Mitsubishi Electric HVAC-Proposed - L-Generation R2-Series - CITY MULTI VRF - Air Source-0_PURY-P216TSLMU-A (-BS)

L-Generation R2-Series - CITY MULTI VRF - Air Source-0_PURY-P216TSLMU-A (-BS)


Category: air source energy recovery | air source energy recovery equipment | air-source energy recovery...

MasterFormat: Decentralized Unitary HVAC Equipment | Room Air-Conditioners | Air-Source Unitary Heat Pumps...



Mitsubishi Electric HVAC-Proposed
3400 Lawrenceville Suwanee Rd.
Suwanee, GA 30024
Tel: (800) 687-1966
Fax: (800) 658-1458

http://www.mehvac.com

Request More Info

DOWNLOADS

Related Products

Overview



L-Generation R2-Series - CITY MULTI VRF - Air Source - 0_PURY-P216TSLMU-A (-BS)

L-Generation R2-Series - CITY MULTI VRF - Air Source


Model Number: 0_PURY-P216TSLMU-A (-BS)

The L-Generation Air Source VRF Outdoor Units represent the latest in a long line of innovations from Mitsubishi Electric Cooling & Heating. Featuring HexiCoil™ aluminum flat tube heat exchanger technology, the L-Generation offers best-in-class efficiency ratings across all categories improving on the already highly efficient variable refrigerant flow technology. With single modules up to 14 tons and an optimized footprint, the L-Generation Air Source Outdoor Unit is the perfect fit for any commercial application.


Best-in-class efficiency ratings.
Single modules up to 14 tons with the ability to combine modules for systems up to 28 tons.
HexiCoil™ aluminum flat tube, zinc-coated heat exchanger technology eliminates copper tubing from the condenser coil. Featuring turbulated tube walls and a unique fin shape for water shedding capability, the HexiCoil™ condenser coil ensures maximum heat transfer through an optimized cross section.
Up to 50% less refrigerant charge required than previous generations.
Floating/adjustable evaporation temperature in swing seasons, saving energy while maintaining exceptional performance.
Automated and dynamic refrigerant temperature control.
Optimized refrigerant circuit and component design for improved flow distribution, allowing maximum energy transfer with minimal power input.
Superior high-ambient cooling performance with guaranteed operation to 126°F.
Extended 10-year parts and compressor warranty available.




Compressor Operating Range 15% to 100%
Compressor Type x Quantity Inverter scroll hermetic compressor x 1
Compressor Lubricant MEL32
Compressor Starting method Inverter
Power Source Voltage, Phase, Cycle 208 / 230V, 3-Phase, 60Hz
Cooling Capacity (Nominal) 120000 Btu/h (35.2 kW) *1
Cooling Power Input (Nominal) 8.08 kW *1
Heating Capacity (Nominal) 135000 Btu/h (39.6 kW) *1
Heating Power Input (Nominal) 10.21 kW *1
Minimum Circuit Ampacity MCA 42-39 Ampere
Maximum Overcurrent Protection MOP 60/60 Ampere
Refrigerant Type R410A x 23 lbs + 2 oz (10.5 kg)
Fan Airflow Rate 11300 cfm (320 m³/min)
Fan Type x Quantity Propeller fan x 2
Fan Control, Driving mechanism Inverter-control, Brushless DC motor
External Static Pressure 0.12 or 0.24"WG external static pressure; factory set to 0"WG
Sound Pressure Level (measured in anechoic room) 60 dB(A)
Dimensions H x W x D Height 64-31/32 Inches (1650 mm)
Dimensions H x W x D Width 68-29/32 Inches (1750 mm)
Dimensions H x W x D Depth 29-5/32 Inches (740 mm)
Indoor unit connectable Total capacity 50~150% of outdoor unit capacity
Indoor unit connectable Model (Quantity) P06~P96/1~30
Piping Diameter Liquid (High Pressure) From Twinning Kit to Indoor Units (Brazed) 3/4 Inch (19.05 mm) Brazed
Piping Diameter Gas (Low Pressure) From Twinning Kit to Indoor Units (Brazed) 1-1/8 Inches (28.58 mm) Brazed
Operating Temperature Range Cooling (Outdoor) 23~126°F(-5~52°C) D.B. **
Operating Temperature Range Heating (Outdoor) W.B. -4~60° F (-20~15.5° C)
External Finish Pre-coated galvanized steel sheet
Max. Total Refrigerant Line Length 1969 Ft. (600 m)
Max. Refrigerant Line Length (Between ODU & IDU) 541 Ft. (165 m)
Max. Control Wiring Length 1650 Ft. (503 m)
Heat Exchanger Salt-resistant cross fin & aluminum tube
Protection Device High Pressure Protection High pressure sensor, High pressure switch at 4.15 MPa (601 psi)
Protection Device Inverter Circuit (Comp. / Fan) Over-current protection
Protection Device Fan Motor Thermal switch
AHRI Ratings EER (Ducted/Non-Ducted) 11.7 / 12.2
AHRI Ratings IEER (Ducted/Non-Ducted) 18.6 / 20.8
AHRI Ratings COP (Ducted/Non-Ducted) 3.45 / 3.61
AHRI Ratings SCHE (Ducted/Non-Ducted) 16.8 / 19.7

Compressor Operating Range 15% to 100%
Compressor Type x Quantity Inverter scroll hermetic compressor x 1
Compressor Lubricant MEL32
Compressor Starting method Inverter
Power Source Voltage, Phase, Cycle 460V, 3-Phase, 60Hz
Cooling Capacity (Nominal) 120000 Btu/h (35.2 kW) *1
Cooling Power Input (Nominal) 8.08 kW *1
Heating Capacity (Nominal) 135000 Btu/h (39.6 kW) *1
Heating Power Input (Nominal) 10.21 kW *1
Minimum Circuit Ampacity MCA 19 Ampere
Maximum Overcurrent Protection MOP 30 Ampere
Refrigerant Type R410A x 23 lbs + 2 oz (10.5 kg)
Fan Airflow Rate 11300 cfm (320 m³/min)
Fan Type x Quantity Propeller fan x 2
Fan Control, Driving mechanism Inverter-control, Brushless DC motor
External Static Pressure 0.12 or 0.24"WG external static pressure; factory set to 0"WG
Sound Pressure Level (measured in anechoic room) 60 dB(A)
Dimensions H x W x D Height 64-31/32 Inches (1650 mm)
Dimensions H x W x D Width 68-29/32 Inches (1750 mm)
Dimensions H x W x D Depth 29-5/32 Inches (740 mm)
Indoor unit connectable Total capacity 50~150% of outdoor unit capacity
Indoor unit connectable Model (Quantity) P06~P96/1~36
Piping Diameter Liquid (High Pressure) From Twinning Kit to Indoor Units (Brazed) 3/4 Inch (19.05 mm) Brazed
Piping Diameter Gas (Low Pressure) From Twinning Kit to Indoor Units (Brazed) 1-1/8 Inches (28.58 mm) Brazed
Operating Temperature Range Cooling (Outdoor) 23~126°F(-5~52°C) D.B. **
Operating Temperature Range Heating (Outdoor) W.B. -4~60° F (-20~15.5° C)
External Finish Pre-coated galvanized steel sheet
Max. Total Refrigerant Line Length 1969 Ft. (600 m)
Max. Refrigerant Line Length (Between ODU & IDU) 541 Ft. (165 m)
Max. Control Wiring Length 1650 Ft. (503 m)
Protection Device High Pressure Protection High pressure sensor, High pressure switch at 4.15 MPa (601 psi)
Protection Device Inverter Circuit (Comp. / Fan) Over-current protection
Protection Device Fan Motor Thermal switch
AHRI Ratings EER (Ducted/Non-Ducted) 11.7 / 12.2
AHRI Ratings IEER (Ducted/Non-Ducted) 18.6 / 20.8
AHRI Ratings COP (Ducted/Non-Ducted) 3.45 / 3.61
AHRI Ratings SCHE (Ducted/Non-Ducted) 16.8 / 19.7
Heat Exchanger Salt-resistant cross fin & aluminum tube

