Foster™ -Foster® 30-35 Tite-Fit™ Coating

DOWNLOADS

FOSTER ® TITE-FIT ™ COATING Foster ® Tite- FitTM Coating is a flexible, low odor, fire resistive, high solids, vapor barrier finish for most types of rigid thermal insulation, except Polystyrene. Tite-Fit Coating is formulated for both indoor and outdoor use on commercial type applic


Category: fiberboard insulation | plumbing insulation | polyurethane foam...

MasterFormat: Board Insulation | High-Performance Coatings | Fire-Retardant Coatings...


Related Products

Overview


Foster® 30-35 Tite-Fit™ Coating



FOSTER ® TITE-FIT COATING

Foster ® Tite- FitTM Coating is a flexible, low odor, fire resistive, high solids, vapor barrier finish for most types of rigid thermal insulation, except Polystyrene.

Tite-Fit Coating is formulated for both indoor and outdoor use on commercial type applications. It is a solvent based coating with a mild "paint type" odor, designed for use on pipes, vessels, ducts and equipment operating below ambient temperatures.

Tite-Fit Coating is also used for vapor sealing ASJ, FRK, and FSK jackets and board facings at joints, laps, and over staple and weld pin punctures. It exhibits good adhesion to these jacketing materials when used as a protective coating.

Tite-Fit Coating meets the requirements of Military Specification MIL-PRF-19565C, Type II.

Tite-Fit Coating is produced under the Classification and Follow-up Service of Underwriter's Laboratories, Inc.

Tite-Fit Coating meets NFPA 90A and 90B 25/50 requirements.

Tite-Fit Coating contains no asbestos, lead, mercury, or mercury compounds.

LIMITATIONS
Store and apply between 40°F (4°C) and 100°F (38°C). For best results, select Elastolar 95-44 for insulation joint sealing under TITE-FIT Coating. The solvent odor in this product may take several days to dissipate. When working in occupied or confined areas, the use of 30-80 or 30-90, water based products, is recommended. Always test plastic materials for compatibility when using a solvent based product. Make certain this product is completely dry and the area free from solvent odor if food is involved. Outdoor horizontal surfaces must always drain completely. A pitch of at least 1/2 inch per foot (4 cm/m) is required. After long term outdoor exposure 30-35 may weather to an off-white or buff color.


COLOR:
White

APPLICATION CONSISTENCY:
Brush, glove, or spray

AVERAGE WEIGHT/U.S. GALLON (ASTM D 1475):
9.8 pounds (1.17 Kg/l)

AVERAGE NON-VOLATILE (ASTM D 1644):
44% by volume (62% by weight)

COVERAGE (FSTM 72):
(Subject to the nature of material being coated). Wet coverages shown below are for smooth non-porous surfaces. Porous or rough surfaces will require higher gallonage to attain required dry thickness. 4 gallons per 100 square feet minimum (1.6 l/m2) 0.064 in. wet thickness (1.6 mm)

DRYING TIME 73°F (23°C) 50% RH (ASTM D 1640):
Set to Touch: 8 hours
Dry Through: 24 hours

SERVICE TEMPERATURE LIMITS (FSTM 70):
(Temperature at coated surface) 0°F to 180°F (-18°C to 82°C)

WATER VAPOR PERMEANCE (ASTM F 1249):
0.05 perm at 0.035 inch dry film thickness (0.03 metric perm at 0.9 mm).

WET FLAMMABILITY (ASTM D 93)
Flash point 100°F (38°C)

SURFACE BURNING CHARACTERISTICS (ASTM E 84):
Flame Spread: 20
Smoke Developed: 10
Tested at coverage rate of 50 square feet per gallon (1.2 m2/l).
Applied to 1/4 inch (6.4 mm) inorganic reinforced cement board.


TM TradeMark of Specialty Construction Brands, Inc.

Visit us on the web at www.fosterproducts.com