Mitsubishi Electric HVAC-Proposed - PKA - P-Series AC-0_PKA-A36KA4/PUY-A36NHA4

PKA - P-Series AC Model Number: 0_PKA-A36KA4/PUY-A36NHA4 Wall-mounted ductless indoor unit for residential and light commercial applications. Ideal for applications such as churches, classrooms, daycare centers, small offices, and more. Rated capacities range from 12,000 - 34,200 Btu/h....


MasterFormat: Central Cooling Equipment | Decentralized HVAC Equipment | Decentralized Unitary HVAC Equipment...



Mitsubishi Electric HVAC-Proposed
3400 Lawrenceville Suwanee Rd.
Suwanee, GA 30024
Tel: (800) 687-1966
Fax: (800) 658-1458

http://www.mehvac.com

Request More Info

DOWNLOADS

Related Products

Overview



PKA - P-Series AC - 0_PKA-A36KA4/PUY-A36NHA4

PKA - P-Series AC


Model Number: 0_PKA-A36KA4/PUY-A36NHA4

Wall-mounted ductless indoor unit for residential and light commercial applications. Ideal for applications such as churches, classrooms, daycare centers, small offices, and more. Rated capacities range from 12,000 - 34,200 Btu/h.


Shiny-white–exterior plastic; compact design
Sleek, slim-line design
Ductless installation
RedLINK enabled for wall-mounted wireless, hand-held wireless or wired controller
Optional i-see sensor for improved temperature sensing
Limited warranty: five years on parts and defects and seven years on compressors




Power Supply Phase, Cycle, Voltage 1 Phase, 60Hz, 208/230V *2
Cooling Rated Capacity 12000 Btu/h (3.52 kW) *1
Cooling Capacity Range 6000 - 12000 Btu/h (1.8 - 3.5 kW)
Cooling Total Input 1190 W (1.200 kW)
Cooling Energy Efficiency SEER 15.2
Cooling Sensible Heat Factor 0.81
Cooling EER 10.1
Cooling Moisture Removal Pints/H 2
Minimum Circuit Ampacity MCA 1 Ampere
Recommended Fuse/Breaker Size 15 Ampere
Refrigerant Type R410A
Refrigerant Oil Type 0.65 (MEL56) [20]
Refrigerant Charge 1.3 [2 lbs 14 oz]
Refrigerant Control Linear Expansion Valve
Fan Fan motor output 30 W
Fan Fan Motor 0.033 F.L.A
External Static Pressure 0 in.WG (0 Pa) (direct blow)
Airflow Cooling : DRY 320 - 370 - 425 CFM (9-10.5-12 m³/min)
Airflow Cooling : WET 290-335-380 CFM (8-9.5-11 m³/min)
Sound Pressure Level 36- 40-43 dB(A)
Dimensions H x W x D Height 14-3/8 Inches (365 mm)
Dimensions H x W x D Width 46-1/16 Inches (1170 mm)
Dimensions H x W x D Depth 11-5/8 Inches (295 mm)
Field Drainpipe Size O.D. 5/8 Inch (15.88 mm)
Refrigerant Piping Connection Method Indoor / Outdoor Flared / Flared
Operation Conditions - Indoor Intake Air Temperature Cooling - Maximum - DB , WB 95°F (35°C) DB, 71°F (22°C) WB
Operation Conditions - Indoor Intake Air Temperature Cooling - Minimum - DB , WB 67°F (19°C) DB , 57°F (14°C) WB
Operation Conditions - Indoor Intake Air Temperature Cooling - Minimum - WB 57°F (14°C) WB
Operation Conditions - Indoor Intake Air Temperature Cooling - Maximum - DB 95°F (35°C) DB
Operation Conditions - Indoor Intake Air Temperature Cooling - Maximum -WB 71°F (22°C) WB
Operation Conditions - Indoor Intake Air Temperature Cooling - Minimum - DB 67°F (19°C) DB
Operation Conditions - Outdoor Intake Air Temperature Cooling - Maximum - DB , WB 115°F (46°C) DB
Operation Conditions - Outdoor Intake Air Temperature Cooling - Maximum - DB 115°F (46°C) DB
Operation Conditions - Outdoor Intake Air Temperature Cooling- Minimum - DB 0°F** (-18°C) DB
Operation Conditions - Outdoor Intake Air Temperature Cooling - Maximum - WB 115°F (46°C) DB
External Finish Munsell 1.0Y 9.2 / 0.2
Voltage Indoor - Outdoor S1-S2 AC 208 / 230V
Voltage Indoor - Outdoor S2-S3 DC24V