Compressor Operating Range 15% to 100%
Compressor Type x Quantity Inverter scroll hermetic compressor x 1
Compressor Lubricant MEL32
Compressor Starting method Inverter
Power Source Voltage, Phase, Cycle 208 / 230V, 3-Phase, 60Hz
Cooling Capacity (Nominal) 144000 Btu/h (42.2 kW) *1
Cooling Power Input (Nominal) 10.22 kW *1
Heating Capacity (Nominal) 160000 Btu/h (46.9 kW) *1
Heating Power Input (Nominal) 12.73 kW *1
Minimum Circuit Ampacity MCA 52 / 48 Ampere
Maximum Overcurrent Protection MOP 80/70 Ampere
Refrigerant Type R410A x 23 lbs + 2 oz (10.5 kg)
Fan Airflow Rate 11300 cfm (320 m³/min)
Fan Control, Driving mechanism Inverter-control, Brushless DC motor
Fan Type x Quantity Propeller fan x 2
External Static Pressure 0.12 or 0.24"WG external static pressure; factory set to 0"WG
Sound Pressure Level (measured in anechoic room) 61 dB(A)
Dimensions H x W x D Height 64-31/32 Inches (1650 mm)
Dimensions H x W x D Width 68-29/32 Inches (1750 mm)
Dimensions H x W x D Depth 29-5/32 Inches (740 mm)
Indoor unit connectable Total capacity 50~150% of outdoor unit capacity
Indoor unit connectable Model (Quantity) P06~P96/1~36
Piping Diameter Liquid (High Pressure) From Twinning Kit to Indoor Units (Brazed) 7/8 Inch (22.2 mm) Brazed
Piping Diameter Gas (Low Pressure) From Twinning Kit to Indoor Units (Brazed) 1-1/8 Inches (28.58 mm) Brazed
Operating Temperature Range Cooling (Outdoor) 23~126°F(-5~52°C) D.B. **
Operating Temperature Range Heating (Outdoor) W.B. -4~60° F (-20~15.5° C)
Max. Refrigerant Line Length (Between ODU & IDU) 541 Ft. (165 m)
Heat Exchanger Salt-resistant cross fin & aluminum tube
Max. Total Refrigerant Line Length 1969 Ft. (600 m)
Max. Control Wiring Length 1650 Ft. (503 m)
Protection Device High Pressure Protection High pressure sensor, High pressure switch at 4.15 MPa (601 psi)
Protection Device Inverter Circuit (Comp. / Fan) Over-current protection
Protection Device Fan Motor Thermal switch
AHRI Ratings EER (Ducted/Non-Ducted) 11.7 / 12.7
AHRI Ratings IEER (Ducted/Non-Ducted) 18.0 / 20.9
AHRI Ratings COP (Ducted/Non-Ducted) 3.41 / 3.28
AHRI Ratings SCHE (Ducted/Non-Ducted) 18.2 / 20.2
External Finish Pre-coated galvanized steel sheet

Compressor Operating Range 8% to 100%
Compressor Type x Quantity Inverter scroll hermetic compressor x 1
Compressor Lubricant MEL32
Compressor Starting method Inverter
Power Source Voltage, Phase, Cycle 460V, 3-Phase, 60Hz
Cooling Capacity (Nominal) 144000 Btu/h (42.2 kW) *1
Cooling Power Input (Nominal) 10.09 kW *3
Heating Capacity (Nominal) 160000 Btu/h (46.9 kW) *1
Heating Power Input (Nominal) 11.78 kW *3
Piping Diameter Liquid (High Pressure) From Twinning Kit to Indoor Units (Brazed) 7/8 Inch (22.2 mm) Brazed
Piping Diameter Gas (Low Pressure) From Twinning Kit to Indoor Units (Brazed) 1-1/8 Inches (28.58 mm) Brazed
Set Model With Two PURY-P72YLMU-A (-BS)
Minimum Circuit Ampacity MCA 52 / 48 Ampere *3
Maximum Overcurrent Protection MOP 35 / 35 - 35 / 35 Ampere *3
Refrigerant Type R410A x 13 lbs + 3 oz (6.0 kg) / 13 lbs + 3 oz (6.0 kg)
Fan Airflow Rate 6550 cfm (185 m³/min) / 6550 cfm (185 m³/min)
Fan Control, Driving mechanism Inverter-control, Brushless DC motor
Fan Type x Quantity Propeller fan x 2
External Static Pressure 0 in.WG (0 Pa)
Sound Pressure Level (measured in anechoic room) 61 dB(A)
Indoor unit connectable Total capacity 50~150% of outdoor unit capacity
Indoor unit connectable Model (Quantity) P06~P96/1~48
Operating Temperature Range Cooling (Outdoor) 23~126°F(-5~52°C) D.B. **
Operating Temperature Range Heating (Outdoor) -4~60°F(-20~15.5°C) W.B.
External Finish Pre-coated galvanized steel sheet (+powder coating for -BS type)
Protection Device High Pressure Protection High pressure sensor, High pressure switch at 4.15 MPa (601 psi)
Protection Device Inverter Circuit (Comp. / Fan) Over-current protection
Protection Device Fan Motor Thermal switch
AHRI Ratings EER (Ducted/Non-Ducted) 12 / 14.4
AHRI Ratings IEER (Ducted/Non-Ducted) 18.8 / 20.6
AHRI Ratings COP (Ducted/Non-Ducted) 3.54 / 3.65
AHRI Ratings SCHE (Ducted/Non-Ducted) 21.8 / 24.0
Heat Exchanger Salt-resistant cross fin & aluminum tube
Max. Total Refrigerant Line Length 1969 Ft. (600 m)
Max. Refrigerant Line Length (Between ODU & IDU) 541 Ft. (165 m)
Max. Control Wiring Length 1650 Ft. (503 m)

Compressor Operating Range 15% to 100%
Compressor Type x Quantity Inverter scroll hermetic compressor x 1
Compressor Lubricant MEL32
Compressor Starting method Inverter
Power Source Voltage, Phase, Cycle 460V, 3-Phase, 60Hz
Cooling Capacity (Nominal) 144000 Btu/h (42.2 kW) *1
Cooling Power Input (Nominal) 10.22 kW *1
Heating Capacity (Nominal) 160000 Btu/h (46.9 kW) *1
Heating Power Input (Nominal) 12.73 kW *1
Minimum Circuit Ampacity MCA 24 Ampere
Maximum Overcurrent Protection MOP 35 Ampere
Refrigerant Type R410A x 23 lbs + 2 oz (10.5 kg)
Fan Airflow Rate 12000 cfm (340 m³/min)
Fan Control, Driving mechanism Inverter-control, Brushless DC motor
Fan Control, Driving mechanism Inverter-control, Brushless DC motor
Fan Type x Quantity Propeller fan x 2
External Static Pressure 0.12 or 0.24"WG external static pressure; factory set to 0"WG
Sound Pressure Level (measured in anechoic room) 61 dB(A)
Dimensions H x W x D Height 64-31/32 Inches (1650 mm)
Dimensions H x W x D Width 68-29/32 Inches (1750 mm)
Dimensions H x W x D Depth 29-5/32 Inches (740 mm)
Indoor unit connectable Total capacity 50~150% of outdoor unit capacity
Indoor unit connectable Model (Quantity) P06~P96/1~36
Piping Diameter Liquid (High Pressure) From Twinning Kit to Indoor Units (Brazed) 7/8 Inch (22.2 mm) Brazed
Piping Diameter Gas (Low Pressure) From Twinning Kit to Indoor Units (Brazed) 1-1/8 Inches (28.58 mm) Brazed
Operating Temperature Range Cooling (Outdoor) 23~126°F(-5~52°C) D.B. **
Operating Temperature Range Heating (Outdoor) W.B. -4~60° F (-20~15.5° C)
Heat Exchanger Salt-resistant cross fin & aluminum tube
Heat Exchanger Salt-resistant cross fin & aluminum tube
Max. Total Refrigerant Line Length 1969 Ft. (600 m)
Max. Refrigerant Line Length (Between ODU & IDU) 541 Ft. (165 m)
Max. Control Wiring Length 1650 Ft. (503 m)
Protection Device High Pressure Protection High pressure sensor, High pressure switch at 4.15 MPa (601 psi)
Protection Device Inverter Circuit (Comp. / Fan) Over-current protection
Protection Device Fan Motor Thermal switch
AHRI Ratings EER (Ducted/Non-Ducted) 11.7 / 12.7
AHRI Ratings IEER (Ducted/Non-Ducted) 18.0 / 20.9
AHRI Ratings COP (Ducted/Non-Ducted) 3.41 / 3.28
AHRI Ratings SCHE (Ducted/Non-Ducted) 18.2 / 20.2
External Finish Pre-coated galvanized steel sheet

Compressor Operating Range 8% to 100%
Compressor Type x Quantity Inverter scroll hermetic compressor x 1
Compressor Lubricant MEL32
Compressor Starting method Inverter
Power Source Voltage, Phase, Cycle 460V, 3-Phase, 60Hz
Cooling Capacity (Nominal) 144000 Btu/h (42.2 kW) *1
Cooling Power Input (Nominal) 10.09 kW *3
Heating Capacity (Nominal) 160000 Btu/h (46.9 kW) *1
Heating Power Input (Nominal) 11.78 kW *3
Piping Diameter Liquid (High Pressure) From Twinning Kit to Indoor Units (Brazed) 7/8 Inch (22.2 mm) Brazed
Piping Diameter Gas (Low Pressure) From Twinning Kit to Indoor Units (Brazed) 1-1/8 Inches (28.58 mm) Brazed
Set Model With Two PURY-P72YLMU-A (-BS)
Minimum Circuit Ampacity MCA 11 - 11 Ampere *3
Maximum Overcurrent Protection MOP 20 - 20 Ampere *3
Refrigerant Type R410A x 13 lbs + 3 oz (6.0 kg) / 13 lbs + 3 oz (6.0 kg)
Fan Airflow Rate 6550 cfm (185 m³/min) / 6550 cfm (185 m³/min)
Fan Control, Driving mechanism Inverter-control, Brushless DC motor
Fan Type x Quantity Propeller fan x 2
External Static Pressure 0 in.WG (0 Pa)
Sound Pressure Level (measured in anechoic room) 61 dB(A)
Indoor unit connectable Total capacity 50~150% of outdoor unit capacity
Indoor unit connectable Model (Quantity) P06~P96/1~48
Operating Temperature Range Cooling (Outdoor) 23~126°F(-5~52°C) D.B. **
Operating Temperature Range Heating (Outdoor) -4~60°F(-20~15.5°C) W.B.
External Finish Pre-coated galvanized steel sheet (+powder coating for -BS type)
Protection Device High Pressure Protection High pressure sensor, High pressure switch at 4.15 MPa (601 psi)
Protection Device Inverter Circuit (Comp. / Fan) Over-current protection
Protection Device Fan Motor Thermal switch
AHRI Ratings EER (Ducted/Non-Ducted) 12 / 14.4
AHRI Ratings IEER (Ducted/Non-Ducted) 18.8 / 20.6
AHRI Ratings COP (Ducted/Non-Ducted) 3.54 / 3.65
AHRI Ratings SCHE (Ducted/Non-Ducted) 21.8 / 24.0
Heat Exchanger Salt-resistant cross fin & aluminum tube
Max. Total Refrigerant Line Length 1969 Ft. (600 m)
Max. Refrigerant Line Length (Between ODU & IDU) 541 Ft. (165 m)
Max. Control Wiring Length 1650 Ft. (503 m)

