Overview



PKA - P-Series Heat Pumps - Indoor Units - 0_PKA-A30KA6/PUZ-HA30NHA4

PKA - P-Series Heat Pumps - Indoor Units


Model Number: 0_PKA-A30KA6/PUZ-HA30NHA4

Wall-mounted ductless indoor unit for residential and light commercial applications. Ideal for applications such as churches, classrooms, daycare centers, small offices, and more. Rated capacities range from 12,000 - 34,200 Btu/h.


Shiny-white–exterior plastic
Sleek, slim-line design
Ductless installation
RedLINK enabled for wall-mounted wireless, hand-held wireless or wired controller
Easy-clean, washable filter
Wide air flow pattern for better air distribution; independently adjustable vanes
Optional i-see sensor for improved temperature sensing
Self-check function—integrated diagnostics
Hot-start technology
Limited warranty: five years on parts and defects and seven years on compressors




Power Supply Phase, Cycle, Voltage 1 Phase, 60Hz, 208/230V *4
Cooling Rated Capacity 18000 Btu/h (5.28 kW) *1
Cooling Capacity Range 8000 - 18000 BTU/h (2.3 - 5.3 kW)
Cooling Total Input 2240 W (2.200 kW)
Cooling Energy Efficiency SEER 15.3
Cooling Sensible Heat Factor 0.68
Cooling EER 8
Cooling Moisture Removal Pints/H 5.2
Heating at 47° F Rated Capacity 19000 Btu/h (5.6 kW) *2
Heating at 47° F Capacity Range 8000 - 20000 Btu/h (2.3 - 5.9 kW)
Heating at 47° F Total Input 1970 W
Heating at 47° F HSPF (Region IV) 9.5
Heating at 47° F COP 2.8 Btu/Btu
Heating at 17° F COP 2.28 Btu/Btu
Heating at 17° F Rated Capacity 13000 Btu/h (3.8 kW) *3
Heating at 17° F Total Input 1670 W
Minimum Circuit Ampacity MCA 1 Ampere
Recommended Fuse/Breaker Size 15 Ampere
Refrigerant Type R410A
Refrigerant Oil Type 0.65 (MEL56) [20]
Refrigerant Charge 1.7 [3 lbs 12 oz]
Refrigerant Control Linear Expansion Valve
Fan Fan Motor - F.L.A. 0.033 F.L.A
Fan Fan motor output - kW 30 W
External Static Pressure 0
Airflow Cooling : DRY 320 - 370 - 425 CFM ( 9-10.5-12 m³/min)
Airflow Cooling : WET 290 -335 -380 CFM (8-9.5-11 m³/min)
Sound Pressure Level 36 - 40 - 43 dB(A)
Dimensions H x W x D Height 23-5/8 Inches (600 mm)
Dimensions H x W x D Width 31-1/2 Inches (800 mm)
Dimensions H x W x D Depth 13 + 7/8 Inches (330 + 23 mm)
Field Drainpipe Size O.D. 5/8 Inch (16 mm)
Refrigerant Piping Connection Method Indoor / Outdoor Flared / Flared
Operation Conditions - Indoor Intake Air Temperature Cooling - Maximum - DB , WB 95°F (35°C) DB, 71°F (22°C) WB
Operation Conditions - Indoor Intake Air Temperature Cooling - Minimum - DB , WB 67°F (19°C) DB , 57°F (14°C) WB
Operation Conditions - Indoor Intake Air Temperature Heating - Maximum - DB , WB 80°F (27°C) DB, 67°F (19°C) WB
Operation Conditions - Indoor Intake Air Temperature Heating - Minimum - DB , WB 70°F (21°C) DB, 60°F (16°C) WB
Operation Conditions - Indoor Intake Air Temperature Cooling - Maximum - DB 95°F (35°C) DB
Operation Conditions - Indoor Intake Air Temperature Cooling - Maximum -WB 71°F (22°C) WB
Operation Conditions - Indoor Intake Air Temperature Cooling - Minimum - DB 67°F (19°C) DB
Operation Conditions - Indoor Intake Air Temperature Cooling - Minimum - WB 57°F (14°C) WB
Operation Conditions - Indoor Intake Air Temperature Heating - Maximum - DB 80°F (27°C) DB
Operation Conditions - Indoor Intake Air Temperature Heating - Maximum - WB 67°F (19°C) WB
Operation Conditions - Indoor Intake Air Temperature Heating - Minimum - DB 70°F (21°C) DB
Operation Conditions - Indoor Intake Air Temperature Heating - Minimum - WB 60°F (16°C) WB
Operation Conditions - Outdoor Intake Air Temperature Cooling - Maximum - DB , WB 115°F (46°C) DB
Operation Conditions - Outdoor Intake Air Temperature Heating - Maximum - DB , WB 70°F (21°C) DB, 59°F (15°C) WB
Operation Conditions - Outdoor Intake Air Temperature Heating - Minimum - DB , WB 12°F (-11°C) DB, 10°F (-12°C) WB
Operation Conditions - Outdoor Intake Air Temperature Cooling - Maximum - DB 115°F (46°C) DB
Operation Conditions - Outdoor Intake Air Temperature Cooling - Maximum - WB 115°F (46°C) DB
Operation Conditions - Outdoor Intake Air Temperature Cooling- Minimum - DB 0°F** (-18°C) DB
Operation Conditions - Outdoor Intake Air Temperature Heating - Maximum - DB 70°F (21°C) DB
Operation Conditions - Outdoor Intake Air Temperature Heating - Maximum - WB 59°F (15°C) WB
Operation Conditions - Outdoor Intake Air Temperature Heating - Minimum - DB 12°F (-11°C) DB
Operation Conditions - Outdoor Intake Air Temperature Heating - Minimum - WB 10°F (-12°C) WB
External Finish Munsell 1.0Y 9.2 / 0.2
Voltage Indoor - Outdoor S1-S2 AC 208 / 230V
Voltage Indoor - Outdoor S2-S3 DC24V

