Mitsubishi Electric HVAC-Proposed - PLA - M-Series Heat Pumps - Indoor Units (Multi Zone)-0_PLA-A18BA4

Mitsubishi Electric HVAC-Proposed-PLA - M-Series Heat Pumps - Indoor Units (Multi Zone)-0_PLA-A18BA4


MasterFormat: Central Cooling Equipment | Decentralized HVAC Equipment | Decentralized Unitary HVAC Equipment...



Mitsubishi Electric HVAC-Proposed
3400 Lawrenceville Suwanee Rd.
Suwanee, GA 30024
Tel: (800) 687-1966
Fax: (800) 658-1458

http://www.mehvac.com

Request More Info

DOWNLOADS

Related Products

Overview



PLA - M-Series Heat Pumps - Indoor Units (Multi Zone) - 0_PLA-A18BA4

PLA - M-Series Heat Pumps - Indoor Units (Multi Zone)


Model Number: 0_PLA-A18BA4

Ceiling-recessed ductless heat pumps - 33x33". Rated capacity range 12,000 - 42,000 Btu/h.


Branch duct capability
Built-in drain lift mechanism for condensate removal; lifts to 33-7/16"
Wide air flow pattern for better air distribution
Auto wave airflow in heating mode—unit independently cycles through horizontal and vertical positions for more even heat distribution
Independent vane adjustment
Automatic fan speed control
Self-check function—integrated diagnostics
Advanced microprocessor control
Multiple controller options
Limited warranty: five years on parts/defects, seven years on compressors