Compressor Operating Range 15% to 100%
Compressor Type x Quantity Inverter scroll hermetic compressor x 1
Compressor Lubricant MEL32
Compressor Starting method Inverter
Power Source Voltage, Phase, Cycle 208 / 230V, 3-Phase, 60Hz
Cooling Capacity (Nominal) 168000 Btu/h (49.2 kW) *1
Cooling Power Input (Nominal) 14.74 kW *1
Heating Capacity (Nominal) 188000 Btu/h (55.1 kW) *1
Heating Power Input (Nominal) 15.92 kW *1
Minimum Circuit Ampacity MCA 68-63 Ampere
Maximum Overcurrent Protection MOP 110/100 Ampere
Refrigerant Type R410A x 23 lbs + 2 oz (10.5 kg)
Fan Airflow Rate 11300 cfm (320 m³/min)
Fan Control, Driving mechanism Inverter-control, Brushless DC motor
Fan Type x Quantity Propeller fan x 2
External Static Pressure 0.12 or 0.24"WG external static pressure; factory set to 0"WG
Sound Pressure Level (measured in anechoic room) 61 dB(A)
Dimensions H x W x D Height 64-31/32 Inches (1650 mm)
Dimensions H x W x D Width 68-29/32 Inches (1750 mm)
Dimensions H x W x D Depth 29-5/32 Inches (740 mm)
Indoor unit connectable Total capacity 50~150% of outdoor unit capacity
Indoor unit connectable Model (Quantity) P06~P96/1~36
Piping Diameter Liquid (High Pressure) From Twinning Kit to Indoor Units (Brazed) 7/8 Inch (22.2 mm) Brazed
Piping Diameter Gas (Low Pressure) From Twinning Kit to Indoor Units (Brazed) 1-1/8 Inches (28.58 mm) Brazed
Operating Temperature Range Cooling (Outdoor) 23~126°F(-5~52°C) D.B. **
Operating Temperature Range Heating (Outdoor) W.B. -4~60° F (-20~15.5° C)
Max. Refrigerant Line Length (Between ODU & IDU) 541 Ft. (165 m)
Heat Exchanger Salt-resistant cross fin & aluminum tube
Max. Total Refrigerant Line Length 1969 Ft. (600 m)
Max. Control Wiring Length 1650 Ft. (503 m)
Protection Device High Pressure Protection High pressure sensor, High pressure switch at 4.15 MPa (601 psi)
Protection Device Inverter Circuit (Comp. / Fan) Over-current protection
Protection Device Fan Motor Thermal switch
AHRI Ratings EER (Ducted/Non-Ducted) 11.7 / 12.7
AHRI Ratings IEER (Ducted/Non-Ducted) 18.0 / 20.9
AHRI Ratings COP (Ducted/Non-Ducted) 3.41 / 3.28
AHRI Ratings SCHE (Ducted/Non-Ducted) 18.2 / 20.2
External Finish Pre-coated galvanized steel sheet

Compressor Operating Range 7% to 100%
Compressor Type x Quantity Inverter scroll hermetic compressor x 1
Compressor Lubricant MEL32
Compressor Starting method Inverter
Power Source Voltage, Phase, Cycle 208 / 230V, 3 phase, 60Hz
Cooling Capacity (Nominal) 168000 Btu/h (49.2 kW) *1
Cooling Power Input (Nominal) 13.6 kW *3
Heating Capacity (Nominal) 188000 Btu/h (55.1 kW) *1
Heating Power Input (Nominal) 14.94 kW *3
Piping Diameter Liquid (High Pressure) From Twinning Kit to Indoor Units (Brazed) 7/8 Inch (22.2 mm) Brazed
Piping Diameter Gas (Low Pressure) From Twinning Kit to Indoor Units (Brazed) 1-1/8 Inches (28.58 mm) Brazed
Set Model With One PURY-P96TLMU-A (-BS) and One PURY-P72TLMU-A (-BS)
Minimum Circuit Ampacity MCA 33-30 / 24-22 Ampere *3
Maximum Overcurrent Protection MOP 50 / 50 - 35 / 35 Ampere *3
Refrigerant Type R410A x 17 lbs + 10 oz (11.8 kg) / R410A x 13 lbs + 3 oz (6.0 kg)
Fan Airflow Rate 6550 cfm (185 m³/min) / 6550 cfm (185 m³/min)
Fan Control, Driving mechanism Inverter-control, Brushless DC motor
Fan Type x Quantity Propeller fan x 1 / Propeller fan x 1
External Static Pressure 0.12 or 0.24"WG external static pressure; factory set to 0"WG
Sound Pressure Level (measured in anechoic room) 61 dB(A)
Indoor unit connectable Total capacity 50~150% of outdoor unit capacity
Indoor unit connectable Model (Quantity) P06~P96/1~42
Operating Temperature Range Cooling (Outdoor) 23~126°F(-5~52°C) D.B. **
Operating Temperature Range Heating (Outdoor) W.B. -4~60° F (-20~15.5° C)
External Finish Pre-coated galvanized steel sheet (+powder coating for -BS type)
Max. Total Refrigerant Line Length 1969 Ft. (600 m)
Max. Refrigerant Line Length (Between ODU & IDU) 541 Ft. (165 m)
Max. Control Wiring Length 1650 Ft. (503 m)
Heat Exchanger Salt-resistant cross fin & aluminum tube
Protection Device High Pressure Protection High pressure sensor, High pressure switch at 4.15 MPa (601 psi)
Protection Device Inverter Circuit (Comp. / Fan) Over-current protection
Protection Device Fan Motor Thermal switch
AHRI Ratings EER (Ducted/Non-Ducted) 12.1 / 12.9
AHRI Ratings IEER (Ducted/Non-Ducted) 19.4 / 19.1
AHRI Ratings COP (Ducted/Non-Ducted) 3.63 / 3.52
AHRI Ratings SCHE (Ducted/Non-Ducted) 20.0 / 22.6

Compressor Operating Range 15% to 100%
Compressor Type x Quantity Inverter scroll hermetic compressor x 1
Compressor Lubricant MEL32
Compressor Starting method Inverter
Power Source Voltage, Phase, Cycle 460V, 3-Phase, 60Hz
Cooling Capacity (Nominal) 168000 Btu/h (49.2 kW) *1
Cooling Power Input (Nominal) 14.74 kW *1
Heating Capacity (Nominal) 188000 Btu/h (55.1 kW) *1
Heating Power Input (Nominal) 15.92 kW *1
Minimum Circuit Ampacity MCA 31 Ampere
Maximum Overcurrent Protection MOP 50 Ampere
Refrigerant Type R410A x 23 lbs + 2 oz (10.5 kg)
Fan Airflow Rate 11300 cfm (320 m³/min)
Fan Control, Driving mechanism Inverter-control, Brushless DC motor
Fan Control, Driving mechanism Inverter-control, Brushless DC motor
Fan Type x Quantity Propeller fan x 2
External Static Pressure 0.12 or 0.24"WG external static pressure; factory set to 0"WG
Sound Pressure Level (measured in anechoic room) 61 dB(A)
Dimensions H x W x D Height 64-31/32 Inches (1650 mm)
Dimensions H x W x D Width 68-29/32 Inches (1750 mm)
Dimensions H x W x D Depth 29-5/32 Inches (740 mm)
Indoor unit connectable Total capacity 50~150% of outdoor unit capacity
Indoor unit connectable Model (Quantity) P06~P96/1~36
Piping Diameter Liquid (High Pressure) From Twinning Kit to Indoor Units (Brazed) 7/8 Inch (22.2 mm) Brazed
Piping Diameter Gas (Low Pressure) From Twinning Kit to Indoor Units (Brazed) 1-1/8 Inches (28.58 mm) Brazed
Operating Temperature Range Cooling (Outdoor) 23~126°F(-5~52°C) D.B. **
Operating Temperature Range Heating (Outdoor) W.B. -4~60° F (-20~15.5° C)
Heat Exchanger Salt-resistant cross fin & aluminum tube
Heat Exchanger Salt-resistant cross fin & aluminum tube
Max. Total Refrigerant Line Length 1969 Ft. (600 m)
Max. Refrigerant Line Length (Between ODU & IDU) 541 Ft. (165 m)
Max. Control Wiring Length 1650 Ft. (503 m)
Protection Device High Pressure Protection High pressure sensor, High pressure switch at 4.15 MPa (601 psi)
Protection Device Inverter Circuit (Comp. / Fan) Over-current protection
Protection Device Fan Motor Thermal switch
AHRI Ratings EER (Ducted/Non-Ducted) 11.7 / 12.7
AHRI Ratings IEER (Ducted/Non-Ducted) 18.0 / 20.9
AHRI Ratings COP (Ducted/Non-Ducted) 3.41 / 3.28
AHRI Ratings SCHE (Ducted/Non-Ducted) 18.2 / 20.2
External Finish Pre-coated galvanized steel sheet

