M-Series Heat Pumps - Indoor Units (Multi Zone)_MFZ Model Number: #MFZ-KA09NA Floor-mounted indoor unit mounts on the floor or up to 5" above the floor and has front panel access to the filter for ease of cleaning.  It is perfect for difficult areas that may be smaller or don't have usable space...

MasterFormat: Decentralized HVAC Equipment | Decentralized Unitary HVAC Equipment



Mitsubishi Electric HVAC
3400 Lawrenceville Suwanee Rd.
Suwanee, GA 30024
Tel: (800) 687-1966
Fax: (800) 658-1458

http://www.mehvac.com

Request More Info

DOWNLOADS

Related Products

Overview



M-Series Heat Pumps - Indoor Units (Multi Zone)_MFZ - MFZ-KA09NA

M-Series Heat Pumps - Indoor Units (Multi Zone)_MFZ


Model Number: #MFZ-KA09NA

Floor-mounted indoor unit mounts on the floor or up to 5" above the floor and has front panel access to the filter for ease of cleaning.  It is perfect for difficult areas that may be smaller or don't have usable space on the walls. Rated capacities range from 9,000-18,000 Btu/h.


Features
  • Provides cooling and heating in a wide range of capacities
  • Standard Hybrid Catechin pre-filter and Anti-allergy Enzyme filters are included with indoor unit
  • Choice of fan speeds: Low, Medium, High, and Super High; Auto fan speed control also included
  • Quiet operation
  • Bottom supply outlet operates in heat mode
  • Wireless remote controller is included; PAR-21MAA wired remote controller can be installed as an option
  • Indoor unit powered from outdoor unit using A-Control
  • Auto restart following a power outage
  • Unit can be recessed mounted into wall
  • For use with the MXZ series only


Power Supply Phase, Cycle, Voltage 1 Phase, 60Hz, 208/230V *3
Cooling Rated Capacity 9000 Btu/h (2.64 kW) *1
Heating at 47° F Rated Capacity 10900 Btu/h (3.2 kW) *2
Minimum Circuit Ampacity MCA 1 Ampere
Recommended Fuse/Breaker Size 15 Ampere
Refrigerant Type R410A
Airflow Cooling : DRY 169-205-251-314 CFM (5-6-7-9 m³/min)
Airflow Cooling : WET 163-197-241-303 CFM (5-6-7-9 m³/min)
Sound Pressure Level Heating 40-35-30-25 dB(A)
Sound Pressure Level Cooling 40-35-30-25 dB(A)
Dimensions H x W x D Height 23-5/8 Inches (600 mm)
Dimensions H x W x D Width 27-9/16 Inches (700 mm)
Dimensions H x W x D Depth 7-7/8 Inches (200 mm)
Refrigerant Pipe Size O.D. Gas (Low Pressure) 3/8 Inch (9.52 mm)
Refrigerant Pipe Size O.D. Liquid (High Pressure) 1/4 Inch (6.35 mm)
Field Drainpipe Size O.D. 5/8 Inch (15.88 mm)
Refrigerant Piping Connection Method Indoor / Outdoor Flared / Flared
Operation Conditions - Indoor Intake Air Temperature Cooling - Maximum - DB , WB 90°F (32°C) DB , 73°F (23°C) WB
Operation Conditions - Indoor Intake Air Temperature Cooling - Minimum - DB , WB 67°F (19°C) DB , 57°F (14°C) WB
Operation Conditions - Indoor Intake Air Temperature Heating - Maximum - DB , WB 80°F (27°C) DB, 67°F (19°C) WB
Operation Conditions - Indoor Intake Air Temperature Heating - Minimum - DB , WB 70°F (21°C) DB, 60°F (16°C) WB
Operation Conditions - Indoor Intake Air Temperature Cooling - Minimum - WB 57°F (14°C) WB
Operation Conditions - Indoor Intake Air Temperature Heating - Maximum - DB 80°F (27°C) DB, 67°F (19°C) WB
Operation Conditions - Indoor Intake Air Temperature Heating - Maximum - WB 67°F (19°C) WB
Operation Conditions - Indoor Intake Air Temperature Cooling - Maximum - DB 90°F (32°C) DB
Operation Conditions - Indoor Intake Air Temperature Cooling - Maximum -WB 73°F (23°C) WB
Operation Conditions - Indoor Intake Air Temperature Cooling - Minimum - DB 67°F (19°C) DB
Operation Conditions - Indoor Intake Air Temperature Heating - Minimum - DB 70°F (21°C) DB
Operation Conditions - Indoor Intake Air Temperature Heating - Minimum - WB 60°F (16°C) WB
Operation Conditions - Outdoor Intake Air Temperature Cooling - Maximum - DB , WB 115°F (46°C) DB
Operation Conditions - Outdoor Intake Air Temperature Heating - Maximum - DB , WB 75°F (24°C) DB, 65°F (18°C) WB
Operation Conditions - Outdoor Intake Air Temperature Heating - Minimum - DB , WB 6°F (-14°C) DB, 5°F (-15°C) WB
Operation Conditions - Outdoor Intake Air Temperature Cooling - Maximum - DB 115°F (46°C) DB
Operation Conditions - Outdoor Intake Air Temperature Heating - Maximum - WB 65°F (18°C) WB
Operation Conditions - Outdoor Intake Air Temperature Heating - Minimum - DB 6°F (-14°C) DB
Operation Conditions - Outdoor Intake Air Temperature Heating - Minimum - WB 5°F (-15°C) WB
Operation Conditions - Outdoor Intake Air Temperature Cooling- Minimum - DB 14°F (-10°C) DB
Operation Conditions - Outdoor Intake Air Temperature Heating - Maximum - DB 75°F (24°C) DB
External Finish Munsell 1.0Y 9.2 / 0.2
Voltage Indoor - Outdoor S1-S2 AC 208 / 230V
Voltage Indoor - Outdoor S2-S3 DC 12-24V