Power Supply Phase, Cycle, Voltage 1 Phase, 60Hz, 208/230V *4
Cooling Rated Capacity 18000 Btu/h (5.28 kW) *1
Cooling Capacity Range 8000 - 18000 BTU/h (2.3 - 5.3 kW)
Cooling Total Input 2240 W (2.200 kW)
Cooling Energy Efficiency SEER 15.3
Cooling Sensible Heat Factor 0.68
Cooling EER 8
Cooling Moisture Removal Pints/H 5.2
Heating at 47° F Rated Capacity 19000 Btu/h (5.6 kW) *2
Heating at 47° F Capacity Range 8000 - 20000 Btu/h (2.3 - 5.9 kW)
Heating at 47° F Total Input 1970 W
Heating at 47° F HSPF (Region IV) 9.5
Heating at 47° F COP 2.8 Btu/Btu
Heating at 17° F COP 2.28 Btu/Btu
Heating at 17° F Rated Capacity 13000 Btu/h (3.8 kW) *3
Heating at 17° F Total Input 1670 W
Minimum Circuit Ampacity MCA 1 Ampere
Recommended Fuse/Breaker Size 15 Ampere
Refrigerant Type R410A
Refrigerant Oil Type 0.65 (MEL56) [20]
Refrigerant Charge 1.7 [3 lbs 12 oz]
Refrigerant Control Linear Expansion Valve
Fan Fan Motor - F.L.A. 0.033 F.L.A
Fan Fan motor output - kW 30 W
External Static Pressure 0
Airflow Cooling : DRY 320 - 370 - 425 CFM ( 9-10.5-12 m³/min)
Airflow Cooling : WET 290 -335 -380 CFM (8-9.5-11 m³/min)
Sound Pressure Level 36 - 40 - 43 dB(A)
Dimensions H x W x D Height 23-5/8 Inches (600 mm)
Dimensions H x W x D Width 31-1/2 Inches (800 mm)
Dimensions H x W x D Depth 13 + 7/8 Inches (330 + 23 mm)
Field Drainpipe Size O.D. 5/8 Inch (16 mm)
Refrigerant Piping Connection Method Indoor / Outdoor Flared / Flared
Operation Conditions - Indoor Intake Air Temperature Cooling - Maximum - DB , WB 95°F (35°C) DB, 71°F (22°C) WB
Operation Conditions - Indoor Intake Air Temperature Cooling - Minimum - DB , WB 67°F (19°C) DB , 57°F (14°C) WB
Operation Conditions - Indoor Intake Air Temperature Heating - Maximum - DB , WB 80°F (27°C) DB, 67°F (19°C) WB
Operation Conditions - Indoor Intake Air Temperature Heating - Minimum - DB , WB 70°F (21°C) DB, 60°F (16°C) WB
Operation Conditions - Indoor Intake Air Temperature Cooling - Maximum - DB 95°F (35°C) DB
Operation Conditions - Indoor Intake Air Temperature Cooling - Maximum -WB 71°F (22°C) WB
Operation Conditions - Indoor Intake Air Temperature Cooling - Minimum - DB 67°F (19°C) DB
Operation Conditions - Indoor Intake Air Temperature Cooling - Minimum - WB 57°F (14°C) WB
Operation Conditions - Indoor Intake Air Temperature Heating - Maximum - DB 80°F (27°C) DB
Operation Conditions - Indoor Intake Air Temperature Heating - Maximum - WB 67°F (19°C) WB
Operation Conditions - Indoor Intake Air Temperature Heating - Minimum - DB 70°F (21°C) DB
Operation Conditions - Indoor Intake Air Temperature Heating - Minimum - WB 60°F (16°C) WB
Operation Conditions - Outdoor Intake Air Temperature Cooling - Maximum - DB , WB 115°F (46°C) DB
Operation Conditions - Outdoor Intake Air Temperature Heating - Maximum - DB , WB 70°F (21°C) DB, 59°F (15°C) WB
Operation Conditions - Outdoor Intake Air Temperature Heating - Minimum - DB , WB 12°F (-11°C) DB, 10°F (-12°C) WB
Operation Conditions - Outdoor Intake Air Temperature Cooling - Maximum - DB 115°F (46°C) DB
Operation Conditions - Outdoor Intake Air Temperature Cooling - Maximum - WB 115°F (46°C) DB
Operation Conditions - Outdoor Intake Air Temperature Cooling- Minimum - DB 0°F** (-18°C) DB
Operation Conditions - Outdoor Intake Air Temperature Heating - Maximum - DB 70°F (21°C) DB
Operation Conditions - Outdoor Intake Air Temperature Heating - Maximum - WB 59°F (15°C) WB
Operation Conditions - Outdoor Intake Air Temperature Heating - Minimum - DB 12°F (-11°C) DB
Operation Conditions - Outdoor Intake Air Temperature Heating - Minimum - WB 10°F (-12°C) WB
External Finish Munsell 1.0Y 9.2 / 0.2
Voltage Indoor - Outdoor S1-S2 AC 208 / 230V
Voltage Indoor - Outdoor S2-S3 DC24V

Power Supply Phase, Cycle, Voltage 1 Phase, 60Hz, 208/230V *4
Cooling Rated Capacity 24000 Btu/h (7.03 kW) *1
Cooling Capacity Range 12000 - 24000 Btu/h (3.5 - 7 kW)
Cooling Total Input 2270 W (2.300 kW)
Cooling Energy Efficiency SEER 17
Cooling Sensible Heat Factor 0.77
Cooling EER 10.6
Cooling Moisture Removal Pints/H 5
Heating at 47° F Rated Capacity 26000 Btu/h (7.6 kW) *2
Heating at 47° F Capacity Range 12000 Btu/h (3.5 kW)
Heating at 47° F HSPF (Region IV) 10.8 Btu/h/W
Heating at 47° F COP 3.26 Btu/Btu
Heating at 17° F COP 2.4 Btu/Btu
Heating at 17° F Total Input 2200 W
Heating at 17° F Rated Capacity 18000 Btu/h (5.27 kW) *3
Minimum Circuit Ampacity MCA 1 Ampere
Recommended Fuse/Breaker Size 25 Ampere
Refrigerant Type R410A
Refrigerant Oil Type 0.87 (FV50S) [28]
Refrigerant Charge 3.0 [6 lbs 10 oz]
Refrigerant Control Linear Expansion Valve
Fan Fan motor output - kW 56 W
Fan Fan Motor - F.L.A. 0.036 F.L.A
External Static Pressure 0 in.WG (0 Pa) (direct blow)
Airflow Cooling : DRY 635-705-775 CFM (18-20-22 m³/min)
Airflow Cooling : WET 570-635-700 CFM (16-18-20 m³/min))
Sound Pressure Level Cooling 39-42-45 dB(A)
Dimensions H x W x D Height 14-3/8 Inches (365 mm)
Dimensions H x W x D Width 46-1/16 Inches (1170 mm)
Dimensions H x W x D Depth 11-5/8 Inches (295 mm)
Field Drainpipe Size O.D. 5/8 Inch (15.88 mm)
Refrigerant Piping Connection Method Indoor / Outdoor Flared / Flared
Operation Conditions - Indoor Intake Air Temperature Cooling - Maximum - DB , WB 95°F (35°C) DB, 71°F (22°C) WB
Operation Conditions - Indoor Intake Air Temperature Cooling - Minimum - DB , WB 67°F (19°C) DB , 57°F (14°C) WB
Operation Conditions - Indoor Intake Air Temperature Cooling - Maximum - DB 95°F (35°C) DB
Operation Conditions - Indoor Intake Air Temperature Cooling - Maximum -WB 71°F (22°C) WB
Operation Conditions - Indoor Intake Air Temperature Cooling - Minimum - DB 67°F (19°C) DB
Operation Conditions - Indoor Intake Air Temperature Cooling - Minimum - WB 57°F (14°C) WB
Operation Conditions - Outdoor Intake Air Temperature Cooling - Maximum - DB , WB 115°F (46°C) DB
Operation Conditions - Outdoor Intake Air Temperature Cooling - Maximum - DB 115°F (46°C) DB
Operation Conditions - Outdoor Intake Air Temperature Cooling - Maximum - WB 115°F (46°C) DB
Operation Conditions - Outdoor Intake Air Temperature Cooling- Minimum - DB 0°F** (-18°C) DB
Voltage Indoor - Outdoor S1-S2 AC 208 / 230V
Voltage Indoor - Outdoor S2-S3 DC24V
External Finish Munsell 1.0Y 9.2 / 0.2

