Compressor |
Operating Range |
16% to 100% |
Compressor |
Type x Quantity |
Inverter scroll hermetic compressor |
Compressor |
Lubricant |
MEL32 |
Compressor |
Starting method |
Inverter |
Power Source |
Voltage, Phase, Cycle |
208 / 230V, 3-Phase, 60Hz |
Cooling |
Capacity (Nominal) |
96000 Btu/h (28.1 kW) *1 |
Cooling |
Power Input (Nominal) |
7.05 kW *1 |
Heating |
Capacity (Nominal) |
108000 Btu/h (31.7 kW) *1 |
Heating |
Power Input (Nominal) |
8.28 kW *1 |
Minimum Circuit Ampacity |
MCA |
34 / 31 Ampere |
Maximum fuse size (time delay) |
MOCP |
50 Ampere |
Recommended Fuse/Breaker Size |
|
35 Ampere |
Refrigerant |
Type |
R410A x 26 lbs + 1 oz (11.8 kg) |
Fan |
Airflow Rate |
6200 CFM (175 m³/min) |
Fan |
Type x Quantity |
Propeller fan x 1 |
Fan |
Control, Driving mechanism |
Inverter-control, Brushless DC motor |
External Static Pressure |
|
0.12 or 0.24"WG external static pressure;
factory set to 0"WG |
Sound Pressure Level |
(measured in anechoic room) |
58 dB(A) |
Dimensions H x W x D |
Height |
64-31/32 Inches (1650 mm) |
Dimensions H x W x D |
Width |
48-1/16 Inches (1220 mm) |
Dimensions H x W x D |
Depth |
29-5/32 Inches (740 mm) |
Indoor unit connectable |
Total capacity |
50~150% of outdoor unit capacity |
Indoor unit connectable |
Model (Quantity) |
P06~P96/1~24 |
Piping Diameter Liquid (High Pressure) |
From Twinning Kit to Indoor Units (Brazed) |
3/4 Inch (19.05 mm) Brazed |
Piping Diameter Gas (Low Pressure) |
From Twinning Kit to Indoor Units (Brazed) |
7/8 Inch (22.2 mm) Brazed |
Operating Temperature Range |
Cooling (Outdoor) |
D.B. 23~115° F (-5~46° C) ** |
Operating Temperature Range |
Heating (Outdoor) |
W.B. -4~60° F (-20~15.5° C) |
External Finish |
|
Pre-coated galvanized steel sheet |
Max. Total Refrigerant Line Length |
|
1804 Ft. (550 m) |
Max. Refrigerant Line Length |
(Between ODU & IDU) |
541 Ft. (165 m) |
Max. Control Wiring Length |
|
1650 Ft. (503 m) |
Protection Device |
High Pressure Protection |
High pressure sensor, High pressure switch at 4.15 MPa (601 psi) |
Protection Device |
Inverter Circuit (Comp. / Fan) |
Over-current protection |
Protection Device |
Fan Motor |
Thermal switch |
AHRI Ratings |
EER (Ducted/Non-Ducted) |
12.2 / 13.6 |
AHRI Ratings |
IEER (Ducted/Non-Ducted) |
19.7 / 20.9 |
AHRI Ratings |
COP (Ducted/Non-Ducted) |
3.64 / 3.71 |
AHRI Ratings |
SCHE (Ducted/Non-Ducted) |
17.4 / 23.5 |
Heat Exchanger |
|
Salt-resistant cross fin & copper tube |