Mitsubishi Electric HVAC - CITY MULTI VRF - Water Source_L-Generation WR2-Series-PQRY-P96TLMU-A

DOWNLOADS
CITY MULTI VRF - Water Source_L-Generation WR2-Series Model Number: #PQRY-P96TLMU-A Power Source Voltage, Phase, Cycle 208 / 230V, 1-phase, 60Hz Cooling Capacity (Nominal) 96000 Btu/h (28.1 kW) *1

Category: heat recovery | water source energy recovery | water source energy recovery equipment...

MasterFormat: Central HVAC Equipment | Packaged Outdoor HVAC Equipment | Decentralized Unitary HVAC Equipment...



Mitsubishi Electric HVAC
3400 Lawrenceville Suwanee Rd.
Suwanee, GA 30024
Tel: (800) 687-1966
Fax: (800) 658-1458

http://www.mehvac.com

Request More Info

DOWNLOADS

Related Products

Overview



CITY MULTI VRF - Water Source_L-Generation WR2-Series - PQRY-P96TLMU-A

CITY MULTI VRF - Water Source_L-Generation WR2-Series


Model Number: #PQRY-P96TLMU-A



Power Source Voltage, Phase, Cycle 208 / 230V, 1-phase, 60Hz
Cooling Capacity (Nominal) 96000 Btu/h (28.1 kW) *1
Heating Capacity (Nominal) 108000 Btu/h (31.7 kW) *1
Heating Power Input (Nominal) 6.18 kW *1
Minimum Circuit Ampacity MCA 19/17 Ampere
Maximum Overcurrent Protection MOP 30/25 Ampere
Refrigerant Type R410A
Compressor Type Inverter scroll hermetic compressor
Compressor Starting method Inverter
Compressor Motor Output 6.2 kW
Compressor Crankcase Heater 0.051 (230V)
Compressor Lubricant MEL32
Sound Pressure Level (measured in anechoic room) 49 dB(A)
Dimensions H x W x D Height 43-5/16 Inches (1100 mm)
Dimensions H x W x D Width 34-11/16 Inches (880 mm)
Dimensions H x W x D Depth 21-11/16 Inches (550 mm)
Indoor unit connectable Total capacity 50~150% of heatsource unit capacity
Indoor unit connectable Model (Quantity) P06~P96 / 1~24
Refrigerant Pipe Dimensions Liquid (High Pressure) 3/4 Inch (19.05 mm) Brazed
Refrigerant Pipe Dimensions Gas (Low Pressure) 7/8 Inch (22.2 mm) Brazed
Water volume in plate 1.32 Gallons (5 Liters)
Water pressure Maximum 290 psi (2 MPa)
Circulating Water Water Flow Rate 25.4 GPM (5.76m³/h)
Circulating Water Operation Volume Range 13.2 ~ 31.7 GPM (3.0 ~ 7.2 m³/h)
Circulating Water Pressure Drop 17 kPa (2.47psi)
Operating Water Temperature Range Cooling 50° F (10° C) ~ 113° F (45° C) *
Operating Water Temperature Range Heating 50° F (10° C) ~ 113° F (45° C) *
Operating Temperature Range Cooling (Indoor) 59~75° F (15~24° C) D.B.
Operating Temperature Range Heating (Indoor) 59~81° F (15~27° C) D.B.
External Finish Acrylic painted steel plate
Protection Device Compressor Over-heat protection
Protection Device High Pressure Protection High pressure sensor, High pressure switch at 4.15 MPa (601 psi)
Protection Device Inverter circuit (COMP. / FAN) Over-heat protection, Over-current protection

Mitsubishi Electric HVAC
3400 Lawrenceville Suwanee Rd.
Suwanee,  GA USA 30024 
Tel: (800) 687-1966
Fax: (800) 658-1458
Website: http://www.mehvac.com

Sweets app for Revit – Learn More