M-Series Heat Pumps - Indoor Units (Multi Zone)_SEZ - SEZ-KD12NA4

M-Series Heat Pumps - Indoor Units (Multi Zone)_SEZ


Model Number: #SEZ-KD12NA4

Concealed horizontal ducted unit for applications with short duct runs.  SEZ units provide comfort and efficiency while staying hidden either in the ceiling or beneath the floor. Rated capacities range from 8,100-17,200 Btu/h.


Features
  • Quiet operation as low as 23 dBA
  • Ultra thin body: 7-7/8" high
  • Built-in drain mechanism for condensate removal; lifts to 21-11/16"
  • Air filter is included with indoor unit
  • Automatic fan speed control
  • PAR-21MAA wired remote controller is included
  • Indoor unit powered from outdoor unit using A-Control
  • Automatic fan speed control
  • Auto restart following a power outage
  • Limited warranty: five years on parts and defects and seven years on compressors


Power Supply Phase, Cycle, Voltage 1 Phase, 60Hz, 208/230V *4
Cooling Rated Capacity 11500 Btu/h (3.37 kW) *1
Cooling Capacity Range 3800 - 13300 BTU/h (1.1 - 3.9 kW)
Cooling Total Input 920 W (0.900 kW)
Cooling Energy Efficiency SEER 16
Cooling Sensible Heat Factor 0.76
Cooling Moisture Removal Pints/H 2.4
Cooling EER 12.5
Heating at 47° F Rated Capacity 13600 Btu/h (4 kW) *2
Heating at 47° F Capacity Range 4800 - 16400 Btu/h (1.4 - 4.8 kW)
Heating at 47° F Total Input 1140 W
Heating at 47° F HSPF (Region IV) 10
Heating at 47° F COP 3.5 Btu/Btu
Heating at 17° F Maximum Capacity 9000 Btu/h (2.6 kW)
Heating at 17° F COP 2.88 Btu/Btu
Heating at 17° F Total Input 920 W
Heating at 17° F Rated Capacity 9000 Btu/h (2.6 kW) *3
Minimum Circuit Ampacity MCA 1 Ampere
Recommended Fuse/Breaker Size 15 Ampere
Refrigerant Type R410A
Fan Fan Motor - F.L.A. 0.57 F.L.A
External Static Pressure 0.02 -0.06-0.14 -0.20 In. WG (5 -15-35 -50 Pa)
Airflow Cooling : DRY 247-317-388 CFM (7-9-11 m³/min)
Airflow Cooling : WET 222-285-349 CFM (6-8-10 m³/min)
Airflow Heating : WET 222-285-349 CFM (6-8-10 m³/min)
Sound Pressure Level 23-28-33 dB(A)
Dimensions H x W x D Height 7-7/8 Inches (200 mm)
Dimensions H x W x D Width 39 Inches (990 mm)
Dimensions H x W x D Depth 27-9/16 Inches (700 mm)
Refrigerant Pipe Size O.D. Gas (Low Pressure) 3/8 Inch (9.52 mm)
Refrigerant Pipe Size O.D. Liquid (High Pressure) 1/4 Inch (6.35 mm)
Field Drainpipe Size O.D. 1-1/4 Inches (32 mm)
Refrigerant Piping Connection Method Indoor / Outdoor Flared / Flared
Operation Conditions - Indoor Intake Air Temperature Cooling - Maximum - DB , WB 90°F (32°C) DB , 73°F (23°C) WB
Operation Conditions - Indoor Intake Air Temperature Cooling - Minimum - DB , WB 67°F (19°C) DB , 57°F (14°C) WB
Operation Conditions - Indoor Intake Air Temperature Heating - Maximum - DB , WB 80°F (27°C) DB, 67°F (19°C) WB
Operation Conditions - Indoor Intake Air Temperature Heating - Minimum - DB , WB 70°F (21°C) DB, 60°F (16°C) WB
Operation Conditions - Indoor Intake Air Temperature Heating - Maximum - DB 80°F (27°C) DB, 67°F (19°C) WB
Operation Conditions - Indoor Intake Air Temperature Heating - Maximum - WB 67°F (19°C) WB
Operation Conditions - Indoor Intake Air Temperature Cooling - Minimum - WB 57°F (14°C) WB
Operation Conditions - Indoor Intake Air Temperature Heating - Minimum - WB 60°F (16°C) WB
Operation Conditions - Indoor Intake Air Temperature Heating - Minimum - DB 70°F (21°C) DB
Operation Conditions - Indoor Intake Air Temperature Cooling - Minimum - DB 67°F (19°C) DB
Operation Conditions - Indoor Intake Air Temperature Cooling - Maximum -WB 73°F (23°C) WB
Operation Conditions - Indoor Intake Air Temperature Cooling - Maximum - DB 90°F (32°C) DB
Operation Conditions - Outdoor Intake Air Temperature Cooling - Maximum - DB , WB 115°F (46°C) DB
Operation Conditions - Outdoor Intake Air Temperature Heating - Maximum - DB , WB 75°F (24°C) DB, 65°F (18°C) WB
Operation Conditions - Outdoor Intake Air Temperature Heating - Minimum - DB , WB -4°F (-20°C) DB, -5°F (-21°C) WB
Operation Conditions - Outdoor Intake Air Temperature Heating - Maximum - DB 75°F (24°C) DB
Operation Conditions - Outdoor Intake Air Temperature Cooling- Minimum - DB 14°F (-10°C) DB
Operation Conditions - Outdoor Intake Air Temperature Cooling - Maximum - WB 115°F (46°C) DB
Operation Conditions - Outdoor Intake Air Temperature Heating - Minimum - WB -5°F (-21°C) WB
Operation Conditions - Outdoor Intake Air Temperature Heating - Minimum - DB -4°F (-20°C) DB
Operation Conditions - Outdoor Intake Air Temperature Heating - Maximum - WB 65°F (18°C) WB
Operation Conditions - Outdoor Intake Air Temperature Cooling - Maximum - DB 115°F (46°C) DB
External Finish Galvanized-Steel Sheets
Voltage Indoor - Outdoor S2-S3 DC 12-24V
Voltage Indoor - Outdoor S1-S2 AC 208 / 230V