Mitsubishi Electric HVAC-Proposed - MSZ-FE/MUZ-FE - M-Series Heat Pump Systems-0_MUZ-FE09NA-1

MSZ-FE/MUZ-FE - M-Series Heat Pump Systems Model Number: 0_MUZ-FE09NA-1 Slim, wall-mounted indoor units provide zone comfort control. INVERTER-driven compressors and electronic LEV's provide higher efficiency with controlled power usage. The outdoor unit powers the indoor unit, and should a power...


MasterFormat: Central HVAC Equipment | Decentralized Unitary HVAC Equipment | Air-Source Unitary Heat Pumps...



Mitsubishi Electric HVAC-Proposed
3400 Lawrenceville Suwanee Rd.
Suwanee, GA 30024
Tel: (800) 687-1966
Fax: (800) 658-1458

http://www.mehvac.com

Request More Info

DOWNLOADS

Related Products

Overview



MSZ-FE/MUZ-FE - M-Series Heat Pump Systems - 0_MUZ-FE09NA-1

MSZ-FE/MUZ-FE - M-Series Heat Pump Systems


Model Number: 0_MUZ-FE09NA-1

Slim, wall-mounted indoor units provide zone comfort control. INVERTER-driven compressors and electronic LEV's provide higher efficiency with controlled power usage. The outdoor unit powers the indoor unit, and should a power outage occur, the system is automatically restored when power returns.


Complete individual Zone/Room control for exceptional comfort
Premium, high efficiency performance allows maximum comfort with controlled capacity and power consumption
SEER Values up to 26, HSPF up to 10.5 and EER up to 15.5
INVERTER driven compressor and LEV provide high efficiency comfort while using only the energy needed to maintain maximum performance
H2i - Hyper Heat Performance offers full capacity heating at 5°F (9 & 12kBTU) and 73% capacity at -13°F (18kBTU)
Choice of fan speeds: Quiet, Low, Medium, High, and Super High; Auto fan speed control also included
Advanced microprocessor technology and control
Equipped with standard Wireless, IR, Handheld, Remote Controller also offers optional Wireless, RFI-RedLINK™, Full Function, Wall-mount, Remote Controller - MHK1 or Wired Full Function Wall-mount Remote Controller - PAR-21MA
9,000 and 12,000 BTU Systems offer i-See® Sensor Technology and Triple Filtration for total indoor comfort
Hot-start technology - no cold air rush at start-up or re-start after defrost




