Mitsubishi Electric HVAC - M-Series Heat Pumps - Indoor Units (Multi Zone)_SLZ-SLZ-KA15NA

DOWNLOADS
M-Series Heat Pumps - Indoor Units (Multi Zone)_SLZ Model Number: #SLZ-KA15NA Ceiling-recessed cassette (24"x24") ductless heat pump units offer a wide airflow pattern for better air distribution in a less obtrusive style.  Intall SLZ in a hard ceiling (with an access panel for servicing) or in...

MasterFormat: Decentralized HVAC Equipment | Decentralized Unitary HVAC Equipment



Mitsubishi Electric HVAC
3400 Lawrenceville Suwanee Rd.
Suwanee, GA 30024
Tel: (800) 687-1966
Fax: (800) 658-1458

http://www.mehvac.com

Request More Info

DOWNLOADS

Related Products

Overview



M-Series Heat Pumps - Indoor Units (Multi Zone)_SLZ - SLZ-KA15NA

M-Series Heat Pumps - Indoor Units (Multi Zone)_SLZ


Model Number: #SLZ-KA15NA

Ceiling-recessed cassette (24"x24") ductless heat pump units offer a wide airflow pattern for better air distribution in a less obtrusive style.  Intall SLZ in a hard ceiling (with an access panel for servicing) or in a 2'x2' drop ceiling. Rated capacities range from 8,400 to 15,000 Btu/h.


Features
  • Wide airflow pattern for excellent air distribution
  • 4" ventilation air intake knockout
  • Built-in drain condensate lift mechanism
  • Select from MHK1 (preferred), PAR-21MA, or PAR-FL/FA32 remote controllers
  • Long-life air filter included
  • Automatic fan speed control
  • Limited warranty: five years on parts and defects and seven years on compressors


