Mitsubishi Electric HVAC - P-Series Heat Pumps - Indoor Units_PEA/PEAD-PEAD-A42AA5/PUZ-HA42NKA

P-Series Heat Pumps - Indoor Units_PEA/PEAD Model Number: #PEAD-A42AA5/PUZ-HA42NKA Ceiling concealed horizontal ducted unit for applications with short duct runs. Rated capacities range from 12,000-42,000 Btu/h. Features Ceiling-concealed ducted indoor unit for residential and small Ultra-thin...


MasterFormat: Decentralized HVAC Equipment | Decentralized Unitary HVAC Equipment



Mitsubishi Electric HVAC
3400 Lawrenceville Suwanee Rd.
Suwanee, GA 30024
Tel: (800) 687-1966
Fax: (800) 658-1458

http://www.mehvac.com

Request More Info

DOWNLOADS

Related Products

Overview



P-Series Heat Pumps - Indoor Units_PEA/PEAD - PEAD-A42AA5/PUZ-HA42NKA

P-Series Heat Pumps - Indoor Units_PEA/PEAD


Model Number: #PEAD-A42AA5/PUZ-HA42NKA

Ceiling concealed horizontal ducted unit for applications with short duct runs. Rated capacities range from 12,000-42,000 Btu/h.


Features
  • Ceiling-concealed ducted indoor unit for residential and small
  • Ultra-thin body: 7-7/8" high
  • Built-in drain mechanism for condensate removal; lifts to 21-11/16"
  • Air filter is included with indoor unit
  • Quiet operation—both indoor and outdoor units
  • PAR-21MAA wired remote controller is included; wireless
  • Automatic fan speed control
  • Auto restart following a power outage
  • Self-check function—integrated diagnostics


Power Supply Phase, Cycle, Voltage 1 Phase, 60Hz, 208/230V *4
Cooling Rated Capacity 42000 Btu/h (12.31 kW) *1
Cooling Capacity Range 18000 - 42000 Btu/h (5.3 - 12.3 kW)
Cooling Total Input 5350 W (5.400 kW)
Cooling Energy Efficiency SEER 13.8
Cooling Sensible Heat Factor 0.76
Cooling Moisture Removal Pints/H 9
Cooling EER 7.8
Heating at 47° F Rated Capacity 45000 Btu/h (13.2 kW) *2
Heating at 47° F Capacity Range 18000 - 48000 Btu/h (5.3 - 14.1 kW)
Heating at 47° F Total Input 3820 W
Heating at 47° F HSPF (Region IV) 10
Heating at 47° F COP 3.44
Heating at 17° F COP 2.3 Btu/Btu
Heating at 17° F Total Input 3820 W
Heating at 17° F Rated Capacity 30000 Btu/h (8.8 kW) *3
Recommended Fuse/Breaker Size 30 Ampere
Refrigerant Type R410A
Refrigerant Oil Type 1.4 (FV50S) [45]
Refrigerant Charge 4.5 [10lbs]
Refrigerant Control Linear Expansion Valve
Fan Fan Motor - F.L.A. 2.8 F.L.A
Fan Fan motor output - kW 244 W
External Static Pressure 0.14-0.2-0.28-0.4-0.6 in. W.G. (35-50-70-100-150 Pa)
Airflow DRY 1042-1254-1483 CFM ( 29.5-35.5-42 m³/min)
Airflow WET 953-1165-1412 CFM (27-33-40 m³/min)
Sound Pressure Level 36-40-44 dB(A)
Dimensions H x W x D Height 9-7/8 Inches (250 mm)
Dimensions H x W x D Width 55-1/8 Inches (1400 mm)
Dimensions H x W x D Depth 28-7/8 Inches (732 mm)
Field Drainpipe Size O.D. 1-9/32 Inches (32 mm)
Refrigerant Piping Connection Method Indoor / Outdoor Flared / Flared
Operation Conditions - Indoor Intake Air Temperature Cooling - Maximum - DB , WB 95°F (35°C) DB, 71°F (22°C) WB
Operation Conditions - Indoor Intake Air Temperature Cooling - Minimum - DB , WB 67°F (19°C) DB, 57°F (14°C) WB
Operation Conditions - Indoor Intake Air Temperature Heating - Maximum - DB , WB 80°F (27°C) DB, 67° (19°C) WB
Operation Conditions - Indoor Intake Air Temperature Heating - Minimum - DB , WB 70°F (21°C DB, 60°F (16°C) WB
Operation Conditions - Indoor Intake Air Temperature Heating - Minimum - WB 60°F (16°C) WB
Operation Conditions - Indoor Intake Air Temperature Heating - Minimum - DB 70°F (21°C) DB
Operation Conditions - Indoor Intake Air Temperature Cooling - Minimum - DB 67°F (19°C) DB
Operation Conditions - Indoor Intake Air Temperature Cooling - Maximum -WB 71°F (22°C) WB
Operation Conditions - Indoor Intake Air Temperature Cooling - Maximum - DB 95°F (35°C) DB
Operation Conditions - Indoor Intake Air Temperature Heating - Maximum - DB 80°F (27°C) DB, 67° (19°C) WB
Operation Conditions - Indoor Intake Air Temperature Heating - Maximum - WB 67° (19°C) WB
Operation Conditions - Indoor Intake Air Temperature Cooling - Minimum - WB 57°F (14°C) WB
Operation Conditions - Outdoor Intake Air Temperature Cooling - Maximum - DB , WB 115°F (46°C) DB
Operation Conditions - Outdoor Intake Air Temperature Heating - Maximum - DB , WB 70°F (21°C) DB, 59°F (15°C) WB
Operation Conditions - Outdoor Intake Air Temperature Heating - Minimum - DB , WB 12°F (-11°C) DB, 10°F (-12°C) WB
Operation Conditions - Outdoor Intake Air Temperature Heating - Minimum - WB 10°F (-12°C) WB
Operation Conditions - Outdoor Intake Air Temperature Heating - Minimum - DB 12°F (-11°C) DB
Operation Conditions - Outdoor Intake Air Temperature Heating - Maximum - WB 59°F (15°C) WB
Operation Conditions - Outdoor Intake Air Temperature Cooling - Maximum - DB 115°F (46°C) DB
Operation Conditions - Outdoor Intake Air Temperature Cooling - Maximum - WB 115°F (46°C) DB
Operation Conditions - Outdoor Intake Air Temperature Heating - Maximum - DB 70°F (21°C) DB
Operation Conditions - Outdoor Intake Air Temperature Cooling- Minimum - DB 0°F** (-18°C) DB
Voltage Indoor - Outdoor S2-S3 DC24V
Voltage Indoor - Outdoor S1-S2 AC 208 / 230V
External Finish Galvanized