Mitsubishi Electric HVAC-Proposed - K-Generation Y-Series H2i® - CITY MULTI VRF Heat Pumps - Outdoor Units-0_PUHY-HP192TSJMU-A

K-Generation Y-Series H2i® - CITY MULTI VRF Heat Pumps - Outdoor Units-0_PUHY-HP192TSJMU-A


Category: Central HVAC Equipment | heat recovery | heat recovery systems...

MasterFormat: Central HVAC Equipment | Decentralized HVAC Equipment | Decentralized Unitary HVAC Equipment



Mitsubishi Electric HVAC-Proposed
3400 Lawrenceville Suwanee Rd.
Suwanee, GA 30024
Tel: (800) 687-1966
Fax: (800) 658-1458

http://www.mehvac.com

Request More Info

DOWNLOADS

Related Products

Overview



K-Generation Y-Series H2i® - CITY MULTI VRF Heat Pumps - Outdoor Units - 0_PUHY-HP192TSJMU-A

K-Generation Y-Series H2i® - CITY MULTI VRF Heat Pumps - Outdoor Units


Model Number: 0_PUHY-HP192TSJMU-A

 


Cools or heats up to 41 individual zones
Available sizes: 6-16 tons
Available in both 208/230V
Provides full heating capacity at 0° F outdoor ambient
Provides 85% heating capacity at -13° F
Uses T-branches and headers to provide piping design flexibility
INVERTER-driven compressor for outstanding performance and optimized energy usage
Maximum pipe length: 984 feet
Connects to CITY MULTI indoor units; controlled via CITY MULTI Controls Network (CMCN)
External finish: Pre-coated galvanized-steel with thermoset polyester-resin




Power Source Voltage, Phase, Cycle 208 / 230V, 3 phase, 60Hz
Cooling Capacity (Nominal) 144000 Btu/h (42.3 kW) *1
Cooling Power Input (Nominal) 11.54 kW *1
Cooling Current Input (Nominal) 35.5 / 32.1 Ampere *1
Heating Capacity (Nominal) 160000 Btu/h (46.9 kW) *1
Heating Power Input (Nominal) 12.65 kW *1
Heating Current Input (Nominal) 39.0 / 35.2 Ampere *1
Refrigerant Type R410A
Compressor Type x Quantity Inverter scroll hermetic compressor x 1
Compressor Crankcase Heater 0.045(230 V)
Compressor Lubricant MEL32
Compressor Starting method Inverter
Compressor Motor Output 5.3 kW
Fan Airflow Rate 6180 CFM (175 m³/min)
Fan Type x Quantity Propeller fan x 1
Fan Motor output 0.92 kW
Fan Driving mechanism Inverter-control, Direct-driven by motor
External Static Pressure 0 in.WG (0 Pa)
Sound Pressure Level (measured in anechoic room) 59 dB(A)
Dimensions H x W x D Height 64-31/32 Inches (1650 mm) / 64-31/32 Inches (1650 mm)
Dimensions H x W x D Width 36-1/4 Inches (939 mm) / 36-1/4 Inches (939 mm)
Dimensions H x W x D Depth 29-15/16 Inches (760 mm) / 29-15/16 Inches (760 mm)
Indoor unit connectable Total capacity 50~130 % of outdoor unit capacity
Indoor unit connectable Model (Quantity) P06 - P96 / 1 to 31
Refrigerant Pipe Dimensions Liquid (High Pressure) 5/8 Inch (15.88 mm) Brazed
Refrigerant Pipe Dimensions Gas (Low Pressure) 1-1/8 Inches (28.58 mm) Brazed
Operating Temperature Range Cooling (Outdoor) 23~109° F (-5~43° C) D.B. **
Operating Temperature Range Heating (Outdoor) -13~60° F (-25~15.5° C) W.B.
Operating Environment - Minimum Cooling (Outdoor) 23~109°F(-5~43°C) D.B.
Pipe between unit and distributor Liquid (High Pressure) 1/2 Inch (12.7 mm) Brazed
Pipe between unit and distributor Gas (Low Pressure mm) 3/4 Inches (19.05 mm) Brazed
Protection Device High Pressure Protection High pressure sensor, High pressure switch at 4.15MPa (601 psi)
Protection Device Inverter circuit (COMP. / FAN) Over-heat protection,Over-current protection
Protection Device Compressor Over-heat protection
External Finish Pre-coated galvanized steel sheet (+powder coating for -BS type)
Heat Exchanger Salt-resistant cross fin & copper tube