Power Supply Phase, Cycle, Voltage 1 Phase, 60Hz, 208/230V *4
Cooling Rated Capacity 24000 Btu/h (7.03 kW) *1
Cooling Capacity Range 12000 - 24000 Btu/h (3.5 - 7 kW)
Cooling Total Input 2270 W (2.300 kW)
Cooling Energy Efficiency SEER 17
Cooling Sensible Heat Factor 0.77
Cooling EER 10.6
Cooling Moisture Removal Pints/H 5
Heating at 47° F Rated Capacity 26000 Btu/h (7.6 kW) *2
Heating at 47° F Capacity Range 12000 Btu/h (3.5 kW)
Heating at 47° F HSPF (Region IV) 10.8 Btu/h/W
Heating at 47° F COP 3.26 Btu/Btu
Heating at 17° F COP 2.4 Btu/Btu
Heating at 17° F Total Input 2200 W
Heating at 17° F Rated Capacity 18000 Btu/h (5.27 kW) *3
Minimum Circuit Ampacity MCA 1 Ampere
Recommended Fuse/Breaker Size 25 Ampere
Refrigerant Type R410A
Refrigerant Oil Type 0.87 (FV50S) [28]
Refrigerant Charge 3.0 [6 lbs 10 oz]
Refrigerant Control Linear Expansion Valve
Fan Fan motor output - kW 56 W
Fan Fan Motor - F.L.A. 0.036 F.L.A
External Static Pressure 0 in.WG (0 Pa) (direct blow)
Airflow Cooling : DRY 635-705-775 CFM (18-20-22 m³/min)
Airflow Cooling : WET 570-635-700 CFM (16-18-20 m³/min))
Sound Pressure Level Cooling 39-42-45 dB(A)
Dimensions H x W x D Height 14-3/8 Inches (365 mm)
Dimensions H x W x D Width 46-1/16 Inches (1170 mm)
Dimensions H x W x D Depth 11-5/8 Inches (295 mm)
Field Drainpipe Size O.D. 5/8 Inch (15.88 mm)
Refrigerant Piping Connection Method Indoor / Outdoor Flared / Flared
Operation Conditions - Indoor Intake Air Temperature Cooling - Maximum - DB , WB 95°F (35°C) DB, 71°F (22°C) WB
Operation Conditions - Indoor Intake Air Temperature Cooling - Minimum - DB , WB 67°F (19°C) DB , 57°F (14°C) WB
Operation Conditions - Indoor Intake Air Temperature Cooling - Maximum - DB 95°F (35°C) DB
Operation Conditions - Indoor Intake Air Temperature Cooling - Maximum -WB 71°F (22°C) WB
Operation Conditions - Indoor Intake Air Temperature Cooling - Minimum - DB 67°F (19°C) DB
Operation Conditions - Indoor Intake Air Temperature Cooling - Minimum - WB 57°F (14°C) WB
Operation Conditions - Outdoor Intake Air Temperature Cooling - Maximum - DB , WB 115°F (46°C) DB
Operation Conditions - Outdoor Intake Air Temperature Cooling - Maximum - DB 115°F (46°C) DB
Operation Conditions - Outdoor Intake Air Temperature Cooling - Maximum - WB 115°F (46°C) DB
Operation Conditions - Outdoor Intake Air Temperature Cooling- Minimum - DB 0°F** (-18°C) DB
Voltage Indoor - Outdoor S1-S2 AC 208 / 230V
Voltage Indoor - Outdoor S2-S3 DC24V
External Finish Munsell 1.0Y 9.2 / 0.2

Power Supply Phase, Cycle, Voltage 1 Phase, 60Hz, 208/230V *4
Cooling Rated Capacity 30000 Btu/h (8.79 kW) *1
Cooling Capacity Range 12000 - 30000 BTU/h (3.5 - 8.8 kW)
Cooling Total Input 4130 W (4.100 kW)
Cooling Energy Efficiency SEER 15.5
Cooling Sensible Heat Factor 0.7
Cooling EER 7.3
Cooling Moisture Removal Pints/H 8.1
Heating at 47° F Rated Capacity 32000 Btu/h (9.4 kW) *2
Heating at 47° F Capacity Range 12000 - 34000 Btu/h (3.5 - 10 kW)
Heating at 47° F Total Input 3150 W
Heating at 47° F HSPF (Region IV) 8.9
Heating at 47° F COP 2.9 Btu/Btu
Heating at 17° F COP 2.2 Btu/Btu
Heating at 17° F Rated Capacity 23000 Btu/h (6.7 kW) *3
Heating at 17° F Total Input 2850 W
Minimum Circuit Ampacity MCA 1 Ampere
Recommended Fuse/Breaker Size 30 Ampere
Refrigerant Type R410A
Refrigerant Oil Type 0.87 (FV50S) [28]
Refrigerant Charge 3.0 [6 lbs 10 oz]
Refrigerant Control Linear Expansion Valve
Fan Fan motor output - kW 56 W
Fan Fan Motor - F.L.A. 0.036 F.L.A
External Static Pressure 0
Airflow Cooling : DRY 635-705-775 CFM (18-20-22 m³/min)
Airflow Cooling : WET 570-635-700 CFM (16-18-20 m³/min)
Sound Pressure Level 39-42-45 dB(A)
Dimensions H x W x D Height 37-1/8 Inches (943 mm)
Dimensions H x W x D Width 37-3/8 Inches (950 mm)
Dimensions H x W x D Depth 13 + 7/8 Inches (330 + 23 mm)
Field Drainpipe Size O.D. 5/8 Inch (16 mm)
Refrigerant Piping Connection Method Indoor / Outdoor Flared / Flared
Operation Conditions - Indoor Intake Air Temperature Cooling - Maximum - DB , WB 95°F (35°C) DB, 71°F (22°C) WB
Operation Conditions - Indoor Intake Air Temperature Cooling - Minimum - DB , WB 67°F (19°C) DB , 57°F (14°C) WB
Operation Conditions - Indoor Intake Air Temperature Heating - Maximum - DB , WB 80°F (27°C) DB, 67°F (19°C) WB
Operation Conditions - Indoor Intake Air Temperature Heating - Minimum - DB , WB 70°F (21°C) DB, 60°F (16°C) WB
Operation Conditions - Indoor Intake Air Temperature Cooling - Maximum - DB 95°F (35°C) DB
Operation Conditions - Indoor Intake Air Temperature Cooling - Maximum -WB 71°F (22°C) WB
Operation Conditions - Indoor Intake Air Temperature Cooling - Minimum - DB 67°F (19°C) DB
Operation Conditions - Indoor Intake Air Temperature Cooling - Minimum - WB 57°F (14°C) WB
Operation Conditions - Indoor Intake Air Temperature Heating - Maximum - DB 80°F (27°C) DB
Operation Conditions - Indoor Intake Air Temperature Heating - Maximum - WB 67°F (19°C) WB
Operation Conditions - Indoor Intake Air Temperature Heating - Minimum - DB 70°F (21°C) DB
Operation Conditions - Indoor Intake Air Temperature Heating - Minimum - WB 60°F (16°C) WB
Operation Conditions - Outdoor Intake Air Temperature Cooling - Maximum - DB , WB 115°F (46°C) DB
Operation Conditions - Outdoor Intake Air Temperature Heating - Maximum - DB , WB 70°F (21°C) DB, 59°F (15°C) WB
Operation Conditions - Outdoor Intake Air Temperature Heating - Minimum - DB , WB 12°F (-11°C) DB, 10°F (-12°C) WB
Operation Conditions - Outdoor Intake Air Temperature Cooling - Maximum - DB 115°F (46°C) DB
Operation Conditions - Outdoor Intake Air Temperature Cooling- Minimum - DB 0°F** (-18°C) DB
Operation Conditions - Outdoor Intake Air Temperature Heating - Maximum - DB 70°F (21°C) DB
Operation Conditions - Outdoor Intake Air Temperature Heating - Maximum - WB 59°F (15°C) WB
Operation Conditions - Outdoor Intake Air Temperature Heating - Minimum - DB 12°F (-11°C) DB
Operation Conditions - Outdoor Intake Air Temperature Heating - Minimum - WB 10°F (-12°C) WB
External Finish Munsell 1.0Y 9.2 / 0.2
Voltage Indoor - Outdoor S1-S2 AC 208 / 230V
Voltage Indoor - Outdoor S2-S3 DC24V