Power Supply Phase, Cycle, Voltage 1 Phase, 60Hz, 208/230V *2
Cooling Rated Capacity 12000 Btu/h (3.52 kW) *1
Cooling Capacity Range 6000 - 12000 Btu/h (1.8 - 3.5 kW)
Cooling Total Input 1190 W (1.200 kW)
Cooling Energy Efficiency SEER 15.2
Cooling Sensible Heat Factor 0.81
Cooling EER 10.1
Cooling Moisture Removal Pints/H 2
Minimum Circuit Ampacity MCA 1 Ampere
Recommended Fuse/Breaker Size 15 Ampere
Refrigerant Type R410A
Refrigerant Oil Type 0.65 (MEL56) [20]
Refrigerant Charge 1.3 [2 lbs 14 oz]
Refrigerant Control Linear Expansion Valve
Fan Fan motor output 30 W
Fan Fan Motor 0.033 F.L.A
External Static Pressure 0 in.WG (0 Pa) (direct blow)
Airflow Cooling : DRY 320 - 370 - 425 CFM (9-10.5-12 m³/min)
Airflow Cooling : WET 290-335-380 CFM (8-9.5-11 m³/min)
Sound Pressure Level 36- 40-43 dB(A)
Dimensions H x W x D Height 14-3/8 Inches (365 mm)
Dimensions H x W x D Width 46-1/16 Inches (1170 mm)
Dimensions H x W x D Depth 11-5/8 Inches (295 mm)
Field Drainpipe Size O.D. 5/8 Inch (15.88 mm)
Refrigerant Piping Connection Method Indoor / Outdoor Flared / Flared
Operation Conditions - Indoor Intake Air Temperature Cooling - Maximum - DB , WB 95°F (35°C) DB, 71°F (22°C) WB
Operation Conditions - Indoor Intake Air Temperature Cooling - Minimum - DB , WB 67°F (19°C) DB , 57°F (14°C) WB
Operation Conditions - Indoor Intake Air Temperature Cooling - Minimum - WB 57°F (14°C) WB
Operation Conditions - Indoor Intake Air Temperature Cooling - Maximum - DB 95°F (35°C) DB
Operation Conditions - Indoor Intake Air Temperature Cooling - Maximum -WB 71°F (22°C) WB
Operation Conditions - Indoor Intake Air Temperature Cooling - Minimum - DB 67°F (19°C) DB
Operation Conditions - Outdoor Intake Air Temperature Cooling - Maximum - DB , WB 115°F (46°C) DB
Operation Conditions - Outdoor Intake Air Temperature Cooling - Maximum - DB 115°F (46°C) DB
Operation Conditions - Outdoor Intake Air Temperature Cooling- Minimum - DB 0°F** (-18°C) DB
Operation Conditions - Outdoor Intake Air Temperature Cooling - Maximum - WB 115°F (46°C) DB
External Finish Munsell 1.0Y 9.2 / 0.2
Voltage Indoor - Outdoor S1-S2 AC 208 / 230V
Voltage Indoor - Outdoor S2-S3 DC24V