Energy Star System X
Power Supply Phase, Cycle, Voltage 1 Phase, 60Hz, 208/230V *4
Cooling Rated Capacity 9000 Btu/h (2.64 kW) *1
Cooling Capacity Range 2800 - 9000 BTU/h (0.8 - 2.6 kW)
Cooling Total Input 580 W (0.6 kW)
Cooling Energy Efficiency SEER 26
Cooling Sensible Heat Factor 0.76
Cooling Moisture Removal Pints/H 2.1
Cooling EER 15.5
Heating at 47° F Rated Capacity 10900 Btu/h (3.2 kW) *2
Heating at 47° F Capacity Range 3000 - 18000 Btu/h (0.9 - 5.3 kW)
Heating at 47° F Total Input 710 (150 - 2250) W
Heating at 47° F HSPF (Region IV) 10
Heating at 47° F COP 4.5
Heating at 17° F Maximum Capacity 12500 Btu/h (3.7 kW)
Heating at 17° F COP 3.02 Btu/Btu
Heating at 17° F Total Input 650 W
Heating at 17° F Rated Capacity 6700 Btu/h (2 kW) *3
Heating at 5° F Maximum Capacity 10900 Btu/h (4.8 kW)
Minimum Circuit Ampacity MCA 1 Ampere
Recommended Fuse/Breaker Size 15 Ampere
Refrigerant Type R410A
Fan Fan Motor - F.L.A. 0.76 F.L.A
Airflow Cooling : DRY 162-226-339-381 CFM (4-6-9-10 m³/min)
Airflow Cooling : WET 144-202-307-343 CFM (4-6-9-10 m³/min)
Airflow Heating : WET 166-240-367-381 CFM (5-7-10-11 m³/min)
Sound Pressure Level Cooling 22-31-39-42 dB(A)
Sound Pressure Level Heating 22-31-40-42 dB(A)
Dimensions H x W x D Height 11-5/8 Inches (295 mm)
Dimensions H x W x D Width 31-3/8 Inches (799 mm)
Dimensions H x W x D Depth 10-1/8 Inches (257 mm)
Refrigerant Pipe Size O.D. Gas (Low Pressure) 3/8 Inch (9.52 mm)
Refrigerant Pipe Size O.D. Liquid (High Pressure) 1/4 Inch (6.35 mm)
Field Drainpipe Size O.D. 5/8 Inch (15.88 mm)
Refrigerant Piping Connection Method Indoor / Outdoor Flared / Flared
Operation Conditions - Indoor Intake Air Temperature Cooling - Maximum - DB , WB 90°F (32°C) DB , 73°F (23°C) WB
Operation Conditions - Indoor Intake Air Temperature Cooling - Minimum - DB , WB 67°F (19°C) DB , 57°F (14°C) WB
Operation Conditions - Indoor Intake Air Temperature Heating - Maximum - DB , WB 80°F (27°C) DB, 67°F (19°C) WB
Operation Conditions - Indoor Intake Air Temperature Heating - Minimum - DB , WB 70°F (21°C) DB, 60°F (16°C) WB
Operation Conditions - Indoor Intake Air Temperature Heating - Minimum - WB 60°F (16°C) WB
Operation Conditions - Indoor Intake Air Temperature Heating - Minimum - DB 70°F (21°C) DB
Operation Conditions - Indoor Intake Air Temperature Cooling - Minimum - DB 67°F (19°C) DB
Operation Conditions - Indoor Intake Air Temperature Cooling - Maximum -WB 73°F (23°C) WB
Operation Conditions - Indoor Intake Air Temperature Cooling - Maximum - DB 90°F (32°C) DB
Operation Conditions - Indoor Intake Air Temperature Heating - Maximum - DB 80°F (27°C) DB
Operation Conditions - Indoor Intake Air Temperature Heating - Maximum - WB 67°F (19°C) WB
Operation Conditions - Indoor Intake Air Temperature Cooling - Minimum - WB 57°F (14°C) WB
Operation Conditions - Outdoor Intake Air Temperature Cooling - Maximum - DB , WB 115°F (46°C) DB
Operation Conditions - Outdoor Intake Air Temperature Heating - Maximum - DB , WB 75°F (24°C) DB, 65°F (18°C) WB
Operation Conditions - Outdoor Intake Air Temperature Heating - Minimum - DB , WB -13°F (-25°C) DB, -15°F (-26°C) WB
Operation Conditions - Outdoor Intake Air Temperature Heating - Minimum - WB -15°F (-26°C) WB
Operation Conditions - Outdoor Intake Air Temperature Heating - Minimum - DB -13°F (-25°C) DB
Operation Conditions - Outdoor Intake Air Temperature Heating - Maximum - WB 65°F (18°C) WB
Operation Conditions - Outdoor Intake Air Temperature Cooling - Maximum - DB 115°F (46°C) DB
Operation Conditions - Outdoor Intake Air Temperature Heating - Maximum - DB 75°F (24°C) DB
Operation Conditions - Outdoor Intake Air Temperature Cooling- Minimum - DB 14°F (-10°C) DB
External Finish Munsell 1.0Y 9.2 / 0.2
Voltage Indoor - Outdoor S2-S3 DC 12-24V
Voltage Indoor - Outdoor S1-S2 AC 208 / 230V