Energy Star System X
Power Supply Phase, Cycle, Voltage 1 Phase, 60Hz, 208/230V *5
Cooling Rated Capacity 30000 Btu/h (8.79 kW) *1
Cooling Capacity Range 18000 - 30000 Btu/h (5.3 - 8.8 kW)
Cooling Total Input 2500 W (2.500 kW)
Cooling Energy Efficiency SEER 16.5
Cooling Sensible Heat Factor 0.7
Cooling Moisture Removal Pints/H 8.1
Cooling EER 12
Heating at 47° F Rated Capacity 32000 Btu/h (9.4 kW) *2
Heating at 47° F Capacity Range 18000 - 34000 Btu/h (5.3 - 10 kW)
Heating at 47° F Total Input 2930 W
Heating at 47° F HSPF (Region IV) 9.5
Heating at 47° F COP 3.2 Btu/Btu
Heating at 17° F Maximum Capacity 32000 Btu/h (9.4 kW)
Heating at 17° F COP 2.17 Btu/Btu
Heating at 17° F Total Input 2570 W
Heating at 17° F Rated Capacity 19000 Btu/h (5.6 kW) *3
Heating at 5° F Maximum Capacity 32000 Btu/h (4.8 kW)
Heating at 5° F COP 1.62 Btu/Btu
Heating at 5° F Total Input 5770 W
Minimum Circuit Ampacity MCA 1 Ampere
Maximum fuse size (time delay) MOCP 15 Ampere
Recommended Fuse/Breaker Size 30 Ampere
Refrigerant Oil Type 1.4 (FV50S) [45]
Refrigerant Type R410A
Refrigerant Charge 5.5 [12 lbs]
Refrigerant Control Electronic Expansion Valve
Fan Fan Motor - F.L.A. 0.36 F.L.A
Fan Fan motor output - kW 56
External Static Pressure 0 in.WG (0 Pa)
Airflow DRY 635-705-775 CFM ( 18-20-22 m³/min)
Airflow WET 570-635-700 CFM ( 16-18-20 m³/min)
Airflow Cooling 1730 CFM (49 m³/min)
Sound Pressure Level 39-42-45 dB(A)
Dimensions H x W x D Height 53-1/8 Inches (1,350 mm)
Dimensions H x W x D Width 37-3/8 Inches (950 mm)
Dimensions H x W x D Depth 13 + 1-3/16 Inches (330 + 30 mm)
Field Drainpipe Size O.D. 5/8 Inch (16 mm)
Refrigerant Piping Connection Method Indoor / Outdoor Flared / Flared
Operation Conditions - Indoor Intake Air Temperature Cooling - Maximum - DB , WB 90°F (32°C) DB , 73°F (23°C) WB
Operation Conditions - Indoor Intake Air Temperature Cooling - Minimum - DB , WB 66°F (19°C) DB, 59°F (15°C) WB
Operation Conditions - Indoor Intake Air Temperature Heating - Maximum - DB , WB 83°F (28°C) DB
Operation Conditions - Indoor Intake Air Temperature Heating - Minimum - DB , WB 63°F (17°C) DB
Operation Conditions - Indoor Intake Air Temperature Heating - Maximum - DB 83°F (28°C) DB
Operation Conditions - Indoor Intake Air Temperature Cooling - Maximum -WB 73°F (23°C) WB
Operation Conditions - Indoor Intake Air Temperature Cooling - Maximum - DB 90°F (32°C) DB
Operation Conditions - Outdoor Intake Air Temperature Cooling - Maximum - DB , WB 115°F (46°C) DB
Operation Conditions - Outdoor Intake Air Temperature Heating - Maximum - DB , WB 70°F (21°C) DB, 59°F (15°C) WB
Operation Conditions - Outdoor Intake Air Temperature Heating - Minimum - DB , WB -13°F (-25°C) DB, -13°F (-25°C) WB
Operation Conditions - Outdoor Intake Air Temperature Heating - Maximum - DB 70°F (21°C) DB
Operation Conditions - Outdoor Intake Air Temperature Cooling- Minimum - DB 0°F** (-18°C) DB
Operation Conditions - Outdoor Intake Air Temperature Cooling - Maximum - WB 115°F (46°C) DB
Operation Conditions - Outdoor Intake Air Temperature Heating - Maximum - WB 59°F (15°C) WB
Operation Conditions - Outdoor Intake Air Temperature Cooling - Maximum - DB 115°F (46°C) DB
Voltage Indoor - Outdoor S2-S3 DC24V
Voltage Indoor - Outdoor S1-S2 AC 208 / 230V
External Finish Munsell 1.0Y 9.2 / 0.2

