listed as compliant with the UL 1784 standard for smoke and draft control assemblies as defined in NFPA 105.

Opening sizes

≤ 16' wide by ≤ 12' tall

Housing dimensions

6.5” wide x 6.5” tall

Unit electrical control

System controls are listed in accordance with UL 864 for releasing devices. External control box mounted outside of the unit, may be mounted up to 50 conduit feet away.

Emergency power source

Each unit has a battery that can power the unit for up to 18 hours on loss of primary power. Emergency power source will take over automatically if primary AC power is disrupted.