Mitsubishi Electric HVAC - P-Series Heat Pumps - Indoor Units_PCA-PCA-A30KA4/PUZ-A30NHA4

P-Series Heat Pumps - Indoor Units_PCA Model Number: #PCA-A30KA4/PUZ-A30NHA4 Ceiling-suspended ductless indoor unit for residential and commercial applications. Ideal for larger retails stores, classrooms, restaurants, office spaces, entrances, and more. Rated capacities range from 24,000 -...


MasterFormat: Decentralized HVAC Equipment | Decentralized Unitary HVAC Equipment



Mitsubishi Electric HVAC
3400 Lawrenceville Suwanee Rd.
Suwanee, GA 30024
Tel: (800) 687-1966
Fax: (800) 658-1458

http://www.mehvac.com

Request More Info

DOWNLOADS

Related Products

Overview



P-Series Heat Pumps - Indoor Units_PCA - PCA-A30KA4/PUZ-A30NHA4

P-Series Heat Pumps - Indoor Units_PCA


Model Number: #PCA-A30KA4/PUZ-A30NHA4

Ceiling-suspended ductless indoor unit for residential and commercial applications. Ideal for larger retails stores, classrooms, restaurants, office spaces, entrances, and more. Rated capacities range from 24,000 - 42,000 Btu/h.


Features
  • Compact design
  • Standard air filter is included with indoor unit; high-efficiency filter is available as an option
  • High-efficiency
  • Quiet operation—both indoor and outdoor units
  • Optional Wireless Remote Controller with Receiver Kit is available with or without i-see Sensor
  • i-see Sensor available as a stand-alone option
  • PAR-21MAA wired remote controller is included
  • Self-check function—integrated diagnostics
  • Control airflow angle for better coverage


Power Supply Phase, Cycle, Voltage 1 Phase, 60Hz, 208/230V *4
Cooling Rated Capacity 30000 Btu/h (8.79 kW) *1
Cooling Capacity Range 12000 - 30000 BTU/h (3.5 - 8.8 kW)
Cooling Total Input 3760 W (3.800 kW)
Cooling Energy Efficiency SEER 14.5
Cooling Sensible Heat Factor 0.69
Cooling EER 8
Cooling Moisture Removal Pints/H 8.3
Heating at 47° F Rated Capacity 32000 Btu/h (9.4 kW) *2
Heating at 47° F Capacity Range 12000 - 34000 Btu/h (3.5 - 10 kW)
Heating at 47° F Total Input 3210 W
Heating at 47° F HSPF (Region IV) 9.2
Heating at 47° F COP 2.9
Heating at 17° F COP 2.2 Btu/Btu
Heating at 17° F Rated Capacity 23000 Btu/h (6.7 kW) *3
Heating at 17° F Total Input 2940 W
Minimum Circuit Ampacity MCA 1 Ampere
Recommended Fuse/Breaker Size 30 Ampere
Refrigerant Type R410A
Refrigerant Oil Type 0.87 (FV50S) [28]
Refrigerant Charge 3.0 [6 lbs 10 oz]
Fan Fan motor output - kW 95 W
Fan Fan Motor - F.L.A. 0.54 F.L.A
External Static Pressure 0
Airflow Cooling : DRY 565-600-635-705 CFM (16-17-18-20 m³/min)
Airflow Cooling : WET 530-565-600-670 CFM (15-16-17-19 m³/min)
Sound Pressure Level 35-37-39-41 dB(A)
Dimensions H x W x D Height 9-1/16 Inches (230 mm)
Dimensions H x W x D Width 50-3/8 Inches (1280 mm)
Dimensions H x W x D Depth 26-3/4 Inches (680 mm)
Field Drainpipe Size O.D. 1-1/32 Inches (26 mm)
Refrigerant Piping Connection Method Indoor / Outdoor Flared / Flared
Operation Conditions - Indoor Intake Air Temperature Cooling - Maximum - DB , WB 95°F (35°C) DB, 71°F (22°C) WB
Operation Conditions - Indoor Intake Air Temperature Cooling - Minimum - DB , WB 67°F (19°C) DB, 57°F (14°C) WB
Operation Conditions - Indoor Intake Air Temperature Heating - Maximum - DB , WB 80°F (27°C) DB, 67° (19°C) WB
Operation Conditions - Indoor Intake Air Temperature Heating - Minimum - DB , WB 70°F (21°C DB, 60°F (16°C) WB
Operation Conditions - Indoor Intake Air Temperature Cooling - Maximum - DB 95°F (35°C) DB
Operation Conditions - Indoor Intake Air Temperature Cooling - Maximum -WB 71°F (22°C) WB
Operation Conditions - Indoor Intake Air Temperature Cooling - Minimum - DB 67°F (19°C) DB
Operation Conditions - Indoor Intake Air Temperature Cooling - Minimum - WB 57°F (14°C) WB
Operation Conditions - Indoor Intake Air Temperature Heating - Maximum - DB 80°F (27°C) DB
Operation Conditions - Indoor Intake Air Temperature Heating - Maximum - WB 67° (19°C) WB
Operation Conditions - Indoor Intake Air Temperature Heating - Minimum - DB 70°F (21°C) DB
Operation Conditions - Indoor Intake Air Temperature Heating - Minimum - WB 60°F (16°C) WB
Operation Conditions - Outdoor Intake Air Temperature Cooling - Maximum - DB , WB 115°F (46°C) DB
Operation Conditions - Outdoor Intake Air Temperature Heating - Maximum - DB , WB 70°F (21°C) DB, 59°F (15°C) WB
Operation Conditions - Outdoor Intake Air Temperature Heating - Minimum - DB , WB 12°F (-11°C) DB, 10°F (-12°C) WB
Operation Conditions - Outdoor Intake Air Temperature Cooling - Maximum - DB 115°F (46°C) DB
Operation Conditions - Outdoor Intake Air Temperature Cooling- Minimum - DB 0°F** (-18°C) DB
Operation Conditions - Outdoor Intake Air Temperature Heating - Maximum - DB 70°F (21°C) DB
Operation Conditions - Outdoor Intake Air Temperature Heating - Maximum - WB 59°F (15°C) WB
Operation Conditions - Outdoor Intake Air Temperature Heating - Minimum - DB 12°F (-11°C) DB
Operation Conditions - Outdoor Intake Air Temperature Heating - Minimum - WB 10°F (-12°C) WB
Voltage Indoor - Outdoor S1-S2 AC 208 / 230V
Voltage Indoor - Outdoor S2-S3 DC24V
External Finish White Munsell 6.4Y 8.9/0.4

Mitsubishi Electric HVAC
3400 Lawrenceville Suwanee Rd.
Suwanee,  GA USA 30024 
Tel: (800) 687-1966
Fax: (800) 658-1458
Website: http://www.mehvac.com

Sweets app for Revit – Learn More