Power Source Voltage, Phase, Cycle 208 / 230V, 3 phase, 60Hz
Cooling Capacity (Nominal) 192000 Btu/h (56.3 kW) *1
Cooling Power Input (Nominal) 16.81 kW *1
Cooling Current Input (Nominal) 51.8 / 46.8 Ampere *1
Heating Capacity (Nominal) 216000 Btu/h (63.4 kW) *1
Heating Power Input (Nominal) 18.13 kW *1
Heating Current Input (Nominal) 55.9 / 50.5 Ampere *1
Refrigerant Type R410A
Compressor Type x Quantity Inverter scroll hermetic compressor x 1
Compressor Crankcase Heater 0.045(230 V)
Compressor Lubricant MEL32
Compressor Starting method Inverter
Compressor Motor Output 6.7 kW
Fan Airflow Rate 7950 CFM (225 m³/min)
Fan Type x Quantity Propeller fan x 1
Fan Motor output 0.92 kW
Fan Driving mechanism Inverter-control, Direct-driven by motor
External Static Pressure 0 in.WG (0 Pa)
Sound Pressure Level (measured in anechoic room) 60 dB(A)
Dimensions H x W x D Height 64-31/32 Inches (1650 mm) / 64-31/32 Inches (1650 mm)
Dimensions H x W x D Width 48-1/16 Inches (1244 mm) / 48-1/16 Inches (1244 mm)
Dimensions H x W x D Depth 29-15/16 Inches (760 mm) / 29-15/16 Inches (760 mm)
Indoor unit connectable Total capacity 50~130 % of outdoor unit capacity
Indoor unit connectable Model (Quantity) P06 - P96 / 1 to 41
Refrigerant Pipe Dimensions Liquid (High Pressure) 5/8 Inch (15.88 mm) Brazed
Refrigerant Pipe Dimensions Gas (Low Pressure) 1-1/8 Inches (28.58 mm) Brazed
Operating Temperature Range Cooling (Outdoor) 23~109° F (-5~43° C) D.B. **
Operating Temperature Range Heating (Outdoor) -13~60° F (-25~15.5° C) W.B.
Operating Environment - Minimum Cooling (Outdoor) 23~109°F(-5~43°C) D.B.
Heat Exchanger Salt-resistant cross fin & copper tube
Pipe between unit and distributor Liquid (High Pressure) 1/2 Inch (12.7 mm) Brazed
Pipe between unit and distributor Gas (Low Pressure mm) 7/8 Inches (22.2 mm) Brazed
Protection Device High Pressure Protection High pressure sensor, High pressure switch at 4.15MPa (601 psi)
Protection Device Inverter circuit (COMP. / FAN) Over-heat protection,Over-current protection
Protection Device Compressor Over-heat protection
External Finish Pre-coated galvanized steel sheet (+powder coating for -BS type)