Power Supply Phase, Cycle, Voltage 1 Phase, 60Hz, 208/230V *4
Cooling Rated Capacity 30000 Btu/h (8.79 kW) *1
Cooling Capacity Range 12000 - 30000 BTU/h (3.5 - 8.8 kW)
Cooling Total Input 4130 W (4.100 kW)
Cooling Energy Efficiency SEER 15.5
Cooling Sensible Heat Factor 0.7
Cooling EER 7.3
Cooling Moisture Removal Pints/H 8.1
Heating at 47° F Rated Capacity 32000 Btu/h (9.4 kW) *2
Heating at 47° F Capacity Range 12000 - 34000 Btu/h (3.5 - 10 kW)
Heating at 47° F Total Input 3150 W
Heating at 47° F HSPF (Region IV) 8.9
Heating at 47° F COP 2.9 Btu/Btu
Heating at 17° F COP 2.2 Btu/Btu
Heating at 17° F Rated Capacity 23000 Btu/h (6.7 kW) *3
Heating at 17° F Total Input 2850 W
Minimum Circuit Ampacity MCA 1 Ampere
Recommended Fuse/Breaker Size 30 Ampere
Refrigerant Type R410A
Refrigerant Oil Type 0.87 (FV50S) [28]
Refrigerant Charge 3.0 [6 lbs 10 oz]
Refrigerant Control Linear Expansion Valve
Fan Fan motor output - kW 56 W
Fan Fan Motor - F.L.A. 0.036 F.L.A
External Static Pressure 0
Airflow Cooling : DRY 635-705-775 CFM (18-20-22 m³/min)
Airflow Cooling : WET 570-635-700 CFM (16-18-20 m³/min)
Sound Pressure Level 39-42-45 dB(A)
Dimensions H x W x D Height 37-1/8 Inches (943 mm)
Dimensions H x W x D Width 37-3/8 Inches (950 mm)
Dimensions H x W x D Depth 13 + 7/8 Inches (330 + 23 mm)
Field Drainpipe Size O.D. 5/8 Inch (16 mm)
Refrigerant Piping Connection Method Indoor / Outdoor Flared / Flared
Operation Conditions - Indoor Intake Air Temperature Cooling - Maximum - DB , WB 95°F (35°C) DB, 71°F (22°C) WB
Operation Conditions - Indoor Intake Air Temperature Cooling - Minimum - DB , WB 67°F (19°C) DB , 57°F (14°C) WB
Operation Conditions - Indoor Intake Air Temperature Heating - Maximum - DB , WB 80°F (27°C) DB, 67°F (19°C) WB
Operation Conditions - Indoor Intake Air Temperature Heating - Minimum - DB , WB 70°F (21°C) DB, 60°F (16°C) WB
Operation Conditions - Indoor Intake Air Temperature Cooling - Maximum - DB 95°F (35°C) DB
Operation Conditions - Indoor Intake Air Temperature Cooling - Maximum -WB 71°F (22°C) WB
Operation Conditions - Indoor Intake Air Temperature Cooling - Minimum - DB 67°F (19°C) DB
Operation Conditions - Indoor Intake Air Temperature Cooling - Minimum - WB 57°F (14°C) WB
Operation Conditions - Indoor Intake Air Temperature Heating - Maximum - DB 80°F (27°C) DB
Operation Conditions - Indoor Intake Air Temperature Heating - Maximum - WB 67°F (19°C) WB
Operation Conditions - Indoor Intake Air Temperature Heating - Minimum - DB 70°F (21°C) DB
Operation Conditions - Indoor Intake Air Temperature Heating - Minimum - WB 60°F (16°C) WB
Operation Conditions - Outdoor Intake Air Temperature Cooling - Maximum - DB , WB 115°F (46°C) DB
Operation Conditions - Outdoor Intake Air Temperature Heating - Maximum - DB , WB 70°F (21°C) DB, 59°F (15°C) WB
Operation Conditions - Outdoor Intake Air Temperature Heating - Minimum - DB , WB 12°F (-11°C) DB, 10°F (-12°C) WB
Operation Conditions - Outdoor Intake Air Temperature Cooling - Maximum - DB 115°F (46°C) DB
Operation Conditions - Outdoor Intake Air Temperature Cooling- Minimum - DB 0°F** (-18°C) DB
Operation Conditions - Outdoor Intake Air Temperature Heating - Maximum - DB 70°F (21°C) DB
Operation Conditions - Outdoor Intake Air Temperature Heating - Maximum - WB 59°F (15°C) WB
Operation Conditions - Outdoor Intake Air Temperature Heating - Minimum - DB 12°F (-11°C) DB
Operation Conditions - Outdoor Intake Air Temperature Heating - Minimum - WB 10°F (-12°C) WB
External Finish Munsell 1.0Y 9.2 / 0.2
Voltage Indoor - Outdoor S1-S2 AC 208 / 230V
Voltage Indoor - Outdoor S2-S3 DC24V

Energy Star System X
Power Supply Phase, Cycle, Voltage 1 Phase, 60Hz, 208/230V *5
Cooling Rated Capacity 30000 Btu/h (8.79 kW) *1
Cooling Capacity Range 18000 - 30000 Btu/h (5.3 - 8.8 kW)
Cooling Total Input 2500 W (2.500 kW)
Cooling Energy Efficiency SEER 16.5
Cooling Sensible Heat Factor 0.7
Cooling Moisture Removal Pints/H 8.1
Cooling EER 12
Heating at 47° F Rated Capacity 32000 Btu/h (9.4 kW) *2
Heating at 47° F Capacity Range 18000 - 34000 Btu/h (5.3 - 10 kW)
Heating at 47° F Total Input 2930 W
Heating at 47° F HSPF (Region IV) 9.5
Heating at 47° F COP 3.2 Btu/Btu
Heating at 17° F Maximum Capacity 32000 Btu/h (9.4 kW)
Heating at 17° F COP 2.17 Btu/Btu
Heating at 17° F Total Input 2570 W
Heating at 17° F Rated Capacity 19000 Btu/h (5.6 kW) *3
Heating at 5° F Maximum Capacity 32000 Btu/h (4.8 kW)
Heating at 5° F COP 1.62 Btu/Btu
Heating at 5° F Total Input 5770 W
Minimum Circuit Ampacity MCA 1 Ampere
Maximum fuse size (time delay) MOCP 15 Ampere
Recommended Fuse/Breaker Size 30 Ampere
Refrigerant Oil Type 1.4 (FV50S) [45]
Refrigerant Type R410A
Refrigerant Charge 5.5 [12 lbs]
Refrigerant Control Electronic Expansion Valve
Fan Fan Motor - F.L.A. 0.36 F.L.A
Fan Fan motor output - kW 56
External Static Pressure 0 in.WG (0 Pa)
Airflow DRY 635-705-775 CFM ( 18-20-22 m³/min)
Airflow WET 570-635-700 CFM ( 16-18-20 m³/min)
Airflow Cooling 1730 CFM (49 m³/min)
Sound Pressure Level 39-42-45 dB(A)
Dimensions H x W x D Height 53-1/8 Inches (1,350 mm)
Dimensions H x W x D Width 37-3/8 Inches (950 mm)
Dimensions H x W x D Depth 13 + 1-3/16 Inches (330 + 30 mm)
Field Drainpipe Size O.D. 5/8 Inch (16 mm)
Refrigerant Piping Connection Method Indoor / Outdoor Flared / Flared
Operation Conditions - Indoor Intake Air Temperature Cooling - Maximum - DB , WB 90°F (32°C) DB , 73°F (23°C) WB
Operation Conditions - Indoor Intake Air Temperature Cooling - Minimum - DB , WB 66°F (19°C) DB, 59°F (15°C) WB
Operation Conditions - Indoor Intake Air Temperature Heating - Maximum - DB , WB 83°F (28°C) DB
Operation Conditions - Indoor Intake Air Temperature Heating - Minimum - DB , WB 63°F (17°C) DB
Operation Conditions - Indoor Intake Air Temperature Heating - Maximum - DB 83°F (28°C) DB
Operation Conditions - Indoor Intake Air Temperature Cooling - Maximum -WB 73°F (23°C) WB
Operation Conditions - Indoor Intake Air Temperature Cooling - Maximum - DB 90°F (32°C) DB
Operation Conditions - Outdoor Intake Air Temperature Cooling - Maximum - DB , WB 115°F (46°C) DB
Operation Conditions - Outdoor Intake Air Temperature Heating - Maximum - DB , WB 70°F (21°C) DB, 59°F (15°C) WB
Operation Conditions - Outdoor Intake Air Temperature Heating - Minimum - DB , WB -13°F (-25°C) DB, -13°F (-25°C) WB
Operation Conditions - Outdoor Intake Air Temperature Heating - Maximum - DB 70°F (21°C) DB
Operation Conditions - Outdoor Intake Air Temperature Cooling- Minimum - DB 0°F** (-18°C) DB
Operation Conditions - Outdoor Intake Air Temperature Cooling - Maximum - WB 115°F (46°C) DB
Operation Conditions - Outdoor Intake Air Temperature Heating - Maximum - WB 59°F (15°C) WB
Operation Conditions - Outdoor Intake Air Temperature Cooling - Maximum - DB 115°F (46°C) DB
Voltage Indoor - Outdoor S2-S3 DC24V
Voltage Indoor - Outdoor S1-S2 AC 208 / 230V
External Finish Munsell 1.0Y 9.2 / 0.2