Power Supply Phase, Cycle, Voltage 1 Phase, 60Hz, 208/230V *4
Cooling Rated Capacity 18000 Btu/h (5.28 kW) *1
Cooling Capacity Range 8000 - 18000 Btu/h (2.3 - 5.3 kW)
Cooling Total Input 1940 W (1.900 kW)
Cooling Energy Efficiency SEER 14.2
Cooling Sensible Heat Factor 0.81
Cooling EER 9.3
Cooling Moisture Removal Pints/H 3
Heating at 47° F Rated Capacity 19000 Btu/h (5.6 kW) *2
Heating at 47° F Capacity Range 8000 - 20000 Btu/h (2.3 - 5.9 kW)
Heating at 47° F Total Input 1900 W
Heating at 47° F HSPF (Region IV) 9.8
Heating at 47° F COP 2.9 Btu/Btu
Heating at 17° F COP 2.4 Btu/Btu
Heating at 17° F Rated Capacity 13000 Btu/h (3.8 kW) *3
Heating at 17° F Total Input 1590 W
Minimum Circuit Ampacity MCA 1 Ampere
Maximum fuse size (time delay) MOCP 15 Ampere
Refrigerant Type R410A
Fan Fan motor output - kW 0.05 kW
Fan Fan(drive) x No. Turbo fan (direct) x 1
Fan Fan Motor - F.L.A. 0.51 F.L.A
External Static Pressure 0 (direct blow)
Airflow DRY 12-14-16-18 CFM (420-490-570-640 m³/min)
Airflow WET 11-13-15-17 m³/min (390-460-530-600 CFM)
Sound Pressure Level 28-29-31-32 dB(A)
Dimensions H x W x D Height UNIT : 258 Inches (10-3/16 mm) ; PANEL : 35 Inches (1-3/8 mm)
Dimensions H x W x D Width UNIT : 840 Inches (33-1/16 mm) PANEL : 950 Inches (37-3/8 mm)
Dimensions H x W x D Depth UNIT : 840 Inches (33-1/16 mm) PANEL : 950 Inches (37-3/8 mm)
Field Drainpipe Size O.D. 1-1/4 Inches (32 mm)
Refrigerant Piping Connection Method Indoor / Outdoor Flared / Flared
Operation Conditions - Indoor Intake Air Temperature Cooling - Maximum - DB , WB 95°F (35°C) DB, 71°F (22°C) WB
Operation Conditions - Indoor Intake Air Temperature Cooling - Minimum - DB , WB 67°F (19°C) DB, 57°F (14°C) WB
Operation Conditions - Indoor Intake Air Temperature Heating - Maximum - DB , WB 80°F (27°C) DB, 67° (19°C) WB
Operation Conditions - Indoor Intake Air Temperature Heating - Minimum - DB , WB 70°F (21°C DB, 60°F (16°C) WB
Operation Conditions - Indoor Intake Air Temperature Cooling - Maximum - DB 95°F (35°C) DB
Operation Conditions - Indoor Intake Air Temperature Cooling - Maximum -WB 71°F (22°C) WB
Operation Conditions - Indoor Intake Air Temperature Cooling - Minimum - DB 67°F (19°C) DB
Operation Conditions - Indoor Intake Air Temperature Cooling - Minimum - WB 57°F (14°C) WB
Operation Conditions - Indoor Intake Air Temperature Heating - Maximum - DB 80°F (27°C) DB
Operation Conditions - Indoor Intake Air Temperature Heating - Maximum - WB 67° (19°C) WB
Operation Conditions - Indoor Intake Air Temperature Heating - Minimum - DB 70°F (21°C) DB
Operation Conditions - Indoor Intake Air Temperature Heating - Minimum - WB 60°F (16°C) WB
Operation Conditions - Outdoor Intake Air Temperature Cooling - Maximum - DB , WB 115°F (46°C) DB
Operation Conditions - Outdoor Intake Air Temperature Heating - Maximum - DB , WB 70°F (21°C) DB, 59°F (15°C) WB
Operation Conditions - Outdoor Intake Air Temperature Heating - Minimum - DB , WB 12°F (-11°C) DB, 10°F (-12°C) WB
Operation Conditions - Outdoor Intake Air Temperature Cooling - Maximum - DB 115°F (46°C) DB
Operation Conditions - Outdoor Intake Air Temperature Cooling - Maximum - WB 115°F (46°C) DB
Operation Conditions - Outdoor Intake Air Temperature Cooling- Minimum - DB 0°F** (-18°C) DB
Operation Conditions - Outdoor Intake Air Temperature Heating - Maximum - DB 70°F (21°C) DB
Operation Conditions - Outdoor Intake Air Temperature Heating - Maximum - WB 59°F (15°C) WB
Operation Conditions - Outdoor Intake Air Temperature Heating - Minimum - DB 12°F (-11°C) DB
Operation Conditions - Outdoor Intake Air Temperature Heating - Minimum - WB 10°F (-12°C) WB
External Finish Munsell 6.4Y 8.9/0.4
Heat Exchanger Plate fin coil
Voltage Indoor - Outdoor S1-S2 AC 208 / 230V
Voltage Indoor - Outdoor S2-S3 DC 12-24V

