Ceco Door
9159 Telecom Drive
Milan, TN 38358
Phone: (731) 686-8345 
Fax: (731) 686-4211 
http://www.cecodoor.com/contact.htm
e-mail: marketing@cecodoor.com


Temperature Rated Fire Doors

Ceco manufacturers two types of temperature-rise rated fire doors:

  • The Medallion 450 Degree is a temperature -rise rated door which will allow the unexposed side of the door to reach only 450 degrees during the first 30 minutes of fire testing
  • The Fuego 250 Degree temperature-rise rated door will allow the unexposed side of the door to only reach a maximum of 250 degrees during the first 30 minutes of the fire test.

Medallion® 450° Fire Doors
Classified for openings rated up to 1-1/2 hours (90 minute) which have 450° temperature rise restrictions

Fire label    
T
1/3 hour
20 minute
C
3/4 hour
45 minute
B
1-1/2 hour
90 minute
A
3 hour
180 minute

A temperature rise rating is not a requirement for qualification as a labeled fire door, but, when required, doors are built to meet this criteria.

Ceco manufactures two types of temperature-rise rated fire doors.

Medallion 450° is a temprature-rise rated door which allows the unexposed side of the door to reach a maximum of 450° during the first 30 minutes of testing.

Fuego is a 250° temperature-rise rated door which will allow the unexposed side of the door to reach a maximum of 250° during the first 30 minutes of testing.

Temperature-rise rated Fire Doors allow people to pass by the door safely when fire is on the other side. When an opening is required to retard the transmission of heat from one area to an ajacent area, a temperature-rise rated door is required. These doors are typically required in locations such as stairwell access doors, electrical control rooms, paint storage, etc. Temperature-rise designations indicate the maximum rise in temperature above ambient on the non-fire side of the door during the first 30 minutes of exposure in a standard fire test.

Note: Always reference the most recent edition of ANSI NFPA 80 - Fire Doors and Fire Windows


Medallion Fire Doors

Medallion Fire Doors. Vertically Steel Stiffened core. UL, WH or FM label. Classified for openings rated up to three hours (Class A,B,C,D,E, and 20 minute) with optional 450 degree temperature restrictions. Tested and approved in accordance with UL 10b Ambient Fire Test and UBC 7-2 (97) Positive Pressure Fire Test, UL10C.



Available Options:

  • 20 gage (.08 mm) 18 gage (1.0 mm) or 16 gage (1.3 mm) vertical steel stiffeners
  • 12 gage (2.3 mm) closer reinforcement
  • A60 Galvanneled or G90 galvanized steel
  • Steel end channel filler cap
  • Flush welded glass lite trim kits
  • Factory applied ColorStyle® finish

Doors with a Vertically Steel Stiffened Core

Features:

  • Designed for high frequency, severe traffic openings
  • 1-3/4" (44.4 mm) custom construction
  • Seamless design
  • Rated for heavy-duty to maximum duty use
  • 22 gage steel stiffeners spaced 6" apart, welded to face sheets every 5"
  • Fully welded edge seams enhance strength and appearance
  • Fiberglass insulation to limit thermal and sound transmission
  • Inverted end channels welded to both face sheets
  • 7 gage (4.2 mm) steel hinge reinforcement