Power Supply Phase, Cycle, Voltage 1 Phase, 60Hz, 208/230V *2
Cooling Rated Capacity 18000 Btu/h (5.28 kW) *1
Cooling Capacity Range 8000 - 18000 Btu/h (2.3 - 5.3 kW)
Cooling Total Input 2240 W (2.200 kW)
Cooling Energy Efficiency SEER 15.3
Cooling Sensible Heat Factor 0.68
Cooling Moisture Removal Pints/H 5.2
Cooling EER 8
Minimum Circuit Ampacity MCA 1 Ampere
Recommended Fuse/Breaker Size 15 Ampere
Refrigerant Type R410A
Refrigerant Oil Type 0.65 (MEL56) [20]
Refrigerant Charge 1.7 [3 lbs 12 oz]
Refrigerant Control Linear Expansion Valve
Fan Fan Motor - F.L.A. 0.033 F.L.A
Fan Fan motor output - kW 30 W
External Static Pressure 0 in.WG (0 Pa) (direct blow)
Airflow Cooling : DRY 320 - 370 - 425 CFM (9-10.5-12 m³/min)
Airflow Cooling : WET 290-335-380 CFM (8-9.5-11 m³/min)
Sound Pressure Level 36 - 40 - 43 dB(A)
Dimensions H x W x D Height 11-5/8 Inches (295 mm)
Dimensions H x W x D Width 35-3/8 Inches (898 mm)
Dimensions H x W x D Depth 9-13/16 Inches (249
Field Drainpipe Size O.D. 5/8 Inch (15.88 mm)
Refrigerant Piping Connection Method Indoor / Outdoor Flared / Flared
Operation Conditions - Indoor Intake Air Temperature Cooling - Maximum - DB , WB 95°F (35°C) DB, 71°F (22°C) WB
Operation Conditions - Indoor Intake Air Temperature Cooling - Minimum - DB , WB 67°F (19°C) DB , 57°F (14°C) WB
Operation Conditions - Indoor Intake Air Temperature Cooling - Minimum - WB 57°F (14°C) WB
Operation Conditions - Indoor Intake Air Temperature Cooling - Minimum - DB 67°F (19°C) DB
Operation Conditions - Indoor Intake Air Temperature Cooling - Maximum -WB 71°F (22°C) WB
Operation Conditions - Indoor Intake Air Temperature Cooling - Maximum - DB 95°F (35°C) DB
Operation Conditions - Outdoor Intake Air Temperature Cooling - Maximum - DB , WB 115°F (46°C) DB
Operation Conditions - Outdoor Intake Air Temperature Cooling- Minimum - DB 0°F** (-18°C) DB
Operation Conditions - Outdoor Intake Air Temperature Cooling - Maximum - DB 115°F (46°C) DB
Operation Conditions - Outdoor Intake Air Temperature Cooling - Maximum - WB 115°F (46°C) DB
Voltage Indoor - Outdoor S2-S3 DC24V
Voltage Indoor - Outdoor S1-S2 AC 208 / 230V
External Finish Munsell 1.0Y 9.2 / 0.2