Power Supply Phase, Cycle, Voltage 1 Phase, 60Hz, 208/230V *4
Cooling Rated Capacity 24000 Btu/h (7.03 kW) *1
Cooling Capacity Range 12000 - 24000 Btu/h (3.5 - 7 kW)
Cooling Total Input 2500 W (2.500 kW)
Cooling Energy Efficiency SEER 13.6
Cooling Sensible Heat Factor 0.76
Cooling EER 9.6
Cooling Moisture Removal Pints/H 5.1
Heating at 47° F Rated Capacity 26000 Btu/h (7.6 kW) *2
Heating at 47° F Capacity Range 12000 - 28000 Btu/h (3.5 - 8.2 kW)
Heating at 47° F Total Input 2570 W
Heating at 47° F HSPF (Region IV) 8.5
Heating at 47° F COP 2.9 Btu/Btu
Heating at 17° F COP 2.14 Btu/Btu
Heating at 17° F Rated Capacity 16000 Btu/h (4.7 kW) *3
Heating at 17° F Total Input 2200 W
Minimum Circuit Ampacity MCA 1 Ampere
Maximum fuse size (time delay) MOCP 15 Ampere
Refrigerant Type R410A
Fan Fan motor output - kW 0.05 kW
Fan Fan(drive) x No. Turbo fan (direct) x 1
Fan Fan Motor - F.L.A. 0.51 F.L.A
External Static Pressure 0 (direct blow)
Airflow DRY 420-490-570-640 CFM (12-14-16-18 m³/min)
Airflow WET 390-460-530-600 CFM (11-13-15-17 m³/min)
Sound Pressure Level 28-29-31-32 dB(A)
Dimensions H x W x D Height UNIT : 258 Inches (10-3/16 mm) ; PANEL : 35 Inches (1-3/8 mm)
Dimensions H x W x D Width UNIT : 840 Inches (33-1/16 mm) PANEL : 950 Inches (37-3/8 mm)
Dimensions H x W x D Depth UNIT : 840 Inches (33-1/16 mm) PANEL : 950 Inches (37-3/8 mm)
Field Drainpipe Size O.D. 1-1/4 Inches (32 mm)
Refrigerant Piping Connection Method Indoor / Outdoor Flared / Flared
Operation Conditions - Indoor Intake Air Temperature Cooling - Maximum - DB , WB 95°F (35°C) DB, 71°F (22°C) WB
Operation Conditions - Indoor Intake Air Temperature Cooling - Minimum - DB , WB 67°F (19°C) DB, 57°F (14°C) WB
Operation Conditions - Indoor Intake Air Temperature Heating - Maximum - DB , WB 80°F (27°C) DB, 67° (19°C) WB
Operation Conditions - Indoor Intake Air Temperature Heating - Minimum - DB , WB 70°F (21°C DB, 60°F (16°C) WB
Operation Conditions - Indoor Intake Air Temperature Cooling - Maximum - DB 95°F (35°C) DB
Operation Conditions - Indoor Intake Air Temperature Cooling - Maximum -WB 71°F (22°C) WB
Operation Conditions - Indoor Intake Air Temperature Cooling - Minimum - DB 67°F (19°C) DB
Operation Conditions - Indoor Intake Air Temperature Cooling - Minimum - WB 57°F (14°C) WB
Operation Conditions - Indoor Intake Air Temperature Heating - Maximum - DB 80°F (27°C) DB
Operation Conditions - Indoor Intake Air Temperature Heating - Maximum - WB 67° (19°C) WB
Operation Conditions - Indoor Intake Air Temperature Heating - Minimum - DB 70°F (21°C DB
Operation Conditions - Indoor Intake Air Temperature Heating - Minimum - WB 60°F (16°C) WB
Operation Conditions - Outdoor Intake Air Temperature Cooling - Maximum - DB , WB 115°F (46°C) DB
Operation Conditions - Outdoor Intake Air Temperature Heating - Maximum - DB , WB 70°F (21°C) DB, 59°F (15°C) WB
Operation Conditions - Outdoor Intake Air Temperature Heating - Minimum - DB , WB 12°F (-11°C) DB, 10°F (-12°C) WB
Operation Conditions - Outdoor Intake Air Temperature Cooling - Maximum - DB 115°F (46°C) DB
Operation Conditions - Outdoor Intake Air Temperature Cooling - Maximum - WB 115°F (46°C) DB
Operation Conditions - Outdoor Intake Air Temperature Cooling- Minimum - DB 0°F** (-18°C) DB
Operation Conditions - Outdoor Intake Air Temperature Heating - Maximum - DB 70°F (21°C) DB
Operation Conditions - Outdoor Intake Air Temperature Heating - Maximum - WB 59°F (15°C) WB
Operation Conditions - Outdoor Intake Air Temperature Heating - Minimum - DB 12°F (-11°C) DB
Operation Conditions - Outdoor Intake Air Temperature Heating - Minimum - WB 10°F (-12°C) WB
Heat Exchanger Plate fin coil
Voltage Indoor - Outdoor S1-S2 AC 208 / 230V
Voltage Indoor - Outdoor S2-S3 DC 12-24V
External Finish Munsell 6.4Y 8.9/0.4

Mitsubishi Electric HVAC
3400 Lawrenceville Suwanee Rd.
Suwanee,  GA USA 30024 
Tel: (800) 687-1966
Fax: (800) 658-1458
Website: http://www.mehvac.com