Mitsubishi Electric HVAC - CITY MULTI VRF - Air Source_L-Generation R2-Series-PURY-P168YSLMU-A (-BS)

CITY MULTI VRF - Air Source_L-Generation R2-Series Model Number: #PURY-P168YSLMU-A (-BS) The L-Generation Air Source VRF Outdoor Units represent the latest in a long line of innovations from Mitsubishi Electric Cooling & Heating. Featuring HexiCoil™ aluminum flat tube heat exchanger technology,...


Category: air source energy recovery | air source energy recovery equipment | air-source energy recovery...

MasterFormat: Central HVAC Equipment | Packaged Outdoor HVAC Equipment | Decentralized Unitary HVAC Equipment...



Mitsubishi Electric HVAC
3400 Lawrenceville Suwanee Rd.
Suwanee, GA 30024
Tel: (800) 687-1966
Fax: (800) 658-1458

http://www.mehvac.com

Request More Info

DOWNLOADS

Related Products

Overview



CITY MULTI VRF - Air Source_L-Generation R2-Series - PURY-P168YSLMU-A (-BS)

CITY MULTI VRF - Air Source_L-Generation R2-Series


Model Number: #PURY-P168YSLMU-A (-BS)

The L-Generation Air Source VRF Outdoor Units represent the latest in a long line of innovations from Mitsubishi Electric Cooling & Heating. Featuring HexiCoil™ aluminum flat tube heat exchanger technology, the L-Generation offers best-in-class efficiency ratings across all categories improving on the already highly efficient variable refrigerant flow technology. With single modules up to 14 tons and an optimized footprint, the L-Generation Air Source Outdoor Unit is the perfect fit for any commercial application.


Features
  • Best-in-class efficiency ratings.
  • Single modules up to 14 tons with the ability to combine modules for systems up to 28 tons.
  • HexiCoil™ aluminum flat tube, zinc-coated heat exchanger technology eliminates copper tubing from the condenser coil. Featuring turbulated tube walls and a unique fin shape for water shedding capability, the HexiCoil™ condenser coil ensures maximum heat transfer through an optimized cross section.
  • Up to 50% less refrigerant charge required than previous generations.
  • Floating/adjustable evaporation temperature in swing seasons, saving energy while maintaining exceptional performance.
  • Automated and dynamic refrigerant temperature control.
  • Optimized refrigerant circuit and component design for improved flow distribution, allowing maximum energy transfer with minimal power input.
  • Superior high-ambient cooling performance with guaranteed operation to 126°F.
  • Extended 10-year parts and compressor warranty available.


Compressor Operating Range 7% to 100%
Compressor Type x Quantity Inverter scroll hermetic compressor x 1
Compressor Lubricant MEL32
Compressor Starting method Inverter
Power Source Voltage, Phase, Cycle 460V, 3-Phase, 60Hz
Cooling Capacity (Nominal) 168000 Btu/h (49.2 kW) *1
Cooling Power Input (Nominal) 13.60 kW *3
Heating Capacity (Nominal) 188000 Btu/h (55.1 kW) *1
Heating Power Input (Nominal) 14.94 kW *3
Piping Diameter Liquid (High Pressure) From Twinning Kit to Indoor Units (Brazed) 7/8 Inch (22.2 mm) Brazed
Piping Diameter Gas (Low Pressure) From Twinning Kit to Indoor Units (Brazed) 1-1/8 Inches (28.58 mm) Brazed
Set Model With One PURY-P96YLMU-A (-BS) and One PURY-P72YLMU-A (-BS)
Minimum Circuit Ampacity MCA 15 - 11 Ampere *3
Maximum Overcurrent Protection MOP 25 - 20 Ampere *3
Refrigerant Type R410A x 17 lbs + 10 oz (8.0 kg) / R410A x 13 lbs + 3 oz (6.0 kg)
Fan Airflow Rate 6550 cfm (175 m³/min) / 6550 cfm (185 m³/min)
Fan Control, Driving mechanism Inverter-control, Brushless DC motor
Fan Type x Quantity Propeller fan x 1 / Propeller fan x 1
External Static Pressure 0.12 or 0.24"WG external static pressure; factory set to 0"WG
Sound Pressure Level (measured in anechoic room) 61 dB(A)
Indoor unit connectable Total capacity 50~150% of outdoor unit capacity
Indoor unit connectable Model (Quantity) P06~P96/1~42
Operating Temperature Range Cooling (Outdoor) 23~126°F(-5~52°C) D.B. **
Operating Temperature Range Heating (Outdoor) W.B. -4~60° F (-20~15.5° C)
External Finish Pre-coated galvanized steel sheet (+powder coating for -BS type)
Max. Total Refrigerant Line Length 1969 Ft. (600 m)
Max. Refrigerant Line Length (Between ODU & IDU) 541 Ft. (165 m)
Max. Control Wiring Length 1650 Ft. (503 m)
Heat Exchanger Salt-resistant cross fin & aluminum tube
Protection Device High Pressure Protection High pressure sensor, High pressure switch at 4.15 MPa (601 psi)
Protection Device Inverter Circuit (Comp. / Fan) Over-current protection
Protection Device Fan Motor Thermal switch
AHRI Ratings EER (Ducted/Non-Ducted) 12.1 / 12.9
AHRI Ratings IEER (Ducted/Non-Ducted) 19.4 / 19.1
AHRI Ratings COP (Ducted/Non-Ducted) 3.63 / 3.52
AHRI Ratings SCHE (Ducted/Non-Ducted) 20.0 / 22.6

Mitsubishi Electric HVAC
3400 Lawrenceville Suwanee Rd.
Suwanee,  GA USA 30024 
Tel: (800) 687-1966
Fax: (800) 658-1458
Website: http://www.mehvac.com

Sweets app for Revit – Learn More