Power Supply Phase, Cycle, Voltage 1 Phase, 60Hz, 208/230V *2
Cooling Rated Capacity 18000 Btu/h (5.28 kW) *1
Cooling Capacity Range 8000 - 18000 Btu/h (2.3 - 5.3 kW)
Cooling Total Input 2240 W (2.200 kW)
Cooling Energy Efficiency SEER 15.3
Cooling Sensible Heat Factor 0.68
Cooling Moisture Removal Pints/H 5.2
Cooling EER 8
Minimum Circuit Ampacity MCA 1 Ampere
Recommended Fuse/Breaker Size 15 Ampere
Refrigerant Type R410A
Refrigerant Oil Type 0.65 (MEL56) [20]
Refrigerant Charge 1.7 [3 lbs 12 oz]
Refrigerant Control Linear Expansion Valve
Fan Fan Motor - F.L.A. 0.033 F.L.A
Fan Fan motor output - kW 30 W
External Static Pressure 0 in.WG (0 Pa) (direct blow)
Airflow Cooling : DRY 320 - 370 - 425 CFM (9-10.5-12 m³/min)
Airflow Cooling : WET 290-335-380 CFM (8-9.5-11 m³/min)
Sound Pressure Level 36 - 40 - 43 dB(A)
Dimensions H x W x D Height 11-5/8 Inches (295 mm)
Dimensions H x W x D Width 35-3/8 Inches (898 mm)
Dimensions H x W x D Depth 9-13/16 Inches (249
Field Drainpipe Size O.D. 5/8 Inch (15.88 mm)
Refrigerant Piping Connection Method Indoor / Outdoor Flared / Flared
Operation Conditions - Indoor Intake Air Temperature Cooling - Maximum - DB , WB 95°F (35°C) DB, 71°F (22°C) WB
Operation Conditions - Indoor Intake Air Temperature Cooling - Minimum - DB , WB 67°F (19°C) DB , 57°F (14°C) WB
Operation Conditions - Indoor Intake Air Temperature Cooling - Minimum - WB 57°F (14°C) WB
Operation Conditions - Indoor Intake Air Temperature Cooling - Minimum - DB 67°F (19°C) DB
Operation Conditions - Indoor Intake Air Temperature Cooling - Maximum -WB 71°F (22°C) WB
Operation Conditions - Indoor Intake Air Temperature Cooling - Maximum - DB 95°F (35°C) DB
Operation Conditions - Outdoor Intake Air Temperature Cooling - Maximum - DB , WB 115°F (46°C) DB
Operation Conditions - Outdoor Intake Air Temperature Cooling- Minimum - DB 0°F** (-18°C) DB
Operation Conditions - Outdoor Intake Air Temperature Cooling - Maximum - DB 115°F (46°C) DB
Operation Conditions - Outdoor Intake Air Temperature Cooling - Maximum - WB 115°F (46°C) DB
Voltage Indoor - Outdoor S2-S3 DC24V
Voltage Indoor - Outdoor S1-S2 AC 208 / 230V
External Finish Munsell 1.0Y 9.2 / 0.2

Power Supply Phase, Cycle, Voltage 1 Phase, 60Hz, 208/230V *2
Cooling Rated Capacity 24000 Btu/h (7.03 kW) *1
Cooling Capacity Range 12000 - 24000 Btu/h (3.5 - 7 kW)
Cooling Total Input 2270 W (2.300 kW)
Cooling Energy Efficiency SEER 17
Cooling Sensible Heat Factor 0.77
Cooling Moisture Removal Pints/H 5
Cooling EER 10.6
Minimum Circuit Ampacity MCA 1 Ampere
Recommended Fuse/Breaker Size 25 Ampere
Refrigerant Type R410A
Refrigerant Oil Type 0.87 (FV50S) [28]
Refrigerant Charge 3.0 [6 lbs 10 oz]
Refrigerant Control Linear Expansion Valve
Fan Fan motor output - kW 56 W
Fan Fan Motor - F.L.A. 0.036 F.L.A
External Static Pressure 0 in.WG (0 Pa) (direct blow)
Airflow Cooling : DRY 635-705-775 CFM (18-20-22 m³/min)
Airflow Cooling : WET 570-635-700 CFM (16-18-20 m³/min))
Sound Pressure Level 39-42-45 dB(A)
Dimensions H x W x D Height 14-3/8 Inches (365 mm)
Dimensions H x W x D Width 46-1/16 Inches (1170 mm)
Dimensions H x W x D Depth 11-5/8 Inches (295 mm)
Field Drainpipe Size O.D. 5/8 Inch (15.88 mm)
Refrigerant Piping Connection Method Indoor / Outdoor Flared / Flared
Operation Conditions - Indoor Intake Air Temperature Cooling - Maximum - DB , WB 95°F (35°C) DB, 71°F (22°C) WB
Operation Conditions - Indoor Intake Air Temperature Cooling - Minimum - DB , WB 67°F (19°C) DB , 57°F (14°C) WB
Operation Conditions - Indoor Intake Air Temperature Cooling - Minimum - WB 57°F (14°C) WB
Operation Conditions - Indoor Intake Air Temperature Cooling - Maximum - DB 95°F (35°C) DB
Operation Conditions - Indoor Intake Air Temperature Cooling - Maximum -WB 71°F (22°C) WB
Operation Conditions - Indoor Intake Air Temperature Cooling - Minimum - DB 67°F (19°C) DB
Operation Conditions - Outdoor Intake Air Temperature Cooling - Maximum - DB , WB 115°F (46°C) DB
Operation Conditions - Outdoor Intake Air Temperature Cooling - Maximum - DB 115°F (46°C) DB
Operation Conditions - Outdoor Intake Air Temperature Cooling- Minimum - DB 0°F** (-18°C) DB
Operation Conditions - Outdoor Intake Air Temperature Cooling - Maximum - WB 115°F (46°C) DB
External Finish Munsell 1.0Y 9.2 / 0.2
Voltage Indoor - Outdoor S1-S2 AC 208 / 230V
Voltage Indoor - Outdoor S2-S3 DC24V