Power Supply Phase, Cycle, Voltage 1 Phase, 60Hz, 208/230V *4
Cooling Rated Capacity 34200 Btu/h (10.02 kW) *1
Cooling Capacity Range 12000 - 34200 Btu/h (3.5 - 10 kW)
Cooling Total Input 5030 W (500 kW)
Cooling Energy Efficiency SEER 14
Cooling Sensible Heat Factor 0.7
Cooling EER 6.8
Cooling Moisture Removal Pints/H 9.2
Heating at 47° F Rated Capacity 37000 Btu/h (10.8 kW) *2
Heating at 47° F Capacity Range 12000 - 38000 Btu/h (3.5 - 11.1 kW)
Heating at 47° F Total Input 3610 W
Heating at 47° F HSPF (Region IV) 9.3
Heating at 47° F COP 3 Btu/Btu
Heating at 17° F COP 2 Btu/Btu
Heating at 17° F Rated Capacity 25000 Btu/h (7.3 kW) *3
Heating at 17° F Total Input 3030 W
Minimum Circuit Ampacity MCA 1 Ampere
Recommended Fuse/Breaker Size 30 Ampere
Refrigerant Oil Type 0.87 (FV50S) [28]
Refrigerant Type R410A
Refrigerant Charge 3.0 [6 lbs 10 oz]
Refrigerant Control Linear Expansion Valve
Fan Fan Motor - F.L.A. 0.057 F.L.A
Fan Fan motor output - kW 56 W
External Static Pressure 0
Airflow Cooling : DRY 705 - 810 - 920 CFM (20-23-26 m³/min)
Airflow Cooling : WET 635 -730 -830 CFM (18-21-23 m³/min)
Sound Pressure Level 43-46-49 db(A)
Dimensions H x W x D Height 37-1/8 Inches (943 mm)
Dimensions H x W x D Width 37-3/8 Inches (950 mm)
Dimensions H x W x D Depth 13 + 7/8 Inches (330 + 23 mm)
Field Drainpipe Size O.D. 5/8 Inch (16 mm)
Refrigerant Piping Connection Method Indoor / Outdoor Flared / Flared
Operation Conditions - Indoor Intake Air Temperature Cooling - Maximum - DB , WB 95°F (35°C) DB, 71°F (22°C) WB
Operation Conditions - Indoor Intake Air Temperature Cooling - Minimum - DB , WB 67°F (19°C) DB , 57°F (14°C) WB
Operation Conditions - Indoor Intake Air Temperature Heating - Maximum - DB , WB 80°F (27°C) DB, 67°F (19°C) WB
Operation Conditions - Indoor Intake Air Temperature Heating - Minimum - DB , WB 70°F (21°C) DB, 60°F (16°C) WB
Operation Conditions - Indoor Intake Air Temperature Cooling - Maximum - DB 95°F (35°C) DB
Operation Conditions - Indoor Intake Air Temperature Cooling - Maximum -WB 71°F (22°C) WB
Operation Conditions - Indoor Intake Air Temperature Cooling - Minimum - DB 67°F (19°C) DB
Operation Conditions - Indoor Intake Air Temperature Cooling - Minimum - WB 57°F (14°C) WB
Operation Conditions - Indoor Intake Air Temperature Heating - Maximum - DB 80°F (27°C) DB
Operation Conditions - Indoor Intake Air Temperature Heating - Maximum - WB 67°F (19°C) WB
Operation Conditions - Indoor Intake Air Temperature Heating - Minimum - DB 70°F (21°C) DB
Operation Conditions - Indoor Intake Air Temperature Heating - Minimum - WB 60°F (16°C) WB
Operation Conditions - Outdoor Intake Air Temperature Cooling - Maximum - DB , WB 115°F (46°C) DB
Operation Conditions - Outdoor Intake Air Temperature Heating - Maximum - DB , WB 70°F (21°C) DB, 59°F (15°C) WB
Operation Conditions - Outdoor Intake Air Temperature Heating - Minimum - DB , WB 12°F (-11°C) DB, 10°F (-12°C) WB
Operation Conditions - Outdoor Intake Air Temperature Cooling - Maximum - DB 115°F (46°C) DB
Operation Conditions - Outdoor Intake Air Temperature Cooling - Maximum - WB 115°F (46°C) DB
Operation Conditions - Outdoor Intake Air Temperature Cooling- Minimum - DB 0°F** (-18°C) DB
Operation Conditions - Outdoor Intake Air Temperature Heating - Maximum - DB 70°F (21°C) DB
Operation Conditions - Outdoor Intake Air Temperature Heating - Maximum - WB 59°F (15°C) WB
Operation Conditions - Outdoor Intake Air Temperature Heating - Minimum - DB 12°F (-11°C) DB
Operation Conditions - Outdoor Intake Air Temperature Heating - Minimum - WB 10°F (-12°C) WB
Voltage Indoor - Outdoor S1-S2 AC 208 / 230V
Voltage Indoor - Outdoor S2-S3 DC24V
External Finish Munsell 1.0Y 9.2 / 0.2