Compressor Operating Range 7% to 100%
Compressor Type x Quantity Inverter scroll hermetic compressor x 1
Compressor Lubricant MEL32
Compressor Starting method Inverter
Power Source Voltage, Phase, Cycle 460V, 3-Phase, 60Hz
Cooling Capacity (Nominal) 168000 Btu/h (49.2 kW) *1
Cooling Power Input (Nominal) 13.60 kW *3
Heating Capacity (Nominal) 188000 Btu/h (55.1 kW) *1
Heating Power Input (Nominal) 14.94 kW *3
Piping Diameter Liquid (High Pressure) From Twinning Kit to Indoor Units (Brazed) 7/8 Inch (22.2 mm) Brazed
Piping Diameter Gas (Low Pressure) From Twinning Kit to Indoor Units (Brazed) 1-1/8 Inches (28.58 mm) Brazed
Set Model With One PURY-P96YLMU-A (-BS) and One PURY-P72YLMU-A (-BS)
Minimum Circuit Ampacity MCA 15 - 11 Ampere *3
Maximum Overcurrent Protection MOP 25 - 20 Ampere *3
Refrigerant Type R410A x 17 lbs + 10 oz (8.0 kg) / R410A x 13 lbs + 3 oz (6.0 kg)
Fan Airflow Rate 6550 cfm (175 m³/min) / 6550 cfm (185 m³/min)
Fan Control, Driving mechanism Inverter-control, Brushless DC motor
Fan Type x Quantity Propeller fan x 1 / Propeller fan x 1
External Static Pressure 0.12 or 0.24"WG external static pressure; factory set to 0"WG
Sound Pressure Level (measured in anechoic room) 61 dB(A)
Indoor unit connectable Total capacity 50~150% of outdoor unit capacity
Indoor unit connectable Model (Quantity) P06~P96/1~42
Operating Temperature Range Cooling (Outdoor) 23~126°F(-5~52°C) D.B. **
Operating Temperature Range Heating (Outdoor) W.B. -4~60° F (-20~15.5° C)
External Finish Pre-coated galvanized steel sheet (+powder coating for -BS type)
Max. Total Refrigerant Line Length 1969 Ft. (600 m)
Max. Refrigerant Line Length (Between ODU & IDU) 541 Ft. (165 m)
Max. Control Wiring Length 1650 Ft. (503 m)
Heat Exchanger Salt-resistant cross fin & aluminum tube
Protection Device High Pressure Protection High pressure sensor, High pressure switch at 4.15 MPa (601 psi)
Protection Device Inverter Circuit (Comp. / Fan) Over-current protection
Protection Device Fan Motor Thermal switch
AHRI Ratings EER (Ducted/Non-Ducted) 12.1 / 12.9
AHRI Ratings IEER (Ducted/Non-Ducted) 19.4 / 19.1
AHRI Ratings COP (Ducted/Non-Ducted) 3.63 / 3.52
AHRI Ratings SCHE (Ducted/Non-Ducted) 20.0 / 22.6

Compressor Operating Range 8% to 100%
Compressor Type x Quantity Inverter scroll hermetic compressor x 1 / Inverter scroll hermetic compressor x 1
Compressor Lubricant MEL32
Compressor Starting method Inverter
Power Source Voltage, Phase, Cycle 208 / 230V, 3 phase, 60Hz
Cooling Capacity (Nominal) 192000 Btu/h (56.3 kW) *1
Cooling Power Input (Nominal) 15.56 kW *3
Heating Capacity (Nominal) 215000 Btu/h (63 kW) *1
Heating Power Input (Nominal) 17.18 kW *3
Piping Diameter Liquid (High Pressure) From Twinning Kit to Indoor Units (Brazed) 7/8 Inch (22.2 mm) Brazed
Piping Diameter Gas (Low Pressure) From Twinning Kit to Indoor Units (Brazed) 1-1/8 Inches (28.58 mm) Brazed
Set Model With One PURY-P96TLMU-A (-BS) and One PURY-P72TLMU-A (-BS)
Minimum Circuit Ampacity MCA 33-30 / 33-30 Ampere *3
Maximum Overcurrent Protection MOP 50 / 50 - 50 / 50 Ampere *3
Refrigerant Type R410A x 17 lbs + 10 oz (8.0 kg) / R410A x 17 lbs + 10 oz (8.0 kg)
Fan Airflow Rate 6550 cfm (185 m³/min) / 6550 cfm (185 m³/min)
Fan Control, Driving mechanism Inverter-control, Brushless DC motor
Fan Type x Quantity Propeller fan x 1 / Propeller fan x 1
External Static Pressure 0.12 or 0.24"WG external static pressure; factory set to 0"WG
Sound Pressure Level (measured in anechoic room) 61 dB(A)
Indoor unit connectable Total capacity 50~150% of outdoor unit capacity
Indoor unit connectable Model (Quantity) P06~P96/1~48
Operating Temperature Range Cooling (Outdoor) 23~126°F(-5~52°C) D.B. **
Operating Temperature Range Heating (Outdoor) -4~60°F(-20~15.5°C) W.B.
External Finish Pre-coated galvanized steel sheet (+powder coating for -BS type)
Max. Total Refrigerant Line Length 2461 Ft. (750 m)
Max. Refrigerant Line Length (Between ODU & IDU) 541 Ft. (165 m)
Max. Control Wiring Length 1650 Ft. (503 m)
Heat Exchanger Salt-resistant cross fin & aluminum tube
Protection Device High Pressure Protection High pressure sensor, High pressure switch at 4.15 MPa (601 psi)
Protection Device Inverter Circuit (Comp. / Fan) Over-current protection
Protection Device Fan Motor Thermal switch
AHRI Ratings EER (Ducted/Non-Ducted) 11.6 / 11.9
AHRI Ratings IEER (Ducted/Non-Ducted) 19.3 / 18.2
AHRI Ratings COP (Ducted/Non-Ducted) 3.64 / 3.47
AHRI Ratings SCHE (Ducted/Non-Ducted) 17.4 / 21.8

Compressor Operating Range 8% to 100%
Compressor Type x Quantity Inverter scroll hermetic compressor x 1 / Inverter scroll hermetic compressor x 1
Compressor Lubricant MEL32
Compressor Starting method Inverter
Power Source Voltage, Phase, Cycle 460V, 3-Phase, 60Hz
Cooling Capacity (Nominal) 192000 Btu/h (56.3 kW) *1
Cooling Power Input (Nominal) 15.56 kW *3
Heating Capacity (Nominal) 215000 Btu/h (63 kW) *1
Heating Power Input (Nominal) 17.18 kW *3
Piping Diameter Liquid (High Pressure) From Twinning Kit to Indoor Units (Brazed) 7/8 Inch (22.2 mm) Brazed
Piping Diameter Gas (Low Pressure) From Twinning Kit to Indoor Units (Brazed) 1-1/8 Inches (28.58 mm) Brazed
Set Model With One PURY-P96YLMU-A (-BS) and One PURY-P96YLMU-A (-BS)
Minimum Circuit Ampacity MCA 15 - 15 Ampere *3
Maximum Overcurrent Protection MOP 25 - 25 Ampere *3
Refrigerant Type R410A x 17 lbs + 10 oz (8.0 kg) / R410A x 17 lbs + 10 oz (8.0 kg)
Fan Airflow Rate 6550 cfm (185 m³/min) / 6550 cfm (185 m³/min)
Fan Control, Driving mechanism Inverter-control, Brushless DC motor
Fan Type x Quantity Propeller fan x 1 / Propeller fan x 1
External Static Pressure 0.12 or 0.24"WG external static pressure; factory set to 0"WG
Sound Pressure Level (measured in anechoic room) 61 dB(A)
Indoor unit connectable Total capacity 50~150% of outdoor unit capacity
Indoor unit connectable Model (Quantity) P06~P96/1~48
Operating Temperature Range Cooling (Outdoor) 23~126°F(-5~52°C) D.B. **
Operating Temperature Range Heating (Outdoor) -4~60°F(-20~15.5°C) W.B.
External Finish Pre-coated galvanized steel sheet (+powder coating for -BS type)
Max. Total Refrigerant Line Length 2461 Ft. (750 m)
Max. Refrigerant Line Length (Between ODU & IDU) 541 Ft. (165 m)
Max. Control Wiring Length 1650 Ft. (503 m)
Heat Exchanger Salt-resistant cross fin & aluminum tube
Protection Device High Pressure Protection High pressure sensor, High pressure switch at 4.15 MPa (601 psi)
Protection Device Inverter Circuit (Comp. / Fan) Over-current protection
Protection Device Fan Motor Thermal switch
AHRI Ratings EER (Ducted/Non-Ducted) 11.6 / 11.9
AHRI Ratings IEER (Ducted/Non-Ducted) 19.3 / 18.2
AHRI Ratings COP (Ducted/Non-Ducted) 3.64 / 3.47
AHRI Ratings SCHE (Ducted/Non-Ducted) 17.4 / 21.8