Power Supply Phase, Cycle, Voltage 1 Phase, 60Hz, 208/230V *2
Cooling Rated Capacity 24000 Btu/h (7.03 kW) *1
Cooling Capacity Range 12000 - 24000 Btu/h (3.5 - 7 kW)
Cooling Total Input 2270 W (2.300 kW)
Cooling Energy Efficiency SEER 17
Cooling Sensible Heat Factor 0.77
Cooling Moisture Removal Pints/H 5
Cooling EER 10.6
Minimum Circuit Ampacity MCA 1 Ampere
Recommended Fuse/Breaker Size 25 Ampere
Refrigerant Type R410A
Refrigerant Oil Type 0.87 (FV50S) [28]
Refrigerant Charge 3.0 [6 lbs 10 oz]
Refrigerant Control Linear Expansion Valve
Fan Fan motor output - kW 56 W
Fan Fan Motor - F.L.A. 0.036 F.L.A
External Static Pressure 0 in.WG (0 Pa) (direct blow)
Airflow Cooling : DRY 635-705-775 CFM (18-20-22 m³/min)
Airflow Cooling : WET 570-635-700 CFM (16-18-20 m³/min))
Sound Pressure Level 39-42-45 dB(A)
Dimensions H x W x D Height 14-3/8 Inches (365 mm)
Dimensions H x W x D Width 46-1/16 Inches (1170 mm)
Dimensions H x W x D Depth 11-5/8 Inches (295 mm)
Field Drainpipe Size O.D. 5/8 Inch (15.88 mm)
Refrigerant Piping Connection Method Indoor / Outdoor Flared / Flared
Operation Conditions - Indoor Intake Air Temperature Cooling - Maximum - DB , WB 95°F (35°C) DB, 71°F (22°C) WB
Operation Conditions - Indoor Intake Air Temperature Cooling - Minimum - DB , WB 67°F (19°C) DB , 57°F (14°C) WB
Operation Conditions - Indoor Intake Air Temperature Cooling - Minimum - WB 57°F (14°C) WB
Operation Conditions - Indoor Intake Air Temperature Cooling - Maximum - DB 95°F (35°C) DB
Operation Conditions - Indoor Intake Air Temperature Cooling - Maximum -WB 71°F (22°C) WB
Operation Conditions - Indoor Intake Air Temperature Cooling - Minimum - DB 67°F (19°C) DB
Operation Conditions - Outdoor Intake Air Temperature Cooling - Maximum - DB , WB 115°F (46°C) DB
Operation Conditions - Outdoor Intake Air Temperature Cooling - Maximum - DB 115°F (46°C) DB
Operation Conditions - Outdoor Intake Air Temperature Cooling- Minimum - DB 0°F** (-18°C) DB
Operation Conditions - Outdoor Intake Air Temperature Cooling - Maximum - WB 115°F (46°C) DB
External Finish Munsell 1.0Y 9.2 / 0.2
Voltage Indoor - Outdoor S1-S2 AC 208 / 230V
Voltage Indoor - Outdoor S2-S3 DC24V