Power Source Voltage, Phase, Cycle 208 / 230V, 3 phase, 60Hz
Cooling Capacity (Nominal) 72000 Btu/h (21.1 kW) *1
Cooling Power Input (Nominal) 5.6 kW *3
Cooling Current Input (Nominal) 17.2 / 15.6 Ampere *3
Heating Capacity (Nominal) 80000 Btu/h (23.4 kW) *1
Heating Power Input (Nominal) 6.14 kW *3
Heating Current Input (Nominal) 18.9 / 17.1 Ampere *3
Refrigerant Type R410A
Compressor Type x Quantity Inverter scroll hermetic compressor x 1
Compressor Crankcase Heater 0.045(230 V)
Compressor Lubricant MEL32
Compressor Starting method Inverter
Compressor Motor Output 5.3 kW
Fan Airflow Rate 6180 CFM (175 m³/min)
Fan Type x Quantity Propeller fan x 1
Fan Motor output 0.92 kW
Fan Driving mechanism Inverter-control,Direct-driven by motor
External Static Pressure 0 in.WG (0 Pa)
Sound Pressure Level (measured in anechoic room) 56 dB(A)
Dimensions H x W x D Height 64-31/32 Inches (1650 mm)
Dimensions H x W x D Width 36-1/4 Inches (939 mm)
Dimensions H x W x D Depth 29-15/16 Inches (760 mm)
Indoor unit connectable Total capacity 50~130 % of outdoor unit capacity
Indoor unit connectable Model (Quantity) P06 - P72 / 1 to 15
Refrigerant Pipe Dimensions Liquid (High Pressure) 1/2 Inch (12.7 mm) Brazed
Refrigerant Pipe Dimensions Gas (Low Pressure) 3/4 Inch (19.05 mm) Brazed
Operating Temperature Range Cooling (Outdoor) 23~109° F (-5~43° C) D.B. **
Operating Temperature Range Heating (Outdoor) -13~60° F (-25~15.5° C) W.B.
Heat Exchanger Salt-resistant cross fin & copper tube
Protection Device High Pressure Protection High pressure sensor, High pressure switch at 4.15MPa (601 psi)
Protection Device Inverter circuit (COMP. / FAN) Over-heat protection, Over-current protection
Protection Device Compressor Over-heat protection
External Finish Pre-coated galvanized steel sheet (+powder coating for -BS type)
Operating Environment - Minimum Cooling (Outdoor) 23~109°F(-5~43°C) D.B.

Power Source Voltage, Phase, Cycle 208 / 230V, 3 phase, 60Hz
Cooling Capacity (Nominal) 96000 Btu/h (28.1 kW) *1
Cooling Power Input (Nominal) 8.16 kW *3
Cooling Current Input (Nominal) 25.1 / 22.7 Ampere *3
Heating Capacity (Nominal) 108000 Btu/h (31.7 kW) *1
Heating Power Input (Nominal) 8.8 kW *3
Heating Current Input (Nominal) 27.1 / 24.5 Ampere *3
Refrigerant Type R410A
Compressor Type x Quantity Inverter scroll hermetic compressor x 1
Compressor Crankcase Heater 0.045(230 V)
Compressor Lubricant MEL32
Compressor Starting method Inverter
Compressor Motor Output 6.7 kW
Fan Airflow Rate 7950 CFM (225 m³/min)
Fan Type x Quantity Propeller fan x 1
Fan Motor output 0.92 kW
Fan Driving mechanism Inverter-control, Direct-driven by motor
External Static Pressure 0 in.WG (0 Pa)
Sound Pressure Level (measured in anechoic room) 57 dB(A)
Dimensions H x W x D Height 64-31/32 Inches (1650 mm)
Dimensions H x W x D Width 48-1/16 Inches (1244 mm)
Dimensions H x W x D Depth 29-15/16 Inches (760 mm)
Indoor unit connectable Total capacity 50~130 % of outdoor unit capacity
Indoor unit connectable Model (Quantity) P06 - P96 / 1 to 20
Refrigerant Pipe Dimensions Liquid (High Pressure) 1/2 Inch (12.7 mm) Brazed
Refrigerant Pipe Dimensions Gas (Low Pressure) 7/8 Inch (22.2 mm) Brazed
Operating Temperature Range Cooling (Outdoor) 23~109° F (-5~43° C) D.B. **
Operating Temperature Range Heating (Outdoor) -13~60° F (-25~15.5° C) W.B.
Operating Environment - Minimum Cooling (Outdoor) 23~109°F(-5~43°C) D.B.
Heat Exchanger Salt-resistant cross fin & copper tube
Protection Device High Pressure Protection High pressure sensor, High pressure switch at 4.15MPa (601 psi)
Protection Device Inverter circuit (COMP. / FAN) Over-heat protection, Over-current protection
Protection Device Compressor Over-heat protection
External Finish Pre-coated galvanized steel sheet (+powder coating for -BS type)

Mitsubishi Electric HVAC
3400 Lawrenceville Suwanee Rd.
Suwanee,  GA USA 30024 
Tel: (800) 687-1966
Fax: (800) 658-1458
Website: http://www.mehvac.com

Sweets app for Revit – Learn More