Compressor Operating Range 8% to 100%
Compressor Type x Quantity Inverter scroll hermetic compressor x 1 / Inverter scroll hermetic compressor x 1
Compressor Lubricant MEL32
Compressor Starting method Inverter
Power Source Voltage, Phase, Cycle 208 / 230V, 3 phase, 60Hz
Cooling Capacity (Nominal) 216000 Btu/h (63.3 kW) *1
Cooling Power Input (Nominal) 17.03 kW *3
Heating Capacity (Nominal) 243000 Btu/h (71.2 kW) *1
Heating Power Input (Nominal) 19.47 kW *3
Piping Diameter Liquid (High Pressure) From Twinning Kit to Indoor Units (Brazed) 1-1/8 Inches (28.58 mm) Brazed
Piping Diameter Gas (Low Pressure) From Twinning Kit to Indoor Units (Brazed) 1-1/8 Inches (28.58 mm) Brazed
Set Model With One PURY-P120TLMU-A (-BS) and One PURY-P96TLMU-A (-BS)
Minimum Circuit Ampacity MCA 42-39 / 33-30 Ampere *3
Maximum Overcurrent Protection MOP 60 / 60 - 50 / 50 Ampere *3
Refrigerant Type R410A x 23 lbs + 2 oz (10.5 kg) / R410A x 17 lbs + 10 oz (8.0 kg)
Fan Airflow Rate 11300 cfm (320 m³/min) / 6550 cfm (185 m³/min)
Fan Control, Driving mechanism Inverter-control, Brushless DC motor
Fan Type x Quantity Propeller fan x 2 / Propeller fan x 1
External Static Pressure 0.12 or 0.24"WG external static pressure ; factory set to 0"WG
Sound Pressure Level (measured in anechoic room) 62.5 dB(A)
Indoor unit connectable Total capacity 50~150% of outdoor unit capacity
Indoor unit connectable Model (Quantity) P06~P96/2~50 (Connectable branch pipe number is max. 48.)
Operating Temperature Range Cooling (Outdoor) 23~126°F(-5~52°C) D.B. **
Operating Temperature Range Heating (Outdoor) -4~60°F(-20~15.5°C) W.B.
External Finish Pre-coated galvanized steel sheet (+powder coating for -BS type)
Max. Total Refrigerant Line Length 1804 Ft. (550 m)
Max. Refrigerant Line Length (Between ODU & IDU) 541 Ft. (165 m)
Max. Control Wiring Length 1650 Ft. (503 m)
Heat Exchanger Salt-resistant cross fin & aluminum tube
Protection Device High Pressure Protection High pressure sensor, High pressure switch at 4.15 MPa (601 psi)
Protection Device Inverter Circuit (Comp. / Fan) Over-current protection
Protection Device Fan Motor Thermal switch
AHRI Ratings EER (Ducted/Non-Ducted) 11.4 / 11.3
AHRI Ratings IEER (Ducted/Non-Ducted) 18.7 / 18.3
AHRI Ratings COP (Ducted/Non-Ducted) 3.54 / 3.43
AHRI Ratings SCHE (Ducted/Non-Ducted) 17.1 / 20.1

Compressor Operating Range 8% to 100%
Compressor Type x Quantity Inverter scroll hermetic compressor x 1 / Inverter scroll hermetic compressor x 1
Compressor Lubricant MEL32
Compressor Starting method Inverter
Power Source Voltage, Phase, Cycle 460V, 3-Phase, 60Hz
Cooling Capacity (Nominal) 216000 Btu/h (63.3 kW) *1
Cooling Power Input (Nominal) 17.03 kW *3
Heating Capacity (Nominal) 243000 Btu/h (71.2 kW) *1
Heating Power Input (Nominal) 19.47 kW *3
Piping Diameter Liquid (High Pressure) From Twinning Kit to Indoor Units (Brazed) 1-1/8 Inches (28.58 mm) Brazed
Piping Diameter Gas (Low Pressure) From Twinning Kit to Indoor Units (Brazed) 1-1/8 Inches (28.58 mm) Brazed
Set Model With One PURY-P120YLMU-A (-BS) and One PURY-P96YLMU-A (-BS)
Minimum Circuit Ampacity MCA 19 / 15 Ampere *3
Maximum Overcurrent Protection MOP 30 - 25 Ampere *3
Refrigerant Type R410A x 23 lbs + 2 oz (10.5 kg) / R410A x 17 lbs + 10 oz (8.0 kg)
Fan Airflow Rate 11300 cfm (320 m³/min) / 6550 cfm (185 m³/min)
Fan Control, Driving mechanism Inverter-control, Brushless DC motor
Fan Type x Quantity Propeller fan x 2 / Propeller fan x 1
External Static Pressure 0.12 or 0.24"WG external static pressure ; factory set to 0"WG
Sound Pressure Level (measured in anechoic room) 62.5 dB(A)
Indoor unit connectable Total capacity 50~150% of outdoor unit capacity
Indoor unit connectable Model (Quantity) P06~P96/2~50 (Connectable branch pipe number is max. 48.)
Operating Temperature Range Cooling (Outdoor) 23~126°F(-5~52°C) D.B. **
Operating Temperature Range Heating (Outdoor) -4~60°F(-20~15.5°C) W.B.
External Finish Pre-coated galvanized steel sheet (+powder coating for -BS type)
Heat Exchanger Salt-resistant cross fin & aluminum tube
Max. Total Refrigerant Line Length 2625 Ft. (550 m)
Max. Refrigerant Line Length (Between ODU & IDU) 541 Ft. (165 m)
Max. Control Wiring Length 1650 Ft. (503 m)
Protection Device High Pressure Protection High pressure sensor, High pressure switch at 4.15 MPa (601 psi)
Protection Device Inverter Circuit (Comp. / Fan) Over-current protection
Protection Device Fan Motor Thermal switch
AHRI Ratings EER (Ducted/Non-Ducted) 11.4 / 11.3
AHRI Ratings IEER (Ducted/Non-Ducted) 18.7 / 18.3
AHRI Ratings COP (Ducted/Non-Ducted) 3.54 / 3.43
AHRI Ratings SCHE (Ducted/Non-Ducted) 17.1 / 20.1

Compressor Operating Range 7% to 100%
Compressor Type x Quantity Inverter scroll hermetic compressor x 1 / Inverter scroll hermetic compressor x 1
Compressor Lubricant MEL32
Compressor Starting method Inverter
Power Source Voltage, Phase, Cycle 208 / 230V, 3 phase, 60Hz
Cooling Capacity (Nominal) 240000 Btu/h (70.3 kW) *1
Cooling Power Input (Nominal) 18.44 kW *3
Heating Capacity (Nominal) 270000 Btu/h (79.1 kW) *1
Heating Power Input (Nominal) 21.76 kW *3
Piping Diameter Liquid (High Pressure) From Twinning Kit to Indoor Units (Brazed) 1-1/8 Inches (28.58 mm) Brazed
Piping Diameter Gas (Low Pressure) From Twinning Kit to Indoor Units (Brazed) 1-3/8 Inches (34.93 mm) Brazed
Set Model With Two PURY-P120TLMU-A (-BS)
Minimum Circuit Ampacity MCA 42-39 / 42-39 Ampere *3
Maximum Overcurrent Protection MOP 60 / 60 - 60 / 60 Ampere *3
Refrigerant Type R410A x 23 lbs + 2 oz (10.5 kg) / R410A x 23 lbs + 2 oz (10.5 kg)
Fan Airflow Rate 11300 cfm (320 m³/min) / 11300 cfm (320 m³/min)
Fan Control, Driving mechanism Inverter-control, Brushless DC motor
Fan Type x Quantity Propeller fan x 2 / Propeller fan x 2
External Static Pressure 0.12 or 0.24"WG external static pressure;factory set to 0"WG
Sound Pressure Level (measured in anechoic room) 63 dB(A)
Indoor unit connectable Total capacity 50~150% of outdoor unit capacity
Indoor unit connectable Model (Quantity) P06~P96/2~50 (Connectable branch pipe number is max. 48.)
Operating Temperature Range Cooling (Outdoor) 23~126°F(-5~52°C) D.B. **
Operating Temperature Range Heating (Outdoor) -4~60°F(-20~15.5°C) W.B.
External Finish Pre-coated galvanized steel sheet (+powder coating for -BS type)
Protection Device High Pressure Protection High pressure sensor, High pressure switch at 4.15 MPa (601 psi)
Protection Device Inverter Circuit (Comp. / Fan) Over-current protection
Protection Device Fan Motor Thermal switch
Max. Total Refrigerant Line Length 2625 Ft. (800 m)
Max. Refrigerant Line Length (Between ODU & IDU) 541 Ft. (165 m)
Max. Control Wiring Length 1650 Ft. (503 m)
Heat Exchanger Salt-resistant cross fin & aluminum tube
AHRI Ratings EER (Ducted/Non-Ducted) 10.9 / 10.9
AHRI Ratings IEER (Ducted/Non-Ducted) 17.8 / 18.5
AHRI Ratings COP (Ducted/Non-Ducted) 3.38 / 3.42
AHRI Ratings SCHE (Ducted/Non-Ducted) 16.5 / 18.6