Power Supply Phase, Cycle, Voltage 1 Phase, 60Hz, 208/230V *2
Cooling Rated Capacity 30000 Btu/h (8.79 kW) *1
Cooling Capacity Range 12000 - 30000 Btu/h (3.5 - 8.8 kW)
Cooling Total Input 4130 W (4.100 kW)
Cooling Energy Efficiency SEER 15.5
Cooling Sensible Heat Factor 0.7
Cooling EER 7.3
Cooling Moisture Removal Pints/H 8.1
Minimum Circuit Ampacity MCA 1 Ampere
Recommended Fuse/Breaker Size 30 Ampere
Refrigerant Oil Type 0.87 (FV50S) [28]
Refrigerant Type R410A
Refrigerant Charge 3.0 [6 lbs 10 oz]
Refrigerant Control Linear Expansion Valve
Fan Fan Motor - F.L.A. 0.036 F.L.A
Fan Fan motor output - kW 56 W
External Static Pressure 0 (direct blow)
Airflow Cooling : DRY 635-705-775 CFM (18-20-22 m³/min)
Airflow Cooling : WET 570-635-700 CFM (16-18-20 m³/min)
Sound Pressure Level 39-42-45 dB(A)
Dimensions H x W x D Height 14-3/8 Inches (365 mm)
Dimensions H x W x D Width 46-1/16 Inches (1170 mm)
Dimensions H x W x D Depth 11-5/8 Inches (295 mm)
Field Drainpipe Size O.D. 5/8 Inch (16 mm)
Refrigerant Piping Connection Method Indoor / Outdoor Flared / Flared
Operation Conditions - Indoor Intake Air Temperature Cooling - Maximum - DB , WB 95°F (35°C) DB, 71°F (22°C) WB
Operation Conditions - Indoor Intake Air Temperature Cooling - Minimum - DB , WB 67°F (19°C) DB , 57°F (14°C) WB
Operation Conditions - Indoor Intake Air Temperature Cooling - Maximum - DB 95°F (35°C) DB
Operation Conditions - Indoor Intake Air Temperature Cooling - Maximum -WB 71°F (22°C) WB
Operation Conditions - Indoor Intake Air Temperature Cooling - Minimum - DB 67°F (19°C) DB
Operation Conditions - Indoor Intake Air Temperature Cooling - Minimum - WB 57°F (14°C) WB
Operation Conditions - Outdoor Intake Air Temperature Cooling - Maximum - DB , WB 115°F (46°C) DB
Operation Conditions - Outdoor Intake Air Temperature Cooling - Maximum - DB 115°F (46°C) DB
Operation Conditions - Outdoor Intake Air Temperature Cooling - Maximum - WB 115°F (46°C) DB
Operation Conditions - Outdoor Intake Air Temperature Cooling- Minimum - DB 0°F** (-18°C) DB
Voltage Indoor - Outdoor S1-S2 AC 208 / 230V
Voltage Indoor - Outdoor S2-S3 DC24V
External Finish Munsell 1.0Y 9.2 / 0.2

