Mitsubishi Electric HVAC - P-Series Heat Pumps - Indoor Units_PLA-PLA-A36BA6/PUZ-A36NHA6

DOWNLOADS
P-Series Heat Pumps - Indoor Units_PLA Model Number: #PLA-A36BA6/PUZ-A36NHA6 Ceiling-recessed ductless heat pumps - 33x33". Rated capacity range 12,000 - 42,000 Btu/h. Features Branch duct capability Built-in drain lift mechanism for condensate removal; lifts to 33-7/16" Wide air flow pattern...

MasterFormat: Decentralized HVAC Equipment | Decentralized Unitary HVAC Equipment



Mitsubishi Electric HVAC
3400 Lawrenceville Suwanee Rd.
Suwanee, GA 30024
Tel: (800) 687-1966
Fax: (800) 658-1458

http://www.mehvac.com

Request More Info

DOWNLOADS

Related Products

Overview



P-Series Heat Pumps - Indoor Units_PLA - PLA-A36BA6/PUZ-A36NHA6

P-Series Heat Pumps - Indoor Units_PLA


Model Number: #PLA-A36BA6/PUZ-A36NHA6

Ceiling-recessed ductless heat pumps - 33x33". Rated capacity range 12,000 - 42,000 Btu/h.


Features
  • Branch duct capability
  • Built-in drain lift mechanism for condensate removal; lifts to 33-7/16"
  • Wide air flow pattern for better air distribution
  • Auto wave airflow in heating mode—unit independently cycles through horizontal and vertical positions for more even heat distribution
  • Independent vane adjustment
  • Automatic fan speed control
  • Self-check function—integrated diagnostics
  • Advanced microprocessor control
  • Multiple controller options
  • Limited warranty: five years on parts/defects, seven years on compressors


Power Supply Phase, Cycle, Voltage 1 Phase, 60Hz, 208/230V *4
Cooling Rated Capacity 35000 Btu/h (10.26 kW) *1
Cooling Capacity Range 12000 - 35000 Btu/h (3.5 - 10.3 kW)
Cooling Total Input 4500 W (4.500 kW)
Cooling Energy Efficiency SEER 14.2
Cooling Sensible Heat Factor 0.74
Cooling EER 7.8
Cooling Moisture Removal Pints/H 8.1
Heating at 47° F Rated Capacity 37000 Btu/h (10.8 kW) *2
Heating at 47° F Capacity Range 12000 - 38000 Btu/h (3.5 - 11.1 kW)
Heating at 47° F Total Input 3300 W
Heating at 47° F HSPF (Region IV) 9.3
Heating at 47° F COP 3.2 Btu/Btu
Heating at 17° F COP 2.3 Btu/Btu
Heating at 17° F Rated Capacity 25000 Btu/h (7.3 kW) *3
Heating at 17° F Total Input 3070 W
Minimum Circuit Ampacity MCA 2 Ampere
Maximum fuse size (time delay) MOCP 15 Ampere
Refrigerant Type R410A
Fan Fan(drive) x No. Turbo fan (direct) x 1
Fan Fan Motor - F.L.A. 1 F.L.A
Fan Fan motor output - kW 0.12 kW
External Static Pressure 0 (direct blow)
Airflow DRY 460-530-600-710 CFM (20-23-26-30 m³/min)
Airflow WET 670-770-880-1030 CFM (19-22-25-29 m³/min)
Sound Pressure Level 32-34-39-41 dB(A)
Dimensions H x W x D Height UNIT : 298 Inches (11-3/4 mm) ; PANEL : 35 Inches (1-3/8 mm)
Dimensions H x W x D Width UNIT : 840 Inches (33-1/16 mm) PANEL : 950 Inches (37-3/8 mm)
Dimensions H x W x D Depth UNIT : 840 Inches (33-1/16 mm) PANEL : 950 Inches (37-3/8 mm)
Field Drainpipe Size O.D. 32 (1-1/4)
Refrigerant Piping Connection Method Indoor / Outdoor Flared / Flared
Operation Conditions - Indoor Intake Air Temperature Cooling - Maximum - DB , WB 95°F (35°C) DB, 71°F (22°C) WB
Operation Conditions - Indoor Intake Air Temperature Cooling - Minimum - DB , WB 67°F (19°C) DB, 57°F (14°C) WB
Operation Conditions - Indoor Intake Air Temperature Heating - Maximum - DB , WB 80°F (27°C) DB, 67° (19°C) WB
Operation Conditions - Indoor Intake Air Temperature Heating - Minimum - DB , WB 70°F (21°C DB, 60°F (16°C) WB
Operation Conditions - Indoor Intake Air Temperature Cooling - Maximum - DB 95°F (35°C) DB
Operation Conditions - Indoor Intake Air Temperature Cooling - Maximum -WB 71°F (22°C) WB
Operation Conditions - Indoor Intake Air Temperature Cooling - Minimum - DB 67°F (19°C) DB
Operation Conditions - Indoor Intake Air Temperature Cooling - Minimum - WB 57°F (14°C) WB
Operation Conditions - Indoor Intake Air Temperature Heating - Maximum - DB 80°F (27°C) DB, 67° (19°C) WB
Operation Conditions - Indoor Intake Air Temperature Heating - Maximum - WB 67° (19°C) WB
Operation Conditions - Indoor Intake Air Temperature Heating - Minimum - DB 70°F (21°C DB
Operation Conditions - Indoor Intake Air Temperature Heating - Minimum - WB 60°F (16°C) WB
Operation Conditions - Outdoor Intake Air Temperature Cooling - Maximum - DB , WB 115°F (46°C) DB
Operation Conditions - Outdoor Intake Air Temperature Heating - Maximum - DB , WB 70°F (21°C) DB, 59°F (15°C) WB
Operation Conditions - Outdoor Intake Air Temperature Heating - Minimum - DB , WB 12°F (-11°C) DB, 10°F (-12°C) WB
Operation Conditions - Outdoor Intake Air Temperature Cooling - Maximum - DB 115°F (46°C) DB
Operation Conditions - Outdoor Intake Air Temperature Cooling - Maximum - WB 115°F (46°C) DB
Operation Conditions - Outdoor Intake Air Temperature Cooling- Minimum - DB 0°F** (-18°C) DB
Operation Conditions - Outdoor Intake Air Temperature Heating - Maximum - DB 70°F (21°C) DB
Operation Conditions - Outdoor Intake Air Temperature Heating - Maximum - WB 59°F (15°C) WB
Operation Conditions - Outdoor Intake Air Temperature Heating - Minimum - DB 12°F (-11°C) DB
Operation Conditions - Outdoor Intake Air Temperature Heating - Minimum - WB 10°F (-12°C) WB
Heat Exchanger Plate fin coil
Voltage Indoor - Outdoor S1-S2 AC 208 / 230V
Voltage Indoor - Outdoor S2-S3 DC 12-24V
External Finish Munsell 6.4Y 8.9/0.4