Compressor Operating Range 7% to 100%
Compressor Type x Quantity Inverter scroll hermetic compressor x 1 / Inverter scroll hermetic compressor x 1
Compressor Lubricant MEL32
Compressor Starting method Inverter
Power Source Voltage, Phase, Cycle 460V, 3-Phase, 60Hz
Cooling Capacity (Nominal) 240000 Btu/h (70.3 kW) *1
Cooling Power Input (Nominal) 18.44 kW *3
Heating Capacity (Nominal) 270000 Btu/h (79.1 kW) *1
Heating Power Input (Nominal) 21.76 kW *3
Piping Diameter Liquid (High Pressure) From Twinning Kit to Indoor Units (Brazed) 1-1/8 Inches (28.58 mm) Brazed
Piping Diameter Gas (Low Pressure) From Twinning Kit to Indoor Units (Brazed) 1-3/8 Inches (34.93 mm) Brazed
Set Model With Two PURY-P120YLMU-A (-BS)
Minimum Circuit Ampacity MCA 19 / 19 Ampere *3
Maximum Overcurrent Protection MOP 30 - 30 Ampere *3
Refrigerant Type R410A x 23 lbs + 2 oz (10.5 kg) / R410A x 23 lbs + 2 oz (10.5 kg)
Fan Airflow Rate 11300 cfm (320 m³/min) / 11300 cfm (320 m³/min)
Fan Control, Driving mechanism Inverter-control, Brushless DC motor
Fan Type x Quantity Propeller fan x 2 / Propeller fan x 2
External Static Pressure 0.12 or 0.24"WG external static pressure;factory set to 0"WG
Sound Pressure Level (measured in anechoic room) 63 dB(A)
Indoor unit connectable Total capacity 50~150% of outdoor unit capacity
Indoor unit connectable Model (Quantity) P06~P96/2~50 (Connectable branch pipe number is max. 48.)
Operating Temperature Range Cooling (Outdoor) 23~126°F(-5~52°C) D.B. **
Operating Temperature Range Heating (Outdoor) -4~60°F(-20~15.5°C) W.B.
External Finish Pre-coated galvanized steel sheet (+powder coating for -BS type)
Max. Total Refrigerant Line Length 2625 Ft. (800 m)
Max. Refrigerant Line Length (Between ODU & IDU) 541 Ft. (165 m)
Max. Control Wiring Length 1650 Ft. (503 m)
Heat Exchanger Salt-resistant cross fin & aluminum tube
Protection Device High Pressure Protection High pressure sensor, High pressure switch at 4.15 MPa (601 psi)
Protection Device Inverter Circuit (Comp. / Fan) Over-current protection
Protection Device Fan Motor Thermal switch
AHRI Ratings EER (Ducted/Non-Ducted) 10.9 / 10.9
AHRI Ratings IEER (Ducted/Non-Ducted) 17.8 / 18.5
AHRI Ratings COP (Ducted/Non-Ducted) 3.38 / 3.42
AHRI Ratings SCHE (Ducted/Non-Ducted) 16.5 / 18.6

Compressor Operating Range 7% to 100%
Compressor Type x Quantity Inverter scroll hermetic compressor x 1 / Inverter scroll hermetic compressor x 1
Compressor Lubricant MEL32
Compressor Starting method Inverter
Power Source Voltage, Phase, Cycle 208 / 230V, 3 phase, 60Hz
Cooling Capacity (Nominal) 264000 Btu/h (77.4 kW) *1
Cooling Power Input (Nominal) 20.98 kW *3
Heating Capacity (Nominal) 295000 Btu/h (86.5 kW) *1
Heating Power Input (Nominal) 24.54 kW *3
Piping Diameter Liquid (High Pressure) From Twinning Kit to Indoor Units (Brazed) 1-1/8 Inches (28.58 mm) Brazed
Piping Diameter Gas (Low Pressure) From Twinning Kit to Indoor Units (Brazed) 1-3/8 Inches (34.93 mm) Brazed
Set Model With One PURY-P144TLMU-A (-BS) and One PURY-P120TLMU-A (-BS)
Minimum Circuit Ampacity MCA 52-48 / 42-39 Ampere *3
Maximum Overcurrent Protection MOP 80 / 70 - 60 / 60 Ampere *3
Refrigerant Type R410A x 23 lbs + 2 oz (10.5 kg) / R410A x 23 lbs + 2 oz (10.5 kg)
Fan Airflow Rate 11300 cfm (320 m³/min) / 11300 cfm (320 m³/min)
Fan Type x Quantity Propeller fan x 2 / Propeller fan x 2
Fan Control, Driving mechanism Inverter-control, Brushless DC motor
External Static Pressure 0.12 or 0.24""WG external static pressure ; factory set to 0""WG"
Sound Pressure Level (measured in anechoic room) 63.5 dB(A)
Indoor unit connectable Total capacity 50~150% of outdoor unit capacity
Indoor unit connectable Model (Quantity) P06~P96/2~50 (Connectable branch pipe number is max. 48.)
Operating Temperature Range Cooling (Outdoor) 23~126°F(-5~52°C) D.B. **
Operating Temperature Range Heating (Outdoor) -4~60°F(-20~15.5°C) W.B.
External Finish Pre-coated galvanized steel sheet (+powder coating for -BS type)
Heat Exchanger Salt-resistant cross fin & aluminum tube
Max. Total Refrigerant Line Length 3,177 Ft. (968 m)
Max. Refrigerant Line Length (Between ODU & IDU) 541 Ft. (165 m)
Max. Control Wiring Length 1650 Ft. (503 m)
Protection Device High Pressure Protection High pressure sensor, High pressure switch at 4.15 MPa (601 psi)
Protection Device Inverter Circuit (Comp. / Fan) Over-current protection
Protection Device Fan Motor Thermal switch
AHRI Ratings EER (Ducted/Non-Ducted) 11.0 / 11.0
AHRI Ratings IEER (Ducted/Non-Ducted) 17.7 / 18.4
AHRI Ratings COP (Ducted/Non-Ducted) 3.40 / 3.25
AHRI Ratings SCHE (Ducted/Non-Ducted) 17.3 / 18.7

Compressor Operating Range 7% to 100%
Compressor Type x Quantity Inverter scroll hermetic compressor x 1 / Inverter scroll hermetic compressor x 1
Compressor Lubricant MEL32
Compressor Starting method Inverter
Power Source Voltage, Phase, Cycle 208 / 230V, 3 phase, 60Hz
Cooling Capacity (Nominal) 264000 Btu/h (77.4 kW) *1
Cooling Power Input (Nominal) 20.98 kW *3
Heating Capacity (Nominal) 295000 Btu/h (86.5 kW) *1
Heating Power Input (Nominal) 24.54 kW *3
Piping Diameter Liquid (High Pressure) From Twinning Kit to Indoor Units (Brazed) 1-1/8 Inches (28.58 mm) Brazed
Piping Diameter Gas (Low Pressure) From Twinning Kit to Indoor Units (Brazed) 1-3/8 Inches (34.93 mm) Brazed
Set Model With One PURY-P144YLMU-A (-BS) and One PURY-P120YLMU-A (-BS)
Minimum Circuit Ampacity MCA 24 / 19 Ampere *3
Maximum Overcurrent Protection MOP 35 - 30 Ampere *3
Refrigerant Type R410A x 23 lbs + 2 oz (10.5 kg) / R410A x 23 lbs + 2 oz (10.5 kg)
Fan Airflow Rate 11300 cfm (320 m³/min) / 11300 cfm (320 m³/min)
Fan Type x Quantity Propeller fan x 2 / Propeller fan x 2
Fan Control, Driving mechanism Inverter-control, Brushless DC motor
External Static Pressure 0.12 or 0.24""WG external static pressure ; factory set to 0""WG"
Sound Pressure Level (measured in anechoic room) 63.5 dB(A)
Indoor unit connectable Total capacity 50~150% of outdoor unit capacity
Indoor unit connectable Model (Quantity) P06~P96/2~50 (Connectable branch pipe number is max. 48.)
Operating Temperature Range Cooling (Outdoor) 23~126°F(-5~52°C) D.B. **
Operating Temperature Range Heating (Outdoor) -4~60°F(-20~15.5°C) W.B.
External Finish Pre-coated galvanized steel sheet (+powder coating for -BS type)
Heat Exchanger Salt-resistant cross fin & aluminum tube
Protection Device High Pressure Protection High pressure sensor, High pressure switch at 4.15 MPa (601 psi)
Protection Device Inverter Circuit (Comp. / Fan) Over-current protection
Protection Device Fan Motor Thermal switch
AHRI Ratings EER (Ducted/Non-Ducted) 11.0 / 11.0
AHRI Ratings IEER (Ducted/Non-Ducted) 17.7 / 18.4
AHRI Ratings COP (Ducted/Non-Ducted) 3.40 / 3.25
AHRI Ratings SCHE (Ducted/Non-Ducted) 17.3 / 18.7
Max. Total Refrigerant Line Length 3280 Ft. (1000 m)
Max. Refrigerant Line Length (Between ODU & IDU) 541 Ft. (165 m)
Max. Control Wiring Length 1650 Ft. (503 m)