Energy Star System X
Power Supply Phase, Cycle, Voltage 1 Phase, 60Hz, 208/230V *4
Cooling Rated Capacity 12000 Btu/h (3.52 kW) *1
Cooling Capacity Range 2800 - 12000 Btu/h (0.8 - 3.5 kW)
Cooling Total Input 930 W (0.9 kW)
Cooling Energy Efficiency SEER 23
Cooling Sensible Heat Factor 0.73
Cooling Moisture Removal Pints/H 2.9
Cooling EER 12.9
Heating at 47° F Rated Capacity 13600 Btu/h (4 kW) *2
Heating at 47° F Capacity Range 3000 - 21000 Btu/h (0.9 - 6.2 kW)
Heating at 47° F Total Input 950 (150 - 2250) W
Heating at 47° F HSPF (Region IV) 8.2
Heating at 47° F COP 4.2
Heating at 17° F Maximum Capacity 13600 Btu/h (4 kW)
Heating at 17° F COP 3.04 Btu/Btu
Heating at 17° F Rated Capacity 7900 Btu/h (2.3 kW) *3
Heating at 17° F Total Input 750 W
Heating at 5° F Maximum Capacity 13600 Btu/h (4 kW)
Minimum Circuit Ampacity MCA 1 Ampere
Recommended Fuse/Breaker Size 15 Ampere
Refrigerant Type R410A
Fan Fan Motor - F.L.A. 0.76 F.L.A
Airflow Cooling : DRY 162-226-339-381 CFM (4-6-9-10 m³/min)
Airflow Cooling : WET 144-202-307-343 CFM (4-6-9 m³/min)
Airflow Heating : WET 166-240-367-381 CFM (5-7-10-11 m³/min)
Sound Pressure Level Heating 22-31-40-42 dB(A)
Sound Pressure Level Cooling 22-31-39-42 dB(A)
Dimensions H x W x D Height 11-5/8 Inches (295 mm)
Dimensions H x W x D Width 31-3/8 Inches (799 mm)
Dimensions H x W x D Depth 10-1/8 Inches (257 mm)
Refrigerant Pipe Size O.D. Gas (Low Pressure) 3/8 Inch (9.52 mm)
Refrigerant Pipe Size O.D. Liquid (High Pressure) 5/8 Inch (16 mm)
Field Drainpipe Size O.D. 5/8 Inch (16 mm)
Refrigerant Piping Connection Method Indoor / Outdoor Flared / Flared
Operation Conditions - Indoor Intake Air Temperature Cooling - Maximum - DB , WB 90°F (32°C) DB , 73°F (23°C) WB
Operation Conditions - Indoor Intake Air Temperature Cooling - Minimum - DB , WB 67°F (19°C) DB , 57°F (14°C) WB
Operation Conditions - Indoor Intake Air Temperature Heating - Maximum - DB , WB 80°F (27°C) DB, 67°F (19°C) WB
Operation Conditions - Indoor Intake Air Temperature Heating - Minimum - DB , WB 70°F (21°C) DB, 60°F (16°C) WB
Operation Conditions - Indoor Intake Air Temperature Heating - Maximum - DB 80°F (27°C) DB, 67°F (19°C) WB
Operation Conditions - Indoor Intake Air Temperature Cooling - Minimum - WB 57°F (14°C) WB
Operation Conditions - Indoor Intake Air Temperature Heating - Maximum - WB 67°F (19°C) WB
Operation Conditions - Indoor Intake Air Temperature Cooling - Maximum - DB 90°F (32°C) DB
Operation Conditions - Indoor Intake Air Temperature Cooling - Maximum -WB 73°F (23°C) WB
Operation Conditions - Indoor Intake Air Temperature Cooling - Minimum - DB 67°F (19°C) DB
Operation Conditions - Indoor Intake Air Temperature Heating - Minimum - DB 70°F (21°C) DB
Operation Conditions - Indoor Intake Air Temperature Heating - Minimum - WB 60°F (16°C) WB
Operation Conditions - Outdoor Intake Air Temperature Cooling - Maximum - DB , WB 115°F (46°C) DB
Operation Conditions - Outdoor Intake Air Temperature Heating - Maximum - DB , WB 75°F (24°C) DB, 65°F (18°C) WB
Operation Conditions - Outdoor Intake Air Temperature Heating - Minimum - DB , WB -13°F (-25°C) DB, -15°F (-26°C) WB
Operation Conditions - Outdoor Intake Air Temperature Cooling - Maximum - DB 115°F (46°C) DB
Operation Conditions - Outdoor Intake Air Temperature Heating - Maximum - WB 65°F (18°C) WB
Operation Conditions - Outdoor Intake Air Temperature Heating - Minimum - DB -13°F (-25°C) DB
Operation Conditions - Outdoor Intake Air Temperature Heating - Minimum - WB -15°F (-26°C) WB
Operation Conditions - Outdoor Intake Air Temperature Cooling- Minimum - DB 14°F (-10°C) DB
Operation Conditions - Outdoor Intake Air Temperature Cooling - Maximum - WB 115°F (46°C) DB
Operation Conditions - Outdoor Intake Air Temperature Heating - Maximum - DB 75°F (24°C) DB
External Finish Munsell 1.0Y 9.2 / 0.2
Voltage Indoor - Outdoor S1-S2 AC 208 / 230V
Voltage Indoor - Outdoor S2-S3 DC 12-24V