Energy Star System X
Power Supply Phase, Cycle, Voltage 1 Phase, 60Hz, 208/230V *5
Cooling Rated Capacity 33500 Btu/h (9.82 kW) *1
Cooling Capacity Range 18000 - 34200 Btu/h (5.3 - 10 kW)
Cooling Total Input 2790 W (2.800 kW)
Cooling Energy Efficiency SEER 16.2
Cooling Sensible Heat Factor 0.71
Cooling Moisture Removal Pints/H 8.7
Cooling EER 12
Heating at 47° F Rated Capacity 38000 Btu/h (11.1 kW) *2
Heating at 47° F Capacity Range 18000 - 40000 Btu/h (5.3 - 11.7 kW)
Heating at 47° F Total Input 3410 W
Heating at 47° F HSPF (Region IV) 10
Heating at 47° F COP 3.27 Btu/Btu
Heating at 17° F Maximum Capacity 38000 Btu/h (11.1 kW)
Heating at 17° F COP 2.2 Btu/Btu
Heating at 17° F Rated Capacity 25000 Btu/h (7.3 kW) *3
Heating at 17° F Total Input 3330 W
Heating at 5° F Maximum Capacity 38000 Btu/h (4.8 kW)
Heating at 5° F COP 1.64 Btu/Btu
Heating at 5° F Total Input 6,760
Minimum Circuit Ampacity MCA 1 Ampere
Maximum fuse size (time delay) MOCP 15 Ampere
Recommended Fuse/Breaker Size 30 Ampere
Refrigerant Type R410A
Refrigerant Oil Type 1.4 (FV50S) [45]
Refrigerant Charge 5.5 [12 lbs]
Refrigerant Control Electronic Expansion Valve
Fan Fan motor output - kW 56
Fan Fan Motor - F.L.A. 0.57 F.L.A
External Static Pressure 0 in.WG (0 Pa)
Airflow DRY 705-810-920 CFM (20-23-26 m³/min)
Airflow WET 635-730-830 (18-21-23 m³/min)
Airflow Cooling 1730 CFM (49 m³/min)
Sound Pressure Level 43-46-49 dB(A)
Dimensions H x W x D Height 14-3/8 Inches (365 mm)
Dimensions H x W x D Width 46-1/16 Inches (1,170 mm)
Dimensions H x W x D Depth 11-5/8 Inches (295 mm)
Field Drainpipe Size O.D. 5/8 Inch (16 mm)
Refrigerant Piping Connection Method Indoor / Outdoor Flared / Flared
Operation Conditions - Indoor Intake Air Temperature Cooling - Maximum - DB , WB 90°F (32°C) DB , 73°F (23°C) WB
Operation Conditions - Indoor Intake Air Temperature Cooling - Minimum - DB , WB 66°F (19°C) DB, 59°F (15°C) WB
Operation Conditions - Indoor Intake Air Temperature Heating - Maximum - DB , WB 83°F (28°C) DB
Operation Conditions - Indoor Intake Air Temperature Heating - Minimum - DB , WB 63°F (17°C) DB
Operation Conditions - Indoor Intake Air Temperature Heating - Maximum - DB 83°F (28°C) DB
Operation Conditions - Indoor Intake Air Temperature Cooling - Maximum - DB 90°F (32°C) DB
Operation Conditions - Indoor Intake Air Temperature Cooling - Maximum -WB 73°F (23°C) WB
Operation Conditions - Outdoor Intake Air Temperature Cooling - Maximum - DB , WB 115°F (46°C) DB
Operation Conditions - Outdoor Intake Air Temperature Heating - Maximum - DB , WB 70°F (21°C) DB, 59°F (15°C) WB
Operation Conditions - Outdoor Intake Air Temperature Heating - Minimum - DB , WB -13°F (-25°C) DB, -13°F (-25°C) WB
Operation Conditions - Outdoor Intake Air Temperature Cooling - Maximum - WB 115°F (46°C) DB
Operation Conditions - Outdoor Intake Air Temperature Cooling- Minimum - DB 0°F** (-18°C) DB
Operation Conditions - Outdoor Intake Air Temperature Heating - Maximum - DB 70°F (21°C) DB
Operation Conditions - Outdoor Intake Air Temperature Cooling - Maximum - DB 115°F (46°C) DB
Operation Conditions - Outdoor Intake Air Temperature Heating - Maximum - WB 59°F (15°C) WB
External Finish Munsell 1.0Y 9.2 / 0.2
Voltage Indoor - Outdoor S1-S2 AC 208 / 230V
Voltage Indoor - Outdoor S2-S3 DC24V

Power Supply Phase, Cycle, Voltage 1 Phase, 60Hz, 208/230V *4
Cooling Rated Capacity 34200 Btu/h (10.02 kW) *1
Cooling Capacity Range 12000 - 34200 Btu/h (3.5 - 10 kW)
Cooling Total Input 5030 W (500 kW)
Cooling Energy Efficiency SEER 14
Cooling Sensible Heat Factor 0.7
Cooling EER 6.8
Cooling Moisture Removal Pints/H 9.2
Heating at 47° F Rated Capacity 37000 Btu/h (10.8 kW) *2
Heating at 47° F Capacity Range 12000 - 38000 Btu/h (3.5 - 11.1 kW)
Heating at 47° F Total Input 3610 W
Heating at 47° F HSPF (Region IV) 9.3
Heating at 47° F COP 3 Btu/Btu
Heating at 17° F COP 2 Btu/Btu
Heating at 17° F Rated Capacity 25000 Btu/h (7.3 kW) *3
Heating at 17° F Total Input 3030 W
Minimum Circuit Ampacity MCA 1 Ampere
Recommended Fuse/Breaker Size 30 Ampere
Refrigerant Oil Type 0.87 (FV50S) [28]
Refrigerant Type R410A
Refrigerant Charge 3.0 [6 lbs 10 oz]
Refrigerant Control Linear Expansion Valve
Fan Fan Motor - F.L.A. 0.057 F.L.A
Fan Fan motor output - kW 56 W
External Static Pressure 0
Airflow Cooling : DRY 705 - 810 - 920 CFM (20-23-26 m³/min)
Airflow Cooling : WET 635 -730 -830 CFM (18-21-23 m³/min)
Sound Pressure Level 43-46-49 db(A)
Dimensions H x W x D Height 37-1/8 Inches (943 mm)
Dimensions H x W x D Width 37-3/8 Inches (950 mm)
Dimensions H x W x D Depth 13 + 7/8 Inches (330 + 23 mm)
Field Drainpipe Size O.D. 5/8 Inch (16 mm)
Refrigerant Piping Connection Method Indoor / Outdoor Flared / Flared
Operation Conditions - Indoor Intake Air Temperature Cooling - Maximum - DB , WB 95°F (35°C) DB, 71°F (22°C) WB
Operation Conditions - Indoor Intake Air Temperature Cooling - Minimum - DB , WB 67°F (19°C) DB , 57°F (14°C) WB
Operation Conditions - Indoor Intake Air Temperature Heating - Maximum - DB , WB 80°F (27°C) DB, 67°F (19°C) WB
Operation Conditions - Indoor Intake Air Temperature Heating - Minimum - DB , WB 70°F (21°C) DB, 60°F (16°C) WB
Operation Conditions - Indoor Intake Air Temperature Cooling - Maximum - DB 95°F (35°C) DB
Operation Conditions - Indoor Intake Air Temperature Cooling - Maximum -WB 71°F (22°C) WB
Operation Conditions - Indoor Intake Air Temperature Cooling - Minimum - DB 67°F (19°C) DB
Operation Conditions - Indoor Intake Air Temperature Cooling - Minimum - WB 57°F (14°C) WB
Operation Conditions - Indoor Intake Air Temperature Heating - Maximum - DB 80°F (27°C) DB
Operation Conditions - Indoor Intake Air Temperature Heating - Maximum - WB 67°F (19°C) WB
Operation Conditions - Indoor Intake Air Temperature Heating - Minimum - DB 70°F (21°C) DB
Operation Conditions - Indoor Intake Air Temperature Heating - Minimum - WB 60°F (16°C) WB
Operation Conditions - Outdoor Intake Air Temperature Cooling - Maximum - DB , WB 115°F (46°C) DB
Operation Conditions - Outdoor Intake Air Temperature Heating - Maximum - DB , WB 70°F (21°C) DB, 59°F (15°C) WB
Operation Conditions - Outdoor Intake Air Temperature Heating - Minimum - DB , WB 12°F (-11°C) DB, 10°F (-12°C) WB
Operation Conditions - Outdoor Intake Air Temperature Cooling - Maximum - DB 115°F (46°C) DB
Operation Conditions - Outdoor Intake Air Temperature Cooling - Maximum - WB 115°F (46°C) DB
Operation Conditions - Outdoor Intake Air Temperature Cooling- Minimum - DB 0°F** (-18°C) DB
Operation Conditions - Outdoor Intake Air Temperature Heating - Maximum - DB 70°F (21°C) DB
Operation Conditions - Outdoor Intake Air Temperature Heating - Maximum - WB 59°F (15°C) WB
Operation Conditions - Outdoor Intake Air Temperature Heating - Minimum - DB 12°F (-11°C) DB
Operation Conditions - Outdoor Intake Air Temperature Heating - Minimum - WB 10°F (-12°C) WB
Voltage Indoor - Outdoor S1-S2 AC 208 / 230V
Voltage Indoor - Outdoor S2-S3 DC24V
External Finish Munsell 1.0Y 9.2 / 0.2