Compressor Operating Range 7% to 100%
Compressor Type x Quantity Inverter scroll hermetic compressor x 1 / Inverter scroll hermetic compressor x 1
Compressor Lubricant MEL32
Compressor Starting method Inverter
Power Source Voltage, Phase, Cycle 208 / 230V, 3 phase, 60Hz
Cooling Capacity (Nominal) 288000 Btu/h (84.4 kW) *1
Cooling Power Input (Nominal) 23.42 kW *3
Heating Capacity (Nominal) 323000 Btu/h (94.7 kW) *1
Heating Power Input (Nominal) 27.35 kW *3
Piping Diameter Liquid (High Pressure) From Twinning Kit to Indoor Units (Brazed) 1-1/8 Inches (28.58 mm) Brazed
Piping Diameter Gas (Low Pressure) From Twinning Kit to Indoor Units (Brazed) 1-3/8 Inches (34.93 mm) Brazed
Set Model With Two PURY-P144TLMU-A (-BS)
Minimum Circuit Ampacity MCA 52-48 / 52-48 Ampere *3
Maximum Overcurrent Protection MOP 80 / 70 - 80 / 70 Ampere *3
Refrigerant Type R410A x 23 lbs + 2 oz (10.5 kg) / R410A x 23 lbs + 2 oz (10.5 kg)
Fan Airflow Rate 11300 cfm (320 m³/min) / 11300 cfm (320 m³/min)
Fan Control, Driving mechanism Inverter-control, Brushless DC motor
Fan Type x Quantity Propeller fan x 2 / Propeller fan x 2
External Static Pressure 0.12 or 0.24""WG external static pressure ; factory set to 0""WG"
Sound Pressure Level (measured in anechoic room) 64 dB(A)
Indoor unit connectable Total capacity 50~150% of outdoor unit capacity
Indoor unit connectable Model (Quantity) P06~P96/2~50 (Connectable branch pipe number is max. 48.)
Operating Temperature Range Cooling (Outdoor) 23~126°F(-5~52°C) D.B. **
Operating Temperature Range Heating (Outdoor) -4~60°F(-20~15.5°C) W.B.
External Finish Pre-coated galvanized steel sheet (+powder coating for -BS type)
Max. Total Refrigerant Line Length 3,177 Ft. (968 m)
Max. Refrigerant Line Length (Between ODU & IDU) 541 Ft. (165 m)
Max. Control Wiring Length 1650 Ft. (503 m)
Heat Exchanger Salt-resistant cross fin & aluminum tube
Protection Device High Pressure Protection High pressure sensor, High pressure switch at 4.15 MPa (601 psi)
Protection Device Inverter Circuit (Comp. / Fan) Over-current protection
Protection Device Fan Motor Thermal switch
AHRI Ratings EER (Ducted/Non-Ducted) 11.2 / 11.3
AHRI Ratings IEER (Ducted/Non-Ducted) 17.6 / 18.6
AHRI Ratings COP (Ducted/Non-Ducted) 3.41 / 3.20
AHRI Ratings SCHE (Ducted/Non-Ducted) 18.2 / 19.0

Compressor Operating Range 7% to 100%
Compressor Type x Quantity Inverter scroll hermetic compressor x 1 / Inverter scroll hermetic compressor x 1
Compressor Lubricant MEL32
Compressor Starting method Inverter
Power Source Voltage, Phase, Cycle 208 / 230V, 3 phase, 60Hz
Cooling Capacity (Nominal) 288000 Btu/h (84.4 kW)
Cooling Power Input (Nominal) 23.42 kW
Heating Capacity (Nominal) 323000 Btu/h (94.7 kW)
Heating Power Input (Nominal) 27.35 kW
Piping Diameter Liquid (High Pressure) From Twinning Kit to Indoor Units (Brazed) 1-1/8 Inches (28.58 mm) Brazed
Piping Diameter Gas (Low Pressure) From Twinning Kit to Indoor Units (Brazed) 1-3/8 Inches (34.93 mm) Brazed
Set Model With Two PURY-P144YLMU-A (-BS)
Minimum Circuit Ampacity MCA 24 - 24 Ampere
Maximum Overcurrent Protection MOP 35 - 35 Ampere
Refrigerant Type R410A x 23 lbs + 2 oz (10.5 kg) / R410A x 23 lbs + 2 oz (10.5 kg)
Fan Airflow Rate 11300 cfm (320 m³/min) / 11300 cfm (320 m³/min)
Fan Control, Driving mechanism Inverter-control, Brushless DC motor
Fan Type x Quantity Propeller fan x 2 / Propeller fan x 2
External Static Pressure 0.12 or 0.24""WG external static pressure ; factory set to 0""WG"
Sound Pressure Level (measured in anechoic room) 64 dB(A)
Indoor unit connectable Total capacity 50~150% of outdoor unit capacity
Indoor unit connectable Model (Quantity) P06~P96/2~50 (Connectable branch pipe number is max. 48.)
Operating Temperature Range Cooling (Outdoor) 23~126°F(-5~52°C) D.B.
Operating Temperature Range Heating (Outdoor) -4~60°F(-20~15.5°C) W.B.
External Finish Pre-coated galvanized steel sheet (+powder coating for -BS type)
Max. Total Refrigerant Line Length 3280 Ft. (1000 m)
Max. Refrigerant Line Length (Between ODU & IDU) 541 Ft. (165 m)
Max. Control Wiring Length 1650 Ft. (503 m)
Heat Exchanger Salt-resistant cross fin & aluminum tube
Protection Device High Pressure Protection High pressure sensor, High pressure switch at 4.15 MPa (601 psi)
Protection Device Inverter Circuit (Comp. / Fan) Over-current protection
Protection Device Fan Motor Thermal switch
AHRI Ratings EER (Ducted/Non-Ducted) 11.2 / 11.3
AHRI Ratings IEER (Ducted/Non-Ducted) 17.6 / 18.6
AHRI Ratings COP (Ducted/Non-Ducted) 3.41 / 3.20
AHRI Ratings SCHE (Ducted/Non-Ducted) 18.2 / 19.0

Compressor Operating Range 17% to 100%
Compressor Type x Quantity Inverter scroll hermetic compressor
Compressor Lubricant MEL32
Compressor Starting method Inverter
Power Source Voltage, Phase, Cycle 208 / 230V, 3-Phase, 60Hz
Cooling Capacity (Nominal) 72000 Btu/h (21.1 kW) *1
Cooling Power Input (Nominal) 4.57 kW *1
Heating Capacity (Nominal) 80000 Btu/h (23.4 kW) *1
Heating Power Input (Nominal) 5.63 kW *1
Minimum Circuit Ampacity MCA 24 - 22 Ampere
Maximum Overcurrent Protection MOP 35/35 Ampere
Refrigerant Type R410A x 13 lbs + 3 oz (6.0 kg)
Fan Airflow Rate 6550 CFM (185 m³/min)
Fan Type x Quantity Propeller fan x 1
Fan Control, Driving mechanism Inverter-control, Brushless DC motor
External Static Pressure 0.12 or 0.24"WG external static pressure; factory set to 0"WG
Sound Pressure Level (measured in anechoic room) 58 dB(A)
Dimensions H x W x D Height 64-31/32 Inches (1650 mm)
Dimensions H x W x D Width 48-1/16 Inches (1220 mm)
Dimensions H x W x D Depth 29-5/32 Inches (740 mm)
Indoor unit connectable Total capacity 50~150% of outdoor unit capacity
Indoor unit connectable Model (Quantity) P06~P96/1~18
Piping Diameter Liquid (High Pressure) From Twinning Kit to Indoor Units (Brazed) 5/8 Inch (15.88 mm) Brazed
Piping Diameter Gas (Low Pressure) From Twinning Kit to Indoor Units (Brazed) 3/4 Inch (19.05 mm) Brazed
Operating Temperature Range Cooling (Outdoor) 23~126°F(-5~52°C) D.B. **
Operating Temperature Range Heating (Outdoor) W.B. -4~60° F (-20~15.5° C)
External Finish Pre-coated galvanized steel sheet
Max. Total Refrigerant Line Length 1804 Ft. (550 m)
Max. Refrigerant Line Length (Between ODU & IDU) 541 Ft. (165 m)
Max. Control Wiring Length 1650 Ft. (503 m)
Protection Device High Pressure Protection High pressure sensor, High pressure switch at 4.15 MPa (601 psi)
Protection Device Inverter Circuit (Comp. / Fan) Over-current protection
Protection Device Fan Motor Thermal switch
AHRI Ratings EER (Ducted/Non-Ducted) 13.9 / 15.5
AHRI Ratings IEER (Ducted/Non-Ducted) 21.1 / 22.1
AHRI Ratings COP (Ducted/Non-Ducted) 3.81 / 3.72
AHRI Ratings SCHE (Ducted/Non-Ducted) 23.6 / 24.5
Heat Exchanger Salt-resistant cross fin & copper tube