Energy Star System X
Power Supply Phase, Cycle, Voltage 1 Phase, 60Hz, 208/230V *4
Cooling Rated Capacity 18000 Btu/h (5.28 kW) *1
Cooling Capacity Range 8200 - 25200 Btu/h (2.4 - 7.4 kW)
Cooling Total Input 1270 W (1.3 kW)
Cooling Energy Efficiency SEER 20.2
Cooling Sensible Heat Factor 0.84
Cooling Moisture Removal Pints/H 2.7
Cooling EER 14.2
Heating at 47° F Rated Capacity 21600 Btu/h (6.3 kW) *2
Heating at 47° F Capacity Range 7500 - 29700 Btu/h (2.2 - 8.7 kW)
Heating at 47° F Total Input 1540 (520 - 2240) W
Heating at 47° F HSPF (Region IV) 10.5
Heating at 47° F COP 4.11
Heating at 17° F Maximum Capacity 21600 Btu/h (6.3 kW)
Heating at 17° F COP 2.76 Btu/Btu
Heating at 17° F Total Input 1240 W
Heating at 17° F Rated Capacity 11700 Btu/h (3.4 kW) *3
Heating at 5° F Maximum Capacity 21600 Btu/h (4.8 kW)
Minimum Circuit Ampacity MCA 1 Ampere
Recommended Fuse/Breaker Size 20 Ampere
Refrigerant Type R410A
Fan Fan Motor - F.L.A. 0.76 F.L.A
Airflow Cooling : DRY 162-226-381-410 CFM (4-6-10-11 m³/min)
Airflow Cooling : WET 144-202-350-367CFM (4-6-10-10 m³/min)
Airflow Heating : WET 166-240-399-420 CFM (5-7-11-12 m³/min)
Sound Pressure Level Cooling 22-33-43-45 dB(A)
Sound Pressure Level Heating 22-33-43-44 dB(A)
Dimensions H x W x D Height 12-13/16 Inches (325 mm)
Dimensions H x W x D Width 43-5/16 Inches (1,116 mm)
Dimensions H x W x D Depth 9-3/8 Inches (238 mm)
Refrigerant Pipe Size O.D. Gas (Low Pressure) 5/8 Inch (16 mm)
Refrigerant Pipe Size O.D. Liquid (High Pressure) 3/8 Inch (9.52 mm)
Field Drainpipe Size O.D. 5/8 Inch (15.88 mm)
Refrigerant Piping Connection Method Indoor / Outdoor Flared / Flared
Operation Conditions - Indoor Intake Air Temperature Cooling - Maximum - DB , WB 90°F (32°C) DB , 73°F (23°C) WB
Operation Conditions - Indoor Intake Air Temperature Cooling - Minimum - DB , WB 67°F (19°C) DB , 57°F (14°C) WB
Operation Conditions - Indoor Intake Air Temperature Heating - Maximum - DB , WB 80°F (27°C) DB, 67°F (19°C) WB
Operation Conditions - Indoor Intake Air Temperature Heating - Minimum - DB , WB 70°F (21°C) DB, 60°F (16°C) WB
Operation Conditions - Indoor Intake Air Temperature Heating - Maximum - WB 67°F (19°C) WB
Operation Conditions - Indoor Intake Air Temperature Cooling - Minimum - WB 57°F (14°C) WB
Operation Conditions - Indoor Intake Air Temperature Heating - Minimum - WB 60°F (16°C) WB
Operation Conditions - Indoor Intake Air Temperature Heating - Minimum - DB 70°F (21°C) DB
Operation Conditions - Indoor Intake Air Temperature Cooling - Minimum - DB 67°F (19°C) DB
Operation Conditions - Indoor Intake Air Temperature Cooling - Maximum -WB 73°F (23°C) WB
Operation Conditions - Indoor Intake Air Temperature Cooling - Maximum - DB 90°F (32°C) DB
Operation Conditions - Indoor Intake Air Temperature Heating - Maximum - DB 80°F (27°C) DB
Operation Conditions - Outdoor Intake Air Temperature Cooling - Maximum - DB , WB 115°F (46°C) DB
Operation Conditions - Outdoor Intake Air Temperature Heating - Maximum - DB , WB 75°F (24°C) DB, 65°F (18°C) WB
Operation Conditions - Outdoor Intake Air Temperature Heating - Minimum - DB , WB -13°F (-25°C) DB, -15°F (-26°C) WB
Operation Conditions - Outdoor Intake Air Temperature Cooling- Minimum - DB 14°F (-10°C) DB
Operation Conditions - Outdoor Intake Air Temperature Heating - Maximum - DB 75°F (24°C) DB
Operation Conditions - Outdoor Intake Air Temperature Heating - Minimum - WB -15°F (-26°C) WB
Operation Conditions - Outdoor Intake Air Temperature Heating - Minimum - DB -13°F (-25°C) DB
Operation Conditions - Outdoor Intake Air Temperature Heating - Maximum - WB 65°F (18°C) WB
Operation Conditions - Outdoor Intake Air Temperature Cooling - Maximum - DB 115°F (46°C) DB
External Finish Munsell 1.0Y 9.2 / 0.2
Defrost Method Reverse Cycle
Voltage Indoor - Outdoor S2-S3 DC 12-24V
Voltage Indoor - Outdoor S1-S2 AC 208 / 230V