Power Supply Phase, Cycle, Voltage 1 Phase, 60Hz, 208/230V *2
Cooling Rated Capacity 30000 Btu/h (8.79 kW) *1
Cooling Capacity Range 12000 - 30000 Btu/h (3.5 - 8.8 kW)
Cooling Total Input 4130 W (4.100 kW)
Cooling Energy Efficiency SEER 15.5
Cooling Sensible Heat Factor 0.7
Cooling EER 7.3
Cooling Moisture Removal Pints/H 8.1
Minimum Circuit Ampacity MCA 1 Ampere
Recommended Fuse/Breaker Size 30 Ampere
Refrigerant Oil Type 0.87 (FV50S) [28]
Refrigerant Type R410A
Refrigerant Charge 3.0 [6 lbs 10 oz]
Refrigerant Control Linear Expansion Valve
Fan Fan Motor - F.L.A. 0.036 F.L.A
Fan Fan motor output - kW 56 W
External Static Pressure 0 (direct blow)
Airflow Cooling : DRY 635-705-775 CFM (18-20-22 m³/min)
Airflow Cooling : WET 570-635-700 CFM (16-18-20 m³/min)
Sound Pressure Level 39-42-45 dB(A)
Dimensions H x W x D Height 14-3/8 Inches (365 mm)
Dimensions H x W x D Width 46-1/16 Inches (1170 mm)
Dimensions H x W x D Depth 11-5/8 Inches (295 mm)
Field Drainpipe Size O.D. 5/8 Inch (16 mm)
Refrigerant Piping Connection Method Indoor / Outdoor Flared / Flared
Operation Conditions - Indoor Intake Air Temperature Cooling - Maximum - DB , WB 95°F (35°C) DB, 71°F (22°C) WB
Operation Conditions - Indoor Intake Air Temperature Cooling - Minimum - DB , WB 67°F (19°C) DB , 57°F (14°C) WB
Operation Conditions - Indoor Intake Air Temperature Cooling - Maximum - DB 95°F (35°C) DB
Operation Conditions - Indoor Intake Air Temperature Cooling - Maximum -WB 71°F (22°C) WB
Operation Conditions - Indoor Intake Air Temperature Cooling - Minimum - DB 67°F (19°C) DB
Operation Conditions - Indoor Intake Air Temperature Cooling - Minimum - WB 57°F (14°C) WB
Operation Conditions - Outdoor Intake Air Temperature Cooling - Maximum - DB , WB 115°F (46°C) DB
Operation Conditions - Outdoor Intake Air Temperature Cooling - Maximum - DB 115°F (46°C) DB
Operation Conditions - Outdoor Intake Air Temperature Cooling - Maximum - WB 115°F (46°C) DB
Operation Conditions - Outdoor Intake Air Temperature Cooling- Minimum - DB 0°F** (-18°C) DB
Voltage Indoor - Outdoor S1-S2 AC 208 / 230V
Voltage Indoor - Outdoor S2-S3 DC24V
External Finish Munsell 1.0Y 9.2 / 0.2

Power Supply Phase, Cycle, Voltage 1 Phase, 60Hz, 208/230V *2
Cooling Rated Capacity 34200 Btu/h (10.02 kW) *1
Cooling Capacity Range 12000 - 34200 BTU/h (3.5 - 10 kW)
Cooling Total Input 5030 W (500 kW)
Cooling Energy Efficiency SEER 14
Cooling Sensible Heat Factor 0.7
Cooling EER 6.8
Cooling Moisture Removal 9.2 Pints/H
Minimum Circuit Ampacity MCA 1 Ampere
Recommended Fuse/Breaker Size 30 Ampere
Refrigerant Type R410A
Refrigerant Oil Type 0.87 (FV50S) [28]
Refrigerant Charge 3.0 [6 lbs 10 oz]
Refrigerant Control Linear Expansion Valve
Fan Fan Motor 0.057 F.L.A
Fan Fan motor output 56 W
External Static Pressure 0 (direct blow)
Airflow Cooling : DRY 705 - 810 - 920 CFM (20-23-26 m³/min)
Airflow Cooling : WET 635 -730 -830 CFM (18-21-23 m³/min)
Sound Pressure Level Cooling 43-46-49 db(A)
Dimensions H x W x D Height 14-3/8 Inches (365 mm)
Dimensions H x W x D Width 46-1/16 Inches (1170 mm)
Dimensions H x W x D Depth 11-5/8 Inches (295 mm)
Field Drainpipe Size O.D. 5/8 Inch (16 mm)
Refrigerant Piping Connection Method Indoor / Outdoor Flared / Flared
Operation Conditions - Indoor Intake Air Temperature Cooling - Maximum - DB , WB 95°F (35°C) DB, 71°F (22°C) WB
Operation Conditions - Indoor Intake Air Temperature Cooling - Minimum - DB , WB 67°F (19°C) DB , 57°F (14°C) WB
Operation Conditions - Indoor Intake Air Temperature Cooling - Maximum - DB 95°F (35°C) DB
Operation Conditions - Indoor Intake Air Temperature Cooling - Maximum -WB 71°F (22°C) WB
Operation Conditions - Indoor Intake Air Temperature Cooling - Minimum - DB 67°F (19°C) DB
Operation Conditions - Indoor Intake Air Temperature Cooling - Minimum - WB 57°F (14°C) WB
Operation Conditions - Outdoor Intake Air Temperature Cooling - Maximum - DB , WB 115°F (46°C) DB
Operation Conditions - Outdoor Intake Air Temperature Cooling - Maximum - DB 115°F (46°C) DB
Operation Conditions - Outdoor Intake Air Temperature Cooling- Minimum - DB 0°F** (-18°C) DB
Voltage Indoor - Outdoor S1-S2 AC 208 / 230V
Voltage Indoor - Outdoor S2-S3 DC24V
External Finish Munsell 1.0Y 9.2 / 0.2