Compressor Operating Range 17% to 100%
Compressor Type x Quantity Inverter scroll hermetic compressor
Compressor Lubricant MEL32
Compressor Starting method Inverter
Power Source Voltage, Phase, Cycle 460V, 3-Phase, 60Hz
Cooling Capacity (Nominal) 72000 Btu/h (21.1 kW) *1
Cooling Power Input (Nominal) 4.57 kW *1
Heating Capacity (Nominal) 80000 Btu/h (23.4 kW) *1
Heating Power Input (Nominal) 5.63 kW *1
Minimum Circuit Ampacity MCA 11 Ampere
Maximum Overcurrent Protection MOP 20 Ampere
Refrigerant Type R410A x 13 lbs + 3 oz (6.0 kg)
Fan Airflow Rate 6550 cfm (185 m³/min)
Fan Type x Quantity Propeller fan x 1
Fan Control, Driving mechanism Inverter-control, Brushless DC motor
External Static Pressure 0.12 or 0.24"WG external static pressure; factory set to 0"WG
Sound Pressure Level (measured in anechoic room) 58 dB(A)
Dimensions H x W x D Height 64-31/32 Inches (1650 mm)
Dimensions H x W x D Width 48-1/16 Inches (1220 mm)
Dimensions H x W x D Depth 29-5/32 Inches (740 mm)
Indoor unit connectable Total capacity 50~150% of outdoor unit capacity
Indoor unit connectable Model (Quantity) P06~P96/1~24
Piping Diameter Liquid (High Pressure) From Twinning Kit to Indoor Units (Brazed) 5/8 Inch (15.88 mm) Brazed
Piping Diameter Gas (Low Pressure) From Twinning Kit to Indoor Units (Brazed) 3/4 Inch (19.05 mm) Brazed
Operating Temperature Range Cooling (Outdoor) 23~126°F(-5~52°C) D.B. **
Operating Temperature Range Heating (Outdoor) W.B. -4~60° F (-20~15.5° C)
External Finish Pre-coated galvanized steel sheet
Max. Total Refrigerant Line Length 1804 Ft. (550 m)
Max. Refrigerant Line Length (Between ODU & IDU) 541 Ft. (165 m)
Max. Control Wiring Length 1650 Ft. (503 m)
Protection Device High Pressure Protection High pressure sensor, High pressure switch at 4.15 MPa (601 psi)
Protection Device Inverter Circuit (Comp. / Fan) Over-current protection
Protection Device Fan Motor Thermal switch
AHRI Ratings EER (Ducted/Non-Ducted) 13.9 / 15.5
AHRI Ratings IEER (Ducted/Non-Ducted) 21.1 / 22.1
AHRI Ratings COP (Ducted/Non-Ducted) 3.81 / 3.72
AHRI Ratings SCHE (Ducted/Non-Ducted) 23.6 / 24.5
Heat Exchanger Salt-resistant cross fin & aluminum tube

Compressor Operating Range 16% to 100%
Compressor Type x Quantity Inverter scroll hermetic compressor
Compressor Lubricant MEL32
Compressor Starting method Inverter
Power Source Voltage, Phase, Cycle 208 / 230V, 3-Phase, 60Hz
Cooling Capacity (Nominal) 96000 Btu/h (28.1 kW) *1
Cooling Power Input (Nominal) 6.92 kW *1
Heating Capacity (Nominal) 108000 Btu/h (31.7 kW) *1
Heating Power Input (Nominal) 8.11 kW *1
Minimum Circuit Ampacity MCA 33-30 Ampere
Maximum Overcurrent Protection MOP 50/50 Ampere
Refrigerant Type R410A x 17 lbs + 10 oz (8 kg)
Fan Airflow Rate 6550 cfm (185 m³/min)
Fan Type x Quantity Propeller fan x 1
Fan Control, Driving mechanism Inverter-control, Brushless DC motor
External Static Pressure 0.12 or 0.24"WG external static pressure; factory set to 0"WG
Sound Pressure Level (measured in anechoic room) 58 dB(A)
Dimensions H x W x D Height 64-31/32 Inches (1650 mm)
Dimensions H x W x D Width 48-1/16 Inches (1220 mm)
Dimensions H x W x D Depth 29-5/32 Inches (740 mm)
Indoor unit connectable Total capacity 50~150% of outdoor unit capacity
Indoor unit connectable Model (Quantity) P06~P96/1~24
Piping Diameter Liquid (High Pressure) From Twinning Kit to Indoor Units (Brazed) 3/4 Inch (19.05 mm) Brazed
Piping Diameter Gas (Low Pressure) From Twinning Kit to Indoor Units (Brazed) 7/8 Inch (22.2 mm) Brazed
Operating Temperature Range Cooling (Outdoor) 23~126°F(-5~52°C) D.B. **
Operating Temperature Range Heating (Outdoor) W.B. -4~60° F (-20~15.5° C)
External Finish Pre-coated galvanized steel sheet
Protection Device High Pressure Protection High pressure sensor, High pressure switch at 4.15 MPa (601 psi)
Protection Device Inverter Circuit (Comp. / Fan) Over-current protection
Protection Device Fan Motor Thermal switch
AHRI Ratings EER (Ducted/Non-Ducted) 12.2 / 13.6
AHRI Ratings IEER (Ducted/Non-Ducted) 19.7 / 20.9
AHRI Ratings COP (Ducted/Non-Ducted) 3.64 / 3.71
AHRI Ratings SCHE (Ducted/Non-Ducted) 17.4 / 23.5
Max. Total Refrigerant Line Length 1804 Ft. (550 m)
Max. Refrigerant Line Length (Between ODU & IDU) 541 Ft. (165 m)
Max. Control Wiring Length 1650 Ft. (503 m)
Heat Exchanger Salt-resistant cross fin & aluminum tube

Compressor Operating Range 16% to 100%
Compressor Type x Quantity Inverter scroll hermetic compressor
Compressor Lubricant MEL32
Compressor Starting method Inverter
Power Source Voltage, Phase, Cycle 460V, 3-Phase, 60Hz
Cooling Capacity (Nominal) 96000 Btu/h (28.1 kW) *1
Cooling Power Input (Nominal) 6.92 kW *1
Heating Capacity (Nominal) 108000 Btu/h (31.7 kW) *1
Heating Power Input (Nominal) 8.11 kW *1
Minimum Circuit Ampacity MCA 15 Ampere
Maximum Overcurrent Protection MOP 25 Ampere
Refrigerant Type R410A x 17 lbs + 10 oz (8.0 kg)
Fan Airflow Rate 6550 cfm (185 m³/min)
Fan Type x Quantity Propeller fan x 1
Fan Control, Driving mechanism Inverter-control, Brushless DC motor
External Static Pressure 0.12 or 0.24"WG external static pressure; factory set to 0"WG
Sound Pressure Level (measured in anechoic room) 58 dB(A)
Dimensions H x W x D Height 64-31/32 Inches (1650 mm)
Dimensions H x W x D Width 48-1/16 Inches (1220 mm)
Dimensions H x W x D Depth 29-5/32 Inches (740 mm)
Indoor unit connectable Total capacity 50~150% of outdoor unit capacity
Indoor unit connectable Model (Quantity) P06~P96/1~30
Piping Diameter Liquid (High Pressure) From Twinning Kit to Indoor Units (Brazed) 3/4 Inch (19.05 mm) Brazed
Piping Diameter Gas (Low Pressure) From Twinning Kit to Indoor Units (Brazed) 7/8 Inch (22.2 mm) Brazed
Operating Temperature Range Cooling (Outdoor) 23~126°F(-5~52°C) D.B. **
Operating Temperature Range Heating (Outdoor) W.B. -4~60° F (-20~15.5° C)
External Finish Pre-coated galvanized steel sheet
Max. Total Refrigerant Line Length 1804 Ft. (550 m)
Max. Refrigerant Line Length (Between ODU & IDU) 541 Ft. (165 m)
Max. Control Wiring Length 1650 Ft. (503 m)
Protection Device High Pressure Protection High pressure sensor, High pressure switch at 4.15 MPa (601 psi)
Protection Device Inverter Circuit (Comp. / Fan) Over-current protection
Protection Device Fan Motor Thermal switch
AHRI Ratings EER (Ducted/Non-Ducted) 12.2 / 13.6
AHRI Ratings IEER (Ducted/Non-Ducted) 19.7 / 20.9
AHRI Ratings COP (Ducted/Non-Ducted) 3.64 / 3.71
AHRI Ratings SCHE (Ducted/Non-Ducted) 17.4 / 23.5
Heat Exchanger Salt-resistant cross fin & aluminum tube

Mitsubishi Electric HVAC
3400 Lawrenceville Suwanee Rd.
Suwanee,  GA USA 30024 
Tel: (800) 687-1966
Fax: (800) 658-1458
Website: http://www.mehvac.com

Sweets app for Revit – Learn More