Energy Star System X
Power Supply Phase, Cycle, Voltage 1 Phase, 60Hz, 208/230V *5
Cooling Rated Capacity 33500 Btu/h (9.82 kW) *1
Cooling Capacity Range 18000 - 34200 Btu/h (5.3 - 10 kW)
Cooling Total Input 2790 W (2.800 kW)
Cooling Energy Efficiency SEER 16.2
Cooling Sensible Heat Factor 0.71
Cooling Moisture Removal Pints/H 8.7
Cooling EER 12
Heating at 47° F Rated Capacity 38000 Btu/h (11.1 kW) *2
Heating at 47° F Capacity Range 18000 - 40000 Btu/h (5.3 - 11.7 kW)
Heating at 47° F Total Input 3410 W
Heating at 47° F HSPF (Region IV) 10
Heating at 47° F COP 3.27 Btu/Btu
Heating at 17° F Maximum Capacity 38000 Btu/h (11.1 kW)
Heating at 17° F COP 2.2 Btu/Btu
Heating at 17° F Rated Capacity 25000 Btu/h (7.3 kW) *3
Heating at 17° F Total Input 3330 W
Heating at 5° F Maximum Capacity 38000 Btu/h (4.8 kW)
Heating at 5° F COP 1.64 Btu/Btu
Heating at 5° F Total Input 6,760
Minimum Circuit Ampacity MCA 1 Ampere
Maximum fuse size (time delay) MOCP 15 Ampere
Recommended Fuse/Breaker Size 30 Ampere
Refrigerant Type R410A
Refrigerant Oil Type 1.4 (FV50S) [45]
Refrigerant Charge 5.5 [12 lbs]
Refrigerant Control Electronic Expansion Valve
Fan Fan motor output - kW 56
Fan Fan Motor - F.L.A. 0.57 F.L.A
External Static Pressure 0 in.WG (0 Pa)
Airflow DRY 705-810-920 CFM (20-23-26 m³/min)
Airflow WET 635-730-830 (18-21-23 m³/min)
Airflow Cooling 1730 CFM (49 m³/min)
Sound Pressure Level 43-46-49 dB(A)
Dimensions H x W x D Height 14-3/8 Inches (365 mm)
Dimensions H x W x D Width 46-1/16 Inches (1,170 mm)
Dimensions H x W x D Depth 11-5/8 Inches (295 mm)
Field Drainpipe Size O.D. 5/8 Inch (16 mm)
Refrigerant Piping Connection Method Indoor / Outdoor Flared / Flared
Operation Conditions - Indoor Intake Air Temperature Cooling - Maximum - DB , WB 90°F (32°C) DB , 73°F (23°C) WB
Operation Conditions - Indoor Intake Air Temperature Cooling - Minimum - DB , WB 66°F (19°C) DB, 59°F (15°C) WB
Operation Conditions - Indoor Intake Air Temperature Heating - Maximum - DB , WB 83°F (28°C) DB
Operation Conditions - Indoor Intake Air Temperature Heating - Minimum - DB , WB 63°F (17°C) DB
Operation Conditions - Indoor Intake Air Temperature Heating - Maximum - DB 83°F (28°C) DB
Operation Conditions - Indoor Intake Air Temperature Cooling - Maximum - DB 90°F (32°C) DB
Operation Conditions - Indoor Intake Air Temperature Cooling - Maximum -WB 73°F (23°C) WB
Operation Conditions - Outdoor Intake Air Temperature Cooling - Maximum - DB , WB 115°F (46°C) DB
Operation Conditions - Outdoor Intake Air Temperature Heating - Maximum - DB , WB 70°F (21°C) DB, 59°F (15°C) WB
Operation Conditions - Outdoor Intake Air Temperature Heating - Minimum - DB , WB -13°F (-25°C) DB, -13°F (-25°C) WB
Operation Conditions - Outdoor Intake Air Temperature Cooling - Maximum - WB 115°F (46°C) DB
Operation Conditions - Outdoor Intake Air Temperature Cooling- Minimum - DB 0°F** (-18°C) DB
Operation Conditions - Outdoor Intake Air Temperature Heating - Maximum - DB 70°F (21°C) DB
Operation Conditions - Outdoor Intake Air Temperature Cooling - Maximum - DB 115°F (46°C) DB
Operation Conditions - Outdoor Intake Air Temperature Heating - Maximum - WB 59°F (15°C) WB
External Finish Munsell 1.0Y 9.2 / 0.2
Voltage Indoor - Outdoor S1-S2 AC 208 / 230V
Voltage Indoor - Outdoor S2-S3 DC24V