Power Supply Phase, Cycle, Voltage 1 Phase, 60Hz, 208/230V *2
Cooling Rated Capacity 34200 Btu/h (10.02 kW) *1
Cooling Capacity Range 12000 - 34200 BTU/h (3.5 - 10 kW)
Cooling Total Input 5030 W (500 kW)
Cooling Energy Efficiency SEER 14
Cooling Sensible Heat Factor 0.7
Cooling EER 6.8
Cooling Moisture Removal 9.2 Pints/H
Minimum Circuit Ampacity MCA 1 Ampere
Recommended Fuse/Breaker Size 30 Ampere
Refrigerant Type R410A
Refrigerant Oil Type 0.87 (FV50S) [28]
Refrigerant Charge 3.0 [6 lbs 10 oz]
Refrigerant Control Linear Expansion Valve
Fan Fan Motor 0.057 F.L.A
Fan Fan motor output 56 W
External Static Pressure 0 (direct blow)
Airflow Cooling : DRY 705 - 810 - 920 CFM (20-23-26 m³/min)
Airflow Cooling : WET 635 -730 -830 CFM (18-21-23 m³/min)
Sound Pressure Level Cooling 43-46-49 db(A)
Dimensions H x W x D Height 14-3/8 Inches (365 mm)
Dimensions H x W x D Width 46-1/16 Inches (1170 mm)
Dimensions H x W x D Depth 11-5/8 Inches (295 mm)
Field Drainpipe Size O.D. 5/8 Inch (16 mm)
Refrigerant Piping Connection Method Indoor / Outdoor Flared / Flared
Operation Conditions - Indoor Intake Air Temperature Cooling - Maximum - DB , WB 95°F (35°C) DB, 71°F (22°C) WB
Operation Conditions - Indoor Intake Air Temperature Cooling - Minimum - DB , WB 67°F (19°C) DB , 57°F (14°C) WB
Operation Conditions - Indoor Intake Air Temperature Cooling - Maximum - DB 95°F (35°C) DB
Operation Conditions - Indoor Intake Air Temperature Cooling - Maximum -WB 71°F (22°C) WB
Operation Conditions - Indoor Intake Air Temperature Cooling - Minimum - DB 67°F (19°C) DB
Operation Conditions - Indoor Intake Air Temperature Cooling - Minimum - WB 57°F (14°C) WB
Operation Conditions - Outdoor Intake Air Temperature Cooling - Maximum - DB , WB 115°F (46°C) DB
Operation Conditions - Outdoor Intake Air Temperature Cooling - Maximum - DB 115°F (46°C) DB
Operation Conditions - Outdoor Intake Air Temperature Cooling- Minimum - DB 0°F** (-18°C) DB
Voltage Indoor - Outdoor S1-S2 AC 208 / 230V
Voltage Indoor - Outdoor S2-S3 DC24V
External Finish Munsell 1.0Y 9.2 / 0.2

Mitsubishi Electric HVAC
3400 Lawrenceville Suwanee Rd.
Suwanee,  GA USA 30024 
Tel: (800) 687-1966
Fax: (800) 658-1458
Website: http://www.mehvac.com

Sweets app for Revit – Learn More