Power Supply Phase, Cycle, Voltage 4 Phase, 60Hz, 208/230V *4
Cooling Rated Capacity 15000 Btu/h (4.4 kW) *1
Cooling Capacity Range 3,800-17,700 Btu/h (1.1 - 5.2 kW)
Cooling Total Input 1460 W (1.500 kW)
Cooling Energy Efficiency SEER 16
Cooling Sensible Heat Factor 0.67
Cooling Moisture Removal Pints/H 4.5
Cooling EER 10.2
Heating at 47° F Rated Capacity 18000 Btu/h (5.3 kW) *2
Heating at 47° F Capacity Range 3,100-22,000 Btu/h (0.9 - 6.5 kW)
Heating at 47° F Total Input 1950 W
Heating at 47° F HSPF (Region IV) 9.6
Heating at 47° F COP 2.7
Heating at 17° F Maximum Capacity 12000 Btu/h (3.5 kW)
Heating at 17° F COP 2.38 Btu/Btu
Heating at 17° F Rated Capacity 13103 Btu/h (3.8 kW) *3
Heating at 17° F Total Input 1353 W
Minimum Circuit Ampacity MCA 1 Ampere
Recommended Fuse/Breaker Size 15 Ampere
Refrigerant Type R410A
Compressor Model SNB130FQBH
Fan Fan Motor - F.L.A. 0.28 F.L.A
External Static Pressure 0.02 -0.06-0.14 -0.20 In. WG (5 -15-35 -50 Pa)
Airflow Cooling : DRY 280-320-390 CFM (8-9-11 m³/min)
Airflow Cooling : WET 250-290-350 CFM (7-8-10 m³/min)
Airflow Heating : WET 250-290-350 CFM (7-8-10 m³/min)
Sound Pressure Level 31-35-40 dB(A)
Dimensions H x W x D Height UNIT : 9-1/4 Inches (235 mm) ; Grille 13/16 Inches (20 mm)
Dimensions H x W x D Width Unit: 22-7/16 Inches (570 mm) ; Grille: 25-5/8 Inches (650 mm)
Dimensions H x W x D Depth Unit: 22-7/16 Inches (570 mm) ; Grille: 25-5/8 Inches (650 mm)
Refrigerant Pipe Size O.D. Gas (Low Pressure) 1/2 Inch (12.7 mm)
Refrigerant Pipe Size O.D. Liquid (High Pressure) 1/4 Inch (6.35 mm)
Field Drainpipe Size O.D. 1-1/4 Inches (32 mm)
Maximum Refrigerant Pipe Height Difference If Indoor Unit is Above Outdoor Unit 49 ft. (15 m)
Maximum Refrigerant Pipe Height Difference If Indoor Unit is Below Outdoor Unit - Inches (Meter) 33 ft. (10 m)
Maximum Piping Length for Each Indoor Unit 82 ft. (25 m)
Refrigerant Piping Connection Method Indoor / Outdoor Flared / Flared
Operation Conditions - Indoor Intake Air Temperature Cooling - Maximum - DB , WB 95°F (35°C) DB, 71°F (22°C) WB
Operation Conditions - Indoor Intake Air Temperature Cooling - Minimum - DB , WB 67°F (19°C) DB , 57°F (14°C) WB
Operation Conditions - Indoor Intake Air Temperature Heating - Maximum - DB , WB 80°F (27°C) DB, 67°F (19°C) WB
Operation Conditions - Indoor Intake Air Temperature Heating - Minimum - DB , WB 70°F (21°C) DB, 60°F (16°C) WB
Operation Conditions - Indoor Intake Air Temperature Cooling - Maximum - DB 95°F (35°C) DB
Operation Conditions - Indoor Intake Air Temperature Cooling - Maximum -WB 71°F (22°C) WB
Operation Conditions - Indoor Intake Air Temperature Cooling - Minimum - DB 67°F (19°C) DB
Operation Conditions - Indoor Intake Air Temperature Heating - Minimum - DB 70°F (21°C) DB
Operation Conditions - Indoor Intake Air Temperature Heating - Minimum - WB 60°F (16°C) WB
Operation Conditions - Indoor Intake Air Temperature Cooling - Minimum - WB 57°F (14°C) WB
Operation Conditions - Indoor Intake Air Temperature Heating - Maximum - WB 67°F (19°C) WB
Operation Conditions - Indoor Intake Air Temperature Heating - Maximum - DB 80°F (27°C) DB, 67°F (19°C) WB
Operation Conditions - Outdoor Intake Air Temperature Cooling - Maximum - DB , WB 115°F (46°C) DB
Operation Conditions - Outdoor Intake Air Temperature Heating - Maximum - DB , WB 75°F (24°C) DB, 65°F (18°C) WB
Operation Conditions - Outdoor Intake Air Temperature Heating - Minimum - DB , WB -4°F (-20°C) DB, -5°F (-21°C) WB
Operation Conditions - Outdoor Intake Air Temperature Cooling - Maximum - DB 115°F (46°C) DB
Operation Conditions - Outdoor Intake Air Temperature Heating - Maximum - WB 65°F (18°C) WB
Operation Conditions - Outdoor Intake Air Temperature Heating - Minimum - DB -4°F (-20°C) DB
Operation Conditions - Outdoor Intake Air Temperature Heating - Minimum - WB -5°F (-21°C) WB
Operation Conditions - Outdoor Intake Air Temperature Cooling - Maximum - WB 115°F (46°C) DB
Operation Conditions - Outdoor Intake Air Temperature Heating - Maximum - DB 75°F (24°C) DB
Operation Conditions - Outdoor Intake Air Temperature Cooling- Minimum - DB 14°F (-10°C) DB
External Finish Unit: Galvanized sheets with gray heat insulation ; Grille: ABS resin Munsell 6.4Y 8.9/0.4
Voltage Indoor - Outdoor S1-S2 AC 208 / 230V
Voltage Indoor - Outdoor S2-S3 DC 12-24V

Mitsubishi Electric HVAC
3400 Lawrenceville Suwanee Rd.
Suwanee,  GA USA 30024 
Tel: (800) 687-1966
Fax: (800) 658-1458
Website: http://www.mehvac.com