Mitsubishi Electric HVAC - CITY MULTI VRF Heat Pumps - Outdoor Units_K-Generation Y-Series-PUHY-P216TSKMU-A (-BS)

CITY MULTI VRF Heat Pumps - Outdoor Units_K-Generation Y-Series-PUHY-P216TSKMU-A (-BS)


MasterFormat: Decentralized HVAC Equipment | Decentralized Unitary HVAC Equipment



Mitsubishi Electric HVAC
3400 Lawrenceville Suwanee Rd.
Suwanee, GA 30024
Tel: (800) 687-1966
Fax: (800) 658-1458

http://www.mehvac.com

Request More Info

DOWNLOADS

Related Products

Overview



CITY MULTI VRF Heat Pumps - Outdoor Units_K-Generation Y-Series - PUHY-P216TSKMU-A (-BS)

CITY MULTI VRF Heat Pumps - Outdoor Units_K-Generation Y-Series


Model Number: #PUHY-P216TSKMU-A (-BS)

Y-Series outdoor units are flexible enough to cool or heat up to 50 individual zones, maximizing building design options. The modular unit design features a small footprint and low operating sound.


Features
  • Cools or heats up to 50 individual zones
  • Available sizes: 6-30 tons
  • Available in both 208/230V and 460V
  • Maximum operating sound: 65 dB(A) for 30 ton condenser
  • Cooling to -10° F with optional low ambient kit
  • Uses T-branches and headers to provide piping design flexibility
  • INVERTER-driven compressor for outstanding performance and optimized energy usage
  • Maximum pipe length: 3,280 feet
  • Connects to CITY MULTI indoor units; controlled via CITY MULTI Controls Network (CMCN)
  • External finish: Pre-coated galvanized-steel with thermoset polyester-resin


Compressor Operating Range 8% to 100%
Compressor Type x Quantity Inverter scroll hermetic compressor x 1 / Inverter scroll hermetic compressor x 1
Compressor Lubricant MEL32
Compressor Starting method Inverter
Power Source Voltage, Phase, Cycle 208 / 230V, 3 phase, 60Hz
Cooling Capacity (Nominal) 216000 Btu/h (63.3 kW) *1
Cooling Power Input (Nominal) 16.9 kW *3
Heating Capacity (Nominal) 243000 Btu/h (63 kW) *1
Heating Power Input (Nominal) 19.26 kW *3
Piping Diameter Liquid (High Pressure) From Twinning Kit to First Joint or Header (Brazed) 5/8 Inch (15.88 mm) Brazed
Piping Diameter Gas (Low Pressure) From Twinning Kit to First Joint or Header (Brazed) 1-1/8 Inches (28.58 mm) Brazed
Set Model With One PUHY-P120TKMU-A (-BS) and One PUHY-P96TKMU-A (-BS)
Minimum Circuit Ampacity MCA 45/42 / 34/31 Ampere *3
Maximum fuse size (time delay) MOCP 60 / 50 Ampere *3
Recommended Fuse/Breaker Size 50 / 35 Ampere *3
Refrigerant Type R410A x 26 lbs + 1 oz (11.8 kg) / R410A x 26 lbs + 1 oz (11.8 kg)
Fan Airflow Rate 11300 CFM (320 m³/min) / 6200 CFM (175 m³/min)
Fan Type x Quantity Propeller fan x 2 / Propeller fan x 1
Fan Control, Driving mechanism Inverter-control, Brushless DC motor
External Static Pressure 0.12 or 0.24"WG external static pressure ; factory set to 0"WG
Sound Pressure Level (measured in anechoic room) 62.5 dB(A)
Indoor unit connectable Total capacity 50~130% of outdoor unit capacity
Indoor unit connectable Model (Quantity) P06~P96/2~46
Operating Temperature Range Cooling (Outdoor) 23~115°F(-5~46°C) D.B. **
Operating Temperature Range Heating (Outdoor) -4~60°F(-20~15.5°C) W.B.
External Finish Pre-coated galvanized steel sheet (+powder coating for -BS type)
Max. Total Refrigerant Line Length 3280 Ft. (1000 m)
Max. Refrigerant Line Length (Between ODU & IDU) 541 Ft. (165 m)
Max. Control Wiring Length 1650 Ft. (503 m)
Protection Device High Pressure Protection High pressure sensor, High pressure switch at 4.15 MPa (601 psi)
Protection Device Inverter Circuit (Comp. / Fan) Over-current protection
Protection Device Fan Motor Thermal switch
AHRI Ratings EER (Ducted/Non-Ducted) 12.3/12.3
AHRI Ratings IEER (Ducted/Non-Ducted) 18.9/18.6
AHRI Ratings COP (Ducted/Non-Ducted) 3.65/3.56
Heat Exchanger Salt-resistant cross fin & copper tube

Mitsubishi Electric HVAC
3400 Lawrenceville Suwanee Rd.
Suwanee,  GA USA 30024 
Tel: (800) 687-1966
Fax: (800) 658-1458
Website: http://www.mehvac.com

Sweets app for Revit – Learn More