Energy Star System X
Power Supply Phase, Cycle, Voltage 1 Phase, 60Hz, 208/230V *4
Cooling Rated Capacity 9000 Btu/h (2.64 kW) *1
Cooling Capacity Range 2800 - 9000 Btu/h (0.8 - 2.6 kW)
Cooling Total Input 580 W (0.6 kW)
Cooling Energy Efficiency SEER 26
Cooling Sensible Heat Factor 0.76
Cooling EER 15.5
Cooling Moisture Removal Pints/H 2.1
Heating at 47° F Rated Capacity 10900 Btu/h (3.2 kW) *2
Heating at 47° F Capacity Range 3000 - 18000 Btu/h (0.9 - 5.3 kW)
Heating at 47° F Total Input 710 (150 - 2250) W
Heating at 47° F HSPF (Region IV) 10
Heating at 47° F COP 4.5
Heating at 17° F Maximum Capacity 12500 Btu/h (3.7 kW)
Heating at 17° F COP 3.02 Btu/Btu
Heating at 17° F Rated Capacity 6700 Btu/h (2 kW) *3
Heating at 17° F Total Input 650 W
Heating at 5° F Maximum Capacity 10900 Btu/h (4.8 kW)
Minimum Circuit Ampacity MCA 12 Ampere
Maximum fuse size (time delay) MOCP 15 Ampere
Recommended Fuse/Breaker Size 15 Ampere
Refrigerant Oil Type NEO22 (15.2)
Refrigerant Type R410A
Refrigerant Charge 2, 9
Refrigerant Control Linear Expansion Valve
Compressor Type DC INVERTER-driven Twin Rotary
Compressor Model SNB130FQBHT
Compressor R.L.A. 8.6
Compressor L.R.A. 10.8
Fan Fan Motor - F.L.A. 0.56 F.L.A
Airflow Cooling 1102 CFM (31 m³/min)
Airflow Heating 1187 CFM (34 m³/min)
Sound Pressure Level Cooling 48 dB(A)
Sound Pressure Level Heating 49 dB(A)
Dimensions H x W x D Height 21-5/8 Inches (549 mm)
Dimensions H x W x D Width 31-1/2 Inches (800 mm)
Dimensions H x W x D Depth 11-1/4 Inches (286 mm)
Refrigerant Pipe Size O.D. Gas (Low Pressure) 3/8 Inch (9.52 mm)
Refrigerant Pipe Size O.D. Liquid (High Pressure) 1/4 Inch (6.35 mm)
Maximum Refrigerant Pipe Height Difference 40 ft. (12 m)
Maximum Refrigerant Pipe Length 65 ft. (20 m)
Refrigerant Piping Connection Method Indoor / Outdoor Flared / Flared
Operation Conditions - Indoor Intake Air Temperature Cooling - Maximum - DB , WB 90°F (32°C) DB , 73°F (23°C) WB
Operation Conditions - Indoor Intake Air Temperature Cooling - Minimum - DB , WB 67°F (19°C) DB , 57°F (14°C) WB
Operation Conditions - Indoor Intake Air Temperature Heating - Maximum - DB , WB 80°F (27°C) DB, 67°F (19°C) WB
Operation Conditions - Indoor Intake Air Temperature Heating - Minimum - DB , WB 70°F (21°C) DB, 60°F (16°C) WB
Operation Conditions - Indoor Intake Air Temperature Cooling - Maximum - DB 90°F (32°C) DB
Operation Conditions - Indoor Intake Air Temperature Cooling - Maximum -WB 73°F (23°C) WB
Operation Conditions - Indoor Intake Air Temperature Cooling - Minimum - DB 67°F (19°C) DB
Operation Conditions - Indoor Intake Air Temperature Cooling - Minimum - WB 57°F (14°C) WB
Operation Conditions - Indoor Intake Air Temperature Heating - Maximum - DB 80°F (27°C) DB
Operation Conditions - Indoor Intake Air Temperature Heating - Maximum - WB 67°F (19°C) WB
Operation Conditions - Indoor Intake Air Temperature Heating - Minimum - DB 70°F (21°C) DB
Operation Conditions - Indoor Intake Air Temperature Heating - Minimum - WB 60°F (16°C) WB
Operation Conditions - Outdoor Intake Air Temperature Cooling - Maximum - DB , WB 115°F (46°C) DB
Operation Conditions - Outdoor Intake Air Temperature Heating - Maximum - DB , WB 75°F (24°C) DB, 65°F (18°C) WB
Operation Conditions - Outdoor Intake Air Temperature Heating - Minimum - DB , WB -13°F (-25°C) DB, -15°F (-26°C) WB
Operation Conditions - Outdoor Intake Air Temperature Cooling - Maximum - DB 115°F (46°C) DB
Operation Conditions - Outdoor Intake Air Temperature Cooling- Minimum - DB 14°F (-10°C) DB
Operation Conditions - Outdoor Intake Air Temperature Heating - Maximum - DB 75°F (24°C) DB
Operation Conditions - Outdoor Intake Air Temperature Heating - Maximum - WB 65°F (18°C) WB
Operation Conditions - Outdoor Intake Air Temperature Heating - Minimum - DB -13°F (-25°C) DB
Operation Conditions - Outdoor Intake Air Temperature Heating - Minimum - WB -15°F (-26°C) WB
External Finish Munsell 3Y 7.8/1.1
Voltage Indoor - Outdoor S1-S2 AC 208 / 230V
Voltage Indoor - Outdoor S2-S3 DC 12-24V

Energy Star System X
Power Supply Phase, Cycle, Voltage 1 Phase, 60Hz, 208/230V *4
Cooling Rated Capacity 12000 Btu/h (3.52 kW) *1
Cooling Capacity Range 2800 - 12000 Btu/h (0.8 - 3.5 kW)
Cooling Total Input 930 W (0.9 kW)
Cooling Energy Efficiency SEER 23
Cooling Sensible Heat Factor 0.73
Cooling EER 12.9
Cooling Moisture Removal Pints/H 2.9
Heating at 47° F Rated Capacity 13600 Btu/h (4 kW) *2
Heating at 47° F Capacity Range 3000 - 21000 Btu/h (0.9 - 6.2 kW)
Heating at 47° F Total Input 950 (150 - 2250) W
Heating at 47° F HSPF (Region IV) 8.2
Heating at 47° F COP 4.2
Heating at 17° F Maximum Capacity 13600 Btu/h (4 kW)
Heating at 17° F COP 3.04 Btu/Btu
Heating at 17° F Rated Capacity 7900 Btu/h (2.3 kW) *3
Heating at 17° F Total Input 750 W
Heating at 5° F Maximum Capacity 13600 Btu/h (4 kW)
Minimum Circuit Ampacity MCA 12 Ampere
Maximum fuse size (time delay) MOCP 12 Ampere
Recommended Fuse/Breaker Size 15 Ampere
Refrigerant Type R410A
Refrigerant Oil Type NEO22 (15.2)
Refrigerant Charge 2, 9
Refrigerant Control Linear Expansion Valve
Compressor Type DC INVERTER-driven Twin Rotary
Compressor Model SNB130FQBHT
Compressor R.L.A. 8.6
Compressor L.R.A. 10.8
Fan Fan Motor - F.L.A. 0.56 F.L.A
Airflow Cooling 1102 CFM (31 m³/min)
Airflow Heating 1187 CFM (34 m³/min)
Sound Pressure Level Cooling 48 dB(A)
Sound Pressure Level Heating 49 dB(A)
Dimensions H x W x D Height 21-5/8 Inches (549 mm)
Dimensions H x W x D Width 31-1/2 Inches (800 mm)
Dimensions H x W x D Depth 11-1/4 Inches (286 mm)
Refrigerant Pipe Size O.D. Gas (Low Pressure) 3/8 Inch (9.52 mm)
Refrigerant Pipe Size O.D. Liquid (High Pressure) 3/8 Inch (9.52 mm)
Maximum Refrigerant Pipe Height Difference 40 ft. (12 m)
Maximum Refrigerant Pipe Length 65 ft. (20 m)
Refrigerant Piping Connection Method Indoor / Outdoor Flared / Flared
Operation Conditions - Indoor Intake Air Temperature Cooling - Maximum - DB , WB 90°F (32°C) DB , 73°F (23°C) WB
Operation Conditions - Indoor Intake Air Temperature Cooling - Minimum - DB , WB 67°F (19°C) DB , 57°F (14°C) WB
Operation Conditions - Indoor Intake Air Temperature Heating - Maximum - DB , WB 80°F (27°C) DB, 67°F (19°C) WB
Operation Conditions - Indoor Intake Air Temperature Heating - Minimum - DB , WB 70°F (21°C) DB, 60°F (16°C) WB
Operation Conditions - Indoor Intake Air Temperature Cooling - Maximum - DB 90°F (32°C) DB
Operation Conditions - Indoor Intake Air Temperature Cooling - Maximum -WB 73°F (23°C) WB
Operation Conditions - Indoor Intake Air Temperature Cooling - Minimum - DB 67°F (19°C) DB
Operation Conditions - Indoor Intake Air Temperature Cooling - Minimum - WB 57°F (14°C) WB
Operation Conditions - Indoor Intake Air Temperature Heating - Maximum - DB 80°F (27°C) DB
Operation Conditions - Indoor Intake Air Temperature Heating - Maximum - WB 67°F (19°C) WB
Operation Conditions - Indoor Intake Air Temperature Heating - Minimum - DB 70°F (21°C) DB
Operation Conditions - Indoor Intake Air Temperature Heating - Minimum - WB 60°F (16°C) WB
Operation Conditions - Outdoor Intake Air Temperature Cooling - Maximum - DB , WB 115°F (46°C) DB
Operation Conditions - Outdoor Intake Air Temperature Heating - Maximum - DB , WB 75°F (24°C) DB, 65°F (18°C) WB
Operation Conditions - Outdoor Intake Air Temperature Heating - Minimum - DB , WB -13°F (-25°C) DB, -15°F (-26°C) WB
Operation Conditions - Outdoor Intake Air Temperature Cooling - Maximum - DB 115°F (46°C) DB
Operation Conditions - Outdoor Intake Air Temperature Cooling- Minimum - DB 14°F (-10°C) DB
Operation Conditions - Outdoor Intake Air Temperature Heating - Maximum - DB 75°F (24°C) DB
Operation Conditions - Outdoor Intake Air Temperature Heating - Maximum - WB 65°F (18°C) WB
Operation Conditions - Outdoor Intake Air Temperature Heating - Minimum - DB -13°F (-25°C) DB
Operation Conditions - Outdoor Intake Air Temperature Heating - Minimum - WB -15°F (-26°C) WB
External Finish Munsell 3Y 7.8/1.1
Voltage Indoor - Outdoor S1-S2 AC 208 / 230V
Voltage Indoor - Outdoor S2-S3 DC 12-24V

Energy Star System X
Power Supply Phase, Cycle, Voltage 1 Phase, 60Hz, 208/230V *4
Cooling Rated Capacity 18000 Btu/h (5.28 kW) *1
Cooling Capacity Range 8200 - 25200 Btu/h (2.4 - 7.4 kW)
Cooling Total Input 1270 W (1.3 kW)
Cooling Energy Efficiency SEER 20.2
Cooling Sensible Heat Factor 0.84
Cooling Moisture Removal Pints/H 2.7
Cooling EER 14.2
Heating at 47° F Rated Capacity 21600 Btu/h (6.3 kW) *2
Heating at 47° F Capacity Range 7500 - 29700 Btu/h (2.2 - 8.7 kW)
Heating at 47° F Total Input 1540 (520 - 2240) W
Heating at 47° F HSPF (Region IV) 10.5
Heating at 47° F COP 4.11
Heating at 17° F Maximum Capacity 21600 Btu/h (6.3 kW)
Heating at 17° F COP 2.76 Btu/Btu
Heating at 17° F Rated Capacity 11700 Btu/h (3.4 kW) *3
Heating at 17° F Total Input 1240 W
Heating at 5° F Maximum Capacity 21600 Btu/h (4.8 kW)
Minimum Circuit Ampacity MCA 17.1 Ampere
Maximum fuse size (time delay) MOCP 20 Ampere
Recommended Fuse/Breaker Size 20 Ampere
Refrigerant Type R410A
Refrigerant Oil Type FV50S (13.52)
Refrigerant Charge 4, 3
Refrigerant Control Linear Expansion Valve
Compressor Type DC INVERTER-driven Twin Rotary
Compressor Model SNB172FQKMT
Compressor R.L.A. 12.9
Compressor L.R.A. 16.1
Fan Fan Motor - F.L.A. 0.93 F.L.A
Airflow Cooling 1769 CFM (50 m³/min)
Airflow Heating 1701 CFM (48 m³/min)
Sound Pressure Level Heating 55 dB(A)
Sound Pressure Level Cooling 55 dB(A)
Dimensions H x W x D Height 34-5/8 Inches (880 mm)
Dimensions H x W x D Width 33-1/16 Inches (840 mm)
Dimensions H x W x D Depth 13 Inches (330 mm)
Refrigerant Pipe Size O.D. Gas (Low Pressure) 5/8 Inch (16 mm)
Refrigerant Pipe Size O.D. Liquid (High Pressure) 3/8 Inch (9.52 mm)
Maximum Refrigerant Pipe Height Difference 50 ft. (15 m)
Maximum Refrigerant Pipe Length 100 ft. (30 m)
Refrigerant Piping Connection Method Indoor / Outdoor Flared / Flared
Operation Conditions - Indoor Intake Air Temperature Cooling - Maximum - DB , WB 90°F (32°C) DB , 73°F (23°C) WB
Operation Conditions - Indoor Intake Air Temperature Cooling - Minimum - DB , WB 67°F (19°C) DB , 57°F (14°C) WB
Operation Conditions - Indoor Intake Air Temperature Heating - Maximum - DB , WB 80°F (27°C) DB, 67°F (19°C) WB
Operation Conditions - Indoor Intake Air Temperature Heating - Minimum - DB , WB 70°F (21°C) DB, 60°F (16°C) WB
Operation Conditions - Indoor Intake Air Temperature Cooling - Maximum - DB 90°F (32°C) DB
Operation Conditions - Indoor Intake Air Temperature Cooling - Maximum -WB 73°F (23°C) WB
Operation Conditions - Indoor Intake Air Temperature Cooling - Minimum - WB 57°F (14°C) WB
Operation Conditions - Indoor Intake Air Temperature Heating - Maximum - WB 67°F (19°C) WB
Operation Conditions - Indoor Intake Air Temperature Cooling - Minimum - DB 67°F (19°C) DB
Operation Conditions - Indoor Intake Air Temperature Heating - Minimum - DB 70°F (21°C) DB
Operation Conditions - Indoor Intake Air Temperature Heating - Minimum - WB 60°F (16°C) WB
Operation Conditions - Indoor Intake Air Temperature Heating - Maximum - DB 80°F (27°C) DB, 67°F (19°C) WB
Operation Conditions - Outdoor Intake Air Temperature Cooling - Maximum - DB , WB 115°F (46°C) DB
Operation Conditions - Outdoor Intake Air Temperature Heating - Maximum - DB , WB 75°F (24°C) DB, 65°F (18°C) WB
Operation Conditions - Outdoor Intake Air Temperature Heating - Minimum - DB , WB -13°F (-25°C) DB, -15°F (-26°C) WB
Operation Conditions - Outdoor Intake Air Temperature Cooling- Minimum - DB 14°F (-10°C) DB
Operation Conditions - Outdoor Intake Air Temperature Heating - Maximum - DB 75°F (24°C) DB
Operation Conditions - Outdoor Intake Air Temperature Cooling - Maximum - WB 115°F (46°C) DB
Operation Conditions - Outdoor Intake Air Temperature Cooling - Maximum - DB 115°F (46°C) DB
Operation Conditions - Outdoor Intake Air Temperature Heating - Maximum - WB 65°F (18°C) WB
Operation Conditions - Outdoor Intake Air Temperature Heating - Minimum - DB -13°F (-25°C) DB
Operation Conditions - Outdoor Intake Air Temperature Heating - Minimum - WB -15°F (-26°C) WB
Voltage Indoor - Outdoor S1-S2 AC 208 / 230V
Voltage Indoor - Outdoor S2-S3 DC 12-24V
Defrost Method Reverse Cycle
External Finish Munsell 3